XQ570 Rental Generator Set Caterpillar


Setup

Usage:

C18 ME5

------ WARNING! ------

Discharge air is hot and could cause property damage and/or personal injury.


Note: The trailer must be level for proper operation of the cooling, lubrication, fuel, and other systems.

Note: Do not operate the unit below any overhang.



Illustration 1g03144956
Typical flow of the exhaust.


Illustration 2g03145038
Top view of the package and the typical clearance around the package.

The unit should have adequate clearance on all sides to allow proper air flow. Allow approximately 2 m (6.6 ft) of clearance on all sides.

  • Place the unit in a stable position.

  • Ensure that you use wheel chocks that are suitable for the trailer.

  • Unfasten the tow vehicle before you operate the unit.


NOTICE

Ensure that the enclosure doors are closed and locked during generator set operation. Access to the generator set is prohibited during operation of the generator set. Access to the emergency stop push button cannot be obstructed or restricted. Ensure that the emergency stop push button is easily seen, and the emergency stop push button must be readily accessible. The door latch cannot be lockable. The door latch cannot contain a provision for making the door latch lockable.


------ WARNING! ------

Failure to close doors when the unit is operating can result in doors opening and closing at a high rate of speed. Contact with the doors may cause personal injury or death.




Illustration 3g03145093
Typical chocking of the wheels and door latches.

Distribution Panel



Illustration 4g03147518
XQ375 distribution panel

The XQ375 distribution panel is equipped with a single adjustable main circuit breaker that is adjustable for 208 V or 480 V. The panel is equipped with a manual voltage changeover board and a single main load connection.

Manually Change the Voltage for the Dual Voltage Distribution Panel with the Voltage Changeover Board on XQ Generator Sets

------ DANGER! ------

DANGER: Shock/Electrocution Hazard-Do not operate this equipment or work on this equipment unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings will result in serious injury or death.


  1. Ensure that the generator set is not operating. Place the handle of the main circuit breaker in the "OFF" position. The "OFF" position is the open position.


    Illustration 5g01835195

  2. Unfasten the latch (1) and open the access door for the voltage changeover board.


    Illustration 6g01835254

  3. Position the voltage changeover board (3) to the left for low voltage (208V). The position of the voltage changeover board is indicated through the cutout (4). Fasten the voltage changeover board (3) with nuts and washers (2).


    Illustration 7g01835556

  4. Position the voltage changeover board to the right for high voltage (480V). The position of the voltage changeover board is indicated through the cutout (4). Fasten the voltage changeover board (3) with nuts and washers (2).


    Illustration 8g01835195

  5. Close the door for the voltage changeover board and fasten the door with the latch (1).


    Illustration 9g01836974

  6. Use a small screwdriver to adjust the switches (5) of the rotary circuit breaker trip adjustment to the correct amperage.

    • "HIGH (480V) - 400 Amp"

    • "LOW (208V) - 630 Amp"

Load Connections

------ DANGER! ------

DANGER: Shock/Electrocution Hazard-Do not operate this equipment or work on this equipment unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings will result in serious injury or death.



NOTICE

Verify the correct load phase rotation with the generator prior to connecting the output power cables.


Note: The procedure for the load connection is illustrated by using a dual voltage distribution panel. All instructions are typical for both the dual voltage distribution panel and for the single voltage distribution panel.



Illustration 10g03148176
(1) Circuit breakers for the outlets
(2) Generator output circuit breaker
(3) outlet (139/240V, 20A)
(4) GFCI duplex (single-phase, 120V, 15A)
(5) outlets (120V, 20A)
(6) NEMA locking inlets
(7) Auto start/stop terminals
(8) California style twist locks

  1. Ensure that the generator set is not operating. Place main circuit breakers in the "OFF" position. The "OFF" position is the open position.

    Dual voltage distribution panels can have two different voltages. Determine the voltage to use. Use either HIGH (480 V) or LOW (208 V) voltage. Select the applicable receptacles or bus bars.

  2. Connect the output power cables to the receptacles or to the bus bars.

    If necessary, connect the output power cables to the bus bars:

    1. Connect the output power cables to the appropriate bus bars .

    ------ WARNING! ------

    Failure to connect the unit to a suitable grounding electrode can result in electrical shock and may cause injury or death.


  3. Connect the ground connection to a suitable grounding electrode of no more than 25 ohms.

  4. Connect the control wiring (if equipped) for the automatic start/stop to the connection points for the remote start/stop.

  5. Close circuit breakers after the connection is made and the engine is running.

Caterpillar Information System:

120 and 120 AWD Motor Grader Belts - Inspect/Adjust/Replace
120 and 120 AWD Motor Grader Transmission and Differential Oil Level - Check
120 and 120 AWD Motor Grader Transmission and Differential Oil Filter and Screens - Replace/Clean
794 AC Off-Highway Truck Engine Components - Clean/Inspect, Rebuild/Install Reman, Install New
794 AC Off-Highway Truck Exhaust Outlet Nitrogen Oxide Sensor - Replace
794 AC Off-Highway Truck Exhaust Inlet Nitrogen Oxide Sensor - Replace
794 AC Off-Highway Truck Breather Line (Diesel Exhaust Fluid) - Inspect
C27 and C32 Generator Set Engines Atmospheric Pressure Sensor - Remove and Install
794 AC Off-Highway Truck Breather (DEF Tank) - Replace
C175 Tier 4 Final Engines for Caterpillar Built Machines Water Pump - Remove and Install
794 AC Off-Highway Truck Screen (DEF Coolant) - Clean
A Procedure to Improve the Tail Box Section of the (HP) Body for 797F Off-Highway Trucks is Available {7250, 7258, 7269, 7583} A Procedure to Improve the Tail Box Section of the (HP) Body for 797F Off-Highway Trucks is Available {7250, 7258, 7269, 7583}
120 and 120 AWD Motor Grader Transmission and Differential Oil Sample - Obtain
C27 and C32 Generator Set Engines Crankshaft Position Sensor - Remove and Install
120 and 120 AWD Motor Grader Fuel System Water Separator - Drain
336, and 340 Excavator TA2 Technical Inspection {0372, 0374, 1000, 7000, 753T, 7565} 336, and 340 Excavator TA2 Technical Inspection {0372, 0374, 1000, 7000, 753T, 7565}
120 and 120 AWD Motor Grader Declaration of Conformity
120 Motor Grader Monitoring System Display Module
Improved Circuit Breaker Bus Bars are Now Used on Certain C32, C175, 3500, and G3500 Generator Sets {1420, 445B} Improved Circuit Breaker Bus Bars are Now Used on Certain C32, C175, 3500, and G3500 Generator Sets {1420, 445B}
Improved Dust Seal for the Swing Gear and Bearing is Now Available on Certain Excavators {7063} Improved Dust Seal for the Swing Gear and Bearing is Now Available on Certain Excavators {7063}
3500E Marine Engines Engine Oil Level - Check
C27 and C32 Generator Set Engines Coolant Temperature Sensor - Remove and Install
High Soot Loading on Certain C7.1 Engines {1000, 108D} High Soot Loading on Certain C7.1 Engines {1000, 108D}
120 Motor Grader Monitoring System Menus
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.