Radiator for C4.4 Marine Generator Set{1353} Caterpillar


Radiator for C4.4 Marine Generator Set{1353}

Usage:

C4.4 S1M
Marine Generator Set:
C4.4 (S/N: S1M1-182,184-188,190-211,214-215,218-259,262-271,273-327,329-382,384-384,390-391,395-397,400-400,402-402,405-413,416-422,425-428,432-440,442-466,468-469,471-476,479-481,484-491,495-501,504-505,507-543,548-552,556-560,562-565,569-576,578-599,604-607,612-619,624-626,628-667,669-749,754-756,758-788,793-796,798-800,803-820,825-826,828-835,838-845,847-860,862-874,877-882,884-888,891-943,946-952,954-958,960-965,971-984,986-990,993-1232,1235-1291,1293-1367,1369-1375,1377-1380,1382-1391,1393-1408,1411-1418,1420-1457,1459-1477,1479-1484,1486-1721,1723-1733,1735-1755,1758-1762,1764-1773,1776-1785,1787-1788,1790-1810,1812-1886,1888-1899,1901-1921,1923-1927,1929-1937,1939-1950,1953-1954,1956-1957,1959-1961,1963-1967,1969-1970,1973-1984,1986-1990,1993-1993,1996-2079,2082-2086,2088-2090,2092-2097,2099-2099,2101-2103,2105-2106,2108-2116,2118-2119,2121-2124,2126-2131,2133-2137,2139-2143,2145-2215,2217-2543,2545-2662,2664-2666,2668-2678,2680-2853,2855-2855,2857-2896,2899-2900,2902-3307,3309-3383,3386-3429,3433-3470,3474-3608,3610-3693,3695-3806,3808-3823,3825-3874,3876-3946,3948-3948,3950-3971,3973-3973,3975-3985,3987-4001,4004-4044,4046-4046,4048-4054,4057-4066,4068-4070,4072-4072,4075-4076,4081-4085,4088-4089,4091-4094,4096-4097,4099-4101,4103-4106,4108-4116,4118-4121,4123-4124,4126-4128,4130-4141,4143-4147,4149-4169,4171-4172,4174-4190,4192-4198,4200-4200,4202-4204,4206-4209,4211-4212,4216-4222,4224-4225,4227-4236,4238-4289,4291-4292,4294-4303,4305-4312,4314-4317,4320-4321,4323-4334,4336-4342,4344-4345,4348-4349,4352-4359,4361-4377,4379-4381,4383-4386,4388-4388,4390-4423,4426-4431,4433-4440,4442-4451,4453-4481,4483-4483,4485-4524,4526-4535,4537-4541,4543-4548,4551-4551,4554-4555,4557-4561,4563-4568,4570-4573,4575-4580,4582-4591,4593-4615,4617-4631,4633-4634,4636-4636,4638-4640,4642-4648,4651-4655,4657-4669,4671-4677,4679-4680,4683-4685,4691-4691,4693-4694,4696-4707,4709-4709,4711-4729,4731-4731,4734-4745,4747-4768,4771-4772,4774-4784,4786-4786,4788-4792,4794-4816,4818-4831,4833-4840,4843-4848,4850-4868,4870-4880,4882-4883,4885-4888,4890-4904,4911-4911,4913-4913,4916-4917,4919-4921,4923-4930,4933-4934,4936-4938,4940-4948,4950-4951,4953-4954,4956-4956,4959-4961,4964-4965,4968-4971,4973-4977,4979-4979,4981-4986,4988-4988,4993-4995,4997-5002,5004-5009,5011-5014,5016-5019,5021-5051,5054-5065,5068-5076,5078-5078,5081-5081,5083-5087,5089-5089,5091-5101,5103-5107,5110-5115,5117-5123,5126-5136,5139-5139,5141-5143,5145-5148,5152-5153,5155-5156,5159-5170,5172-5191,5193-5195,5199-5199,5202-5215,5218-5223,5225-5231,5233-5233,5235-5236,5238-5239,5242-5249,5251-5252,5254-5255,5263-5263,5271-UP)

Introduction

There have been isolated instances of elevated jacket water temperature when operating at higher loads in high ambient temperature.

As an example, an emergency generator was overheating during commissioning. The generator set was shutting down with high coolant temperature prior to reaching rated load and speed. The generator set was unable to demonstrate 110% load capability to the Marine Societies Classification (MCS).

Note: A change made to the shutdown set-point did not allow the generator set to demonstrate either rated speed or 110% load.

The affected part is 293-9242 Radiator Gp .

Restricted air flow to the cooling radiator will cause the coolant temperature to elevate when the unit is installed in restrictive areas. This situation can also occur when inadequate ducting is provided.

