Usage:
STEP 1. Check For Actuator Travel
Test Procedure:
Crank the engine and check for Actuator Travel.
Expected Results:
Actuator movement to FUEL ON position.
STEP 2. Check Electronic Locomotive Control Box
Test Procedure:
Observe the diagnostic lamps which are visible through the lens on the control box lid.
Expected Results:
SHUTDOWN lamp ON. WHEEL SLIP and GENERATOR LOAD lamps may be ON or OFF depending on locomotive design. All other lamps OFF.
Fig. 1 SHUTDOWN LAMP ON
Fig. 2 BOX FAULT LAMP ON
Fig. 3 TURN CAL ADJ OUT
Fig. 4 CAL ADJ CORRECT
Fig. 5 TURN CAL ADJ IN
Fig. 6 PERSONALITY MODULE FAULT
STEP 3. Check Shutdown Lamp
Test Procedure:
Observe SHUTDOWN lamp while cranking engine.
Expected Results:
SHUTDOWN lamp goes OFF while cranking engine.
STEP 4. Check Fuel Shut-off Systems
Test Procedure:
Visually check any fuel shut-off systems connected between the control box and the actuator. Refer to system wiring diagram.
Expected Results:
All fuel shut-off systems are closed and do not limit current flow to actuator.
STEP 5. Check Rack Actuator Signals
Test Procedures:
Connect a digital multimeter (Caterpillar Service Tool 6V3030) to measure DC amps on the 2A scale. Use this between the engine harness and rack actuator connectors to measure the current to the rack actuator coil while cranking engine.
Expected Results:
Current to rack actuator is greater than 0.2A.
STEP 6. Manual Linkage Check
Test Procedure:
With engine stopped, manually move actuator lever and linkage to full FUEL ON position against stop screw.
Expected Results:
Linkage should move through full travel until it is against stop screw without binding or excessive force.
STEP 7. Check Actuator Oil Pressure Output
Test Procedure:
With engine stopped, remove the test pressure plug from actuator and install 6V2044 Test Pressure Gauge. Crank the engine and read pressure from test pressure gauge.
NOTE: For correct pressure range, see ELECTRIC GOVERNOR ACTUATOR SPECIFICATIONS in Service Procedure B.
Expected Results:
Specified oil pressure with constant output.
STEP 8. Measure Cranking RPM
Test Procedure:
Crank the engine and measure the cranking rpm.
Expected Results:
More than 75 rpm measured.
STEP 9. Check Actuator Oil Supply and Mechanical Drive
Test Procedure:
See Service Procedure B to check actuator functions that follow:
- A. Correct oil supply.
- B. Plugged drain.
- C. Oil too thin.
- D. Drive has rotation.
- E. Correct direction of rotation.
- F. Damage to Coupling or Splines.
- B. Plugged drain.
Engine compartment oil sump must be full, and suction line must be open and without air leaks (caused by faulty gaskets or loose fittings). Actuator oil drain must drain freely.
Expected Results:
To find problem with the actuator drive or oil circuit.
STEP 10. Check Personality Module CAL Switch
Test Procedure:
Remove the fitting covering the CAL switch on the Personality Module. (Fig. 1) Use a small screwdriver to turn the switch clockwise (away from the CAL marking). Replace the fitting covering the CAL switch. Observe the diagnostic lamps in the Locomotive Control box.
Expected Results:
The CAL ADJ (TURN CAL ADJ OUT, CAL ADJ CORRECT and TURN CAL ADJ IN) lamp codes are all OFF.
Fig. 1 PERSONALITY MODULE
STEP 11. Check Electronic Locomotive Control Box
Test Procedure:
Disconnect connector J1 (VE connector) from control box. Reconnect and observe the diagnostic indicator lamps.
Expected Results:
All lamps turn ON for 5 seconds. SHUTDOWN lamp remains ON.
STEP 12. Check Power to Electronic Control Box
Test Procedure:
Disconnect connector J1 (VE connector) from control box. Set a digital multimeter (Cat Service Tool 6V3030) on the 200 VDC scale and connect the probes to measure DC voltage. Use this to measure the DC voltage between pins 8 and 9 of connector J1 at the wiring harness.
Expected Results:
The voltage is greater than 24 VDC and less than 150 VDC.
STEP 13. Check Operator Shutdown Input
Test Procedure:
With the Locomotive Control box connected to the wiring harness, measure the DC voltage applied by the locomotive electrical system to the operator shutdown input (applied to connector J1 pin 12) with respect to the interface (-) battery voltage (applied to connector J1 pin 15). Also measure the interface (+) battery voltage (connector J1, pin 14) with respect to interface (-) battery voltage.
Expected Results:
The DC voltage applied to the operator shutdown input is within 8 VDC of the interface (+) battery voltage.
STEP 14 Check Notch Code Inputs
Test Procedure:
With the Locomotive Control box connected to both connectors (J1 and J2) and the engine being cranked, measure the DC voltage applied by the locomotive electrical system to the Notch Code Inputs (Connector J1, pins 16, 17, 18 and 19) with respect to the Interface (-) Battery Voltage (at Connector J1, pin 15). Also measure Interface (+) Battery Voltage (at Connector J1, pin 14) with respect to Interface (-) Battery Voltage.
Expected Results:
With "high" inputs (code "1's") defined as being within 8 VDC of the Interface (+) Battery Voltage, and "low" inputs (code "0's") defined as being less than 2 VDC with respect to Interface (-) Battery Voltage, the notch code does not correspond with the shutdown code.
STEP 15. Resistance Check of Actuator and Leads
Test Procedure:
Disconnect connector J2 from the Electronic Locomotive Control box. Measure the resistance between pins 1 and 2 of the wiring harness side of connector J2.
Expected Results:
Measured resistance should be between 30 and 40 ohms.
STEP 16. Actuator Coil Resistance Check
Test Procedure:
Disconnect wiring connector from actuator. Put a jumper across pins C and D of connector. Measure the actuator coil resistance across connector pins A and B. (See Service Procedure B fig. 2)
Expected Results:
Measured resistance to be between 30 to 40 ohms.
STEP 17. Actuator Lead Resistance Check
Test Procedure:
Measure resistance of each lead between: Pin A and harness connector J2 pin 1. Pin B and harness connector J2 pin 2.
Expected Results:
Measured resistance of each lead is less than 1 ohm.
STEP 18. Actuator Coil Resistance Check
Test Procedure:
Disconnect wiring connector from actuator. Put a jumper across pins C and D of connector. Measure the actuator coil resistance across connector pins A and B. (See Service Procedure B fig. 2)
Expected Results:
Measured resistance to be between 30 to 40 ohms.
STEP 19. Actuator Lead Resistance Check
Test Procedure:
With actuator connector disconnected, measure resistance between: Harness connector J2 pin 1 and harness connector J2 pin 2.
Expected Results:
Measured resistance is open circuit.