- Electric Power Generation:
- SR4 (S/N: 5CA1-UP; 5DA1-UP; 5EA1-UP; 5FA1-UP; 5GA1-UP; 5HA1-UP; 5JA1-UP; 5KA1-UP; 5LA1-UP; 5MA1-UP; 5NA1-UP; 5RA1-UP; 5TA1-UP; 5UA1-UP; 5VA1-UP; 5YA1-UP; 6BA1-UP; 6CA1-UP; 6DA1-UP; 6EA1-UP; 6FA1-UP; 6HA1-UP; 6JA1-UP; 6MA1-UP; 6NA1-UP; 6PA1-UP; 6WA1-UP; 2WD1-UP; 5TD1-UP; 8JF1-UP; 8KF1-UP; 8LF1-UP; 9EF1-UP; 9FF1-UP; 9GF1-UP; 6CG1-UP; 6DG1-UP; 6EG1-UP; 8HG1-UP; 9FG1-UP; 3KJ1-UP; 4SJ1-UP; 5NJ1-UP; 6EJ1-UP; 7AJ1-UP; 2MM1-UP; 3YM1-UP; 4LM1-UP; 5JM1-UP; 6JM1-UP; 6YR1-UP; 7YR1-UP; 8DR1-UP; 8ER1-UP; 9CR1-UP; 9DR1-UP; 1MS1-UP; 7RS1-UP; 7SS1-UP; 7TS1-UP; 7WS1-UP; 7XS1-UP; 7YS1-UP)
- SR4B (S/N: 6PK1-UP; 8GK1-UP; 7GM1-UP; 1BN1-UP; 3EN1-UP; 3GN1-UP; 3HN1-UP; 4WN1-UP; 5WN1-UP; 9EN1-UP; 8GW1-UP; 8EZ1-UP; 8LZ1-UP; 9AZ1-UP)
- XQ200 (S/N: LEA1-UP)
- SR4B (S/N: 6PK1-UP; 8GK1-UP; 7GM1-UP; 1BN1-UP; 3EN1-UP; 3GN1-UP; 3HN1-UP; 4WN1-UP; 5WN1-UP; 9EN1-UP; 8GW1-UP; 8EZ1-UP; 8LZ1-UP; 9AZ1-UP)
- Engine:
- 3306 (S/N: 66D1-UP; 70R1-UP)
- 3306B (S/N: B8D1-UP)
- 3408 (S/N: 67U1-UP; 78Z1-UP)
- 3408B (S/N: 67U1-UP; 78Z1-UP)
- 3408C (S/N: 67U1-UP; 78Z1-UP)
- 3412 (S/N: 9XF1-UP; 2WJ1-UP; 38S1-UP; 81Z1-UP)
- 3412C (S/N: BAK1-UP; 5FL1-UP; DJN1-UP; 9EP1-UP; TFT1-UP; BCW1-UP; RTY1-UP; 81Z1-UP)
- 3412E (S/N: TGC1-UP)
- 3508 (S/N: CAW1-UP; 23Z1-UP; 70Z1-UP)
- 3508B (S/N: 4GM1-UP; BGX1-UP)
- 3512 (S/N: 6PM1-UP; FDR1-UP; 24Z1-UP; 67Z1-UP)
- 3512B (S/N: BLF1-UP)
- 3516 (S/N: 4XF1-UP; 7KM1-UP; GZX1-UP; 25Z1-UP; 73Z1-UP)
- 3516B (S/N: GZT1-UP; GZY1-UP)
- D333C (S/N: 09A1-UP; 66D1-UP; 70R1-UP)
- D334 (S/N: 92B1-UP)
- D343 (S/N: 62B1-UP)
- G3406 (S/N: 4FD1-UP; R7E1-UP; KAR1-UP)
- G3408 (S/N: 6NB1-UP)
- G3412 (S/N: R7A1-UP; 7DB1-UP; KAP1-UP)
- G3508 (S/N: CPJ1-UP; CPS1-UP)
- G3512 (S/N: CRN1-UP)
- G3516 (S/N: ZBA1-UP; 25Z1-UP)
- G3516B (S/N: ZBB1-UP; ZBC1-UP)
- G3516C (S/N: GSB1-UP; GZZ1-UP)
- 3306B (S/N: B8D1-UP)
- Generator Set:
- 3406B GEN SET (S/N: 4PM1-UP)
- 3406C GEN SET (S/N: KPS1-UP)
- 3412C GEN SET (S/N: BAX1-UP)
- 3456 GEN SET (S/N: CCB1-UP; CBX1-UP)
- 3406C GEN SET (S/N: KPS1-UP)
- Industrial Engine:
- 3406 IND (S/N: 90U1-UP)
- 3412C IND (S/N: 38S1-UP)
Introduction
This Special Instruction will guide you through removing and replacing the CK-frame breakers with the P-frame breakers. This procedure is designed to utilize most of the existing components from the original factory installed system on the Generator Set. Certain circumstances such as replacing the shunt trip and auxiliary contact will require the replacement of the entire breaker.
Important Safety Information
Do not perform any procedure in this Special Instruction until you have read this Special Instruction and you understand this information. Use only proper tools and observe all precautions that pertain to the use of those tools. Failure to follow these procedures can result in personal injury. The following procedures should also be observed.
Work safely. Most accidents that involve product operation, maintenance, and repair are caused by failure to observe basic safety rules or precautions. An accident can often be avoided by recognizing potentially hazardous situations before an accident occurs.
A person must be alert to potential hazards. This person should also have the necessary training, skills, and tools in order to perform these functions properly.