Solution

A redesigned radiator has been introduced in production. The height of the radiator has been increased by 100 mm (3.9 inch) to allow greater tolerance to reduced airflow.

Radiator Cooling

The radiator cooling pack option uses air to cool the engine, rather than sea water. A good supply of air is vital to achieving the correct cooling performance. Not only is the supply of air important but also the exhaust of air from the radiator. The complete air circuit must be considered in order to achieve the correct cooling performance.




Illustration 1g03726325

Cooling air circuit

Illustration 1 shows the cooling air circuit. Although the exact details of the layout will need to vary from installation to installation, the basic air circuit will remain the same. The marine generator set utilizes a pusher fan. The fan draws cooling air from the inlet (1) over the generator and engine (2) and then pushes through the radiator and charge air cooler. Typically, the exhaust from the radiator and charge air cooler then exit the engine room via a vent to outside (3). Cool air enters the engine room from outside through another set of vents.

The radiator cooling system is designed for a maximum air temperature behind the generator set of 50° C (122° F). The design accounts for the radiated heat from the engine and generator which will lead to air temperatures greater than 50° C (122° F) at the inlet to of the radiator fan. The design does not account for any other heat sources in the engine bay. If other sources of heat are present, additional ventilation will need to be considered. This factor is especially important for generator sets that are likely to operate in hotter climates.




Illustration 2g03726361

Airflow pressure measurement




Illustration 3g03726366

The radiator cooling system is designed to operate with a maximum duct restriction pressure of 127 Pa (0.5 inch of H2O). The inlet pressure is measured at a location in front of the fan (along the length of the engine) (5). The outlet pressure is measured at a location directly in front of the radiator outlet (4). In this way, the total pressure over the cooling pack (6) is measured. This measurement includes the restrictions encountered in drawing the air into the engine (7) and the restriction encountered in air exiting the engine room. When designing the engine room ventilation a pressure restriction target of 63.5 Pa (0.25 inch of H2O) should be aimed for, although lower is better.

In order to measure the duct restriction of an installation, static pressure tubes (4) and (5) will be required. Use of any other means is likely to give inaccurate results. A water manometer (8) is normally sufficient for measuring the pressure. The static tubes should be aligned parallel with the air flow. A fine thread on a rod is a useful tool in identifying the direction of air flow over the engine. Care should be taken to keep rod away from rotating parts, including the fan. Illustrations 2 and 3 show typical locations of the static tubes used for taking pressure readings.

Air Flow Measurements

An alternative to taking pressure measurements is to measure the air flow through the radiator. This can be done using an anemometer to measure the air velocity through an opening of known area, from which the volumetric flow can be calculated. As air density decreases with temperature, to get an accurate reading air flow measurements should be taken with the generator operating at no load. As the generator is operating at no load, there is minimum heating of the air flow.

Anemometers are specifically available for ventilation and duct work, an instrument of this type should be used where possible. Measurements should be made where air flow is uniform, ideally just after the radiator outlet, but not after any louvers, bends or obstructions which could lead to non-uniform air velocities. An accurate measurement of volumetric flow is best made by taking at least 12 air velocity readings across the opening. It is best to draw up a grid with each cell being of equal area. Air velocity readings are then averaged, to give a total average air velocity through the opening. This is then multiplied by the opening area to give the volumetric air flow.




Illustration 4g03730753

Typical example

Illustration 4 shows the layout of the grid for calculating the volumetric flow.

  • Width (1)

  • Height (2)

  • Air flow (3)

Technical Marketing Information (TMI) contains air flow data for the fans installed to generator sets along with the restriction curves for radiator cores. Overlaying the two curves will give the operating volumetric air flow at the curve intersection point. If the air flow is measured then the total pressure across the fan can be measured of the fan curve. Given the air flow reading, the pressure drop can also be read off the radiator restriction curve. The difference in the two pressures is the total duct restriction present within the air system.

Volumetric Flow is given by:

  • Q = h x w x vm

  • vm = (v1 + v2 + v3 + v4 + ... + v12) / 12

Where:

  • V1-12 : Air velocity readings 1->12 (m/s or ft/min)

  • vm : Average air velocity (m/s or ft/min)

  • h : Opening height (m or ft)

  • w : Opening width (m or ft)

  • Q : Air volumetric flow (m3/s or cfm)

Whilst taking pressure and air flow measurements can be useful verification methods, good design practice should be used to correctly size and locate inlet and exhaust vents. The biggest restriction around the air circuit is likely to be due to the inlet and exhaust vents themselves. As such the supplier of the vents should be consulted for correct sizing. Other good practices include:

  • Exhaust pipes should be lagged from the turbine outlet. The lagging should be sufficient to ensure that the external surface temperature does not exceed 220° C (428° F) at full load. This helps to ensure that no extra heat is carried into the radiator air.