Safety precautions and warnings are provided in this instruction and on the product. If these hazard warnings are not heeded, bodily injury or death could occur to you or to other persons. Caterpillar cannot anticipate every possible circumstance that might involve a potential hazard.
Therefore, the warnings in this publication and the warnings that are on the product are not all inclusive. Ensure that any tool, procedure, work method, or operating technique you use that is not recommended by Caterpillar is safe.
Ensure that the product will not be damaged or the product will not be made unsafe by the operation, lubrication, maintenance, or repair procedures used.
Do not operate or work on this machine unless you have read and understand the instructions and warnings in the Operation and Maintenance Manuals. Failure to follow the instructions or heed the warnings could result in injury or death. Contact your Cat dealer for replacement manuals. Proper care is your responsibility. |
Electrocution Hazard! Keep the machine and attachments a safe distance from electrical power. Stay clear 3 m (10 ft) plus twice the line insulator length. Read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions and warnings will cause serious injury or death |
Preparation for the Replacement
Note: In order to replace the circuit breaker, the Generator Set must already have a factory installed CK-frame breaker.
- Turn off the Generator Set. Lock out and tag out the Generator Set.
- Remove the breaker cover.
- Disconnect all power cables from the breaker.
Note: Ensure that the cables are properly marked for reinstallation.
- Remove the breaker from the bracket.
Note: The bracket may be removed along with breaker if desired. Disconnect all electrical accessories.
- Remove bus bars from breaker and retain for reinstallation on the new breaker.
Modifying the Bracket for the New P-Frame Breaker
- Refer to Table 1 for the correct circuit breaker group to replace the existing part number.
Show/hide table
Table 1 Existing Part Number     Replacement Part Number     104-7632     270-4534     104-7633     270-4535     104-7634     270-4536     104-7635     270-4537     105-6550     270-4534     112-3509     270-4543     112-3517     270-4543     126-6154     270-4590     183-1872     270-4608     183-1873     270-4609     183-1874     270-4610     183-1875     270-4611     198-1931     265-4714     201-0277     270-4614     201-0278     270-4615     201-0279     270-4616     201-0280     270-4617     201-0291     270-4599     201-0292     270-4668     201-0293     270-4621     201-0294     270-4622     205-8209     270-4537     300-1825     270-4534    
- Identify the location for the new holes to be drilled in the bracket. Refer to Illustration 1.
Illustration 1 | g02556241 |
(A) 65 mm (2.56 inch) (B) 26.3 mm (1.04 inch) (C) 66.3 mm (2.61 inch) (1) Existing holes (2) New holes |
- Mark and drill the new holes using a 6 mm (0.25 inch) drill bit.
- Touch up the new mounting holes with paint.
Modifying the Cover Group for the New P-Frame Breaker and Installing the New Breaker
- Remove the rubber boot from the cover (if equipped).
- The following procedure is applicable for all generator sets except generator number prefixes S/N:KAP, ; S/N:KAR, and ; S/N:KPS. For Generator Sets with serial number prefixes ; S/N:KAP, ; S/N:KAR, and ; S/N:KPS proceed to Step 6. All other prefixes must outline the new opening for the cover using the dimensions in Illustration 2.
Illustration 2 | g02518718 |
(D) 25 mm (1 inch) (3) Material to be removed (4) Existing breaker hole |
- Cut the new rectangular opening using the necessary tooling.
- Smooth the sharp edges and paint the area around the new opening.
- Mount the new P-frame breaker onto the modified bracket using the hardware provided with the new breaker. Reposition the mounting bracket to ensure that the cover is aligned with the front face of the breaker. Proceed to Step 10.
- If the Generator Sets have serial number prefix S/N:KAP, ; S/N:KAR, or ; S/N:KPS, identify which Illustration to use based on the dimensions of the opening. For a 98 mm (3.85 inch) x 132 mm (5.20 inch) opening use Illustration 4. For a 79 mm (3.11 inch) x 108.6 mm (4.28 inch) opening use Illustration 5, and for a 74 mm (2.91 inch) x 104.5 mm (4.11 inch) opening use Illustration 3.
Illustration 3 | g02540005 |
Configuration 1 (E) 190 mm (7.48 inch) (F) 57.8 mm (2.28 inch) (G) 212 mm (8.35 inch) (H) 101.4 mm (4 inch) (J) 74 mm (2.91 inch) (K) 104.5 mm (4.11 inch) (3) Material to be removed (4) Existing breaker hole |
Illustration 4 | g02540264 |
Configuration 2 (L) 190 mm (7.48 inch) (M) 46.3 mm (1.82 inch) (N) 212 mm (8.35 inch) (P) 80 mm (3.15 inch) (Q) 98 mm (3.85 inch) (R) 132 mm (5.20 inch) (3) Material to be removed (4) Existing breaker hole |
Illustration 5 | g02540299 |
Configuration 3 (S) 190 mm (7.48 inch) (T) 65.5 mm (2.58 inch) (U) 212 mm (8.35 inch) (V) 97.3 mm (3.80 inch) (W) 79 mm (3.11 inch) (X) 108.6 mm (4.28 inch) (3) Material to be removed (4) Existing breaker hole |
- Using the correct Illustration, mark the location of the new opening.
- Smooth the sharp edges and paint the area around the new opening.
- Mount the bracket and the breaker assembly in the extension box using the existing hardware.
- Install the bus bars on the new breaker group using the new hardware provided with the new breaker group.
- Reconnect power cables using existing hardware and install the cover onto extension box.