  • Exhaust routing should, where possible, be away from the radiator so that the air flow into the radiator is not impeded.




Illustration 5g03730789

Typical example

Ensure that there is sufficient space in front and behind of any exhaust or inlet vent. Refer to illustration 5. This includes:

  • Fire or heavy weather hatches should be able to fully open away from the vent.

  • Placing the vent such that a bulkhead is not immediately in front or behind the opening.

  • A suggested clearance between the vent and any bulkhead or otherwise is at least the longest of the height or width of the vent itself.

  • Inlet air vents should be placed such that they pick up cool ambient air, not air which has picked up any additional heat, such as air exhausted from another engine room.

  • The exhaust vent should have a frontal area equivalent to the total radiator exit area and ideally the same dimensions. If this cannot be achieved then tapered ductwork should be used to adapt the two together. A minimum length of 1 m (3.3 ft) is recommended for any adapting ductwork, where a significant dimension change needs to take place.

Illustration 5 shows the basic considerations for allowing the generator set to cool.

  • Engine room (3)

  • Vents (2)

  • DM: minimum distance (1)

  • VW: vent width (4)

  • VH: vent height (5)

Dm should meet the following conditions:

Dm is more than or equal to Vw.

Dm is more than or equal to VH.

Power Variability

All engines are subject to variability of power output dependent on various external factors. Two of these factors with high significance are inlet air and fuel. Inlet air is largely affected by temperature, with atmospheric pressure variation being minor for marine sea-level installations. Diesel engines inject fuel by volume, and as such density changes vary the mass of fuel being injected.

The graphs shown in illustrations 6 and 7 display the variation on engine power output based on changes to air inlet temperature and fuel density. The power output change with fuel is the same across all engines regardless of cooling system. The power output change with inlet air temperature does however depend on the charge air cooling method. Engines using an air to water cooler, Heat Exchanged and Keel Cooled, have less variation. This is due to the water being a more stable heat-sink, with resulting inlet manifold air temperatures being stable also. Air to air cooling methods, Radiators, are less stable with the ambient air being used to cool the charge air, leading to high output variability.

CAT engines have the rated power defined at standardized conditions, typically these are 25° C (77° F) air and 850 kg/m3 fuel. As such operating in conditions away from these will likely cause engine power output to drop. This should be born in mind when designing engine room ventilation, so that ambient air temperatures are kept to a minimum.




Illustration 6g03730809

Typical example

(1) Power adjustment (percentage)

(2) Engine power adjustment by ambient temperature. SAE J1995 rating standard.

(3) Ambient temperature

(4) Radiator

(5) Heat exchanger and keel cooled

PBaro is equal to 100 kPa (14.5 psi).

Pvap is equal to 1 kPa (0.145 psi).

Fm is equal to 0.614 (engine factor).

Note: These values are for turbocharged engines only.




Illustration 7g03730813

Typical example

(1) Power adjustment (percentage)

(2) Engine power adjustment by ambient temperature. SAE J1995 rating standard.

(3) Fuel density (kg/m3)

(4) All cooling options

Caterpillar Information System:

C3.4B Engines Relay - Test - Start Relay
XQ400 Power Module Gas Pressure Regulator - Test
XQ400 Power Module Engine Performance - Test
XQ400 Power Module Control Panel - Inspect/Test
CG137-08 and CG137-12 Engines Catalytic Converter Substrate - Inspect
XQ400 Power Module Exhaust Bypass - Inspect
XQ400 Power Module Ignition System Timing - Check/Adjust
XQ400 Power Module Carburetor Air/Fuel Ratio - Check/Adjust
G3520H Generator Set Engine Turbocharger - Assemble
C7 and C9 Industrial Engines Injection Actuation Pressure - Test
C280 Marine Engines Exhaust Temperature - Test
XQ400 Power Module Emergency Stopping
G3512H and G3516H Generator Set Engines Air Inlet Manifold - Remove and Install
DE Series Generator Set With Cat C7.1 Engine Product Description
2014/10/03 Cat® Reman Announces Additional C7 Engine Options for Certain Thomas Built Bus Applications {1000, 1201}
Engine System Setup for Certified CG137-12 Generator Set Engines {1270, 1278} Engine System Setup for Certified CG137-12 Generator Set Engines {1270, 1278}
3500E EPA Tier 4 Final and IMO-II/III Switchable Marine Engines Air Shutoff - Test
DE Series Generator Set With Cat C7.1 Engine Safety Messages
DE Series Generator Set With Cat C7.1 Engine Model View Illustrations
DE Series Generator Set With Cat C7.1 Engine Refill Capacities and Recommendations
352F Excavator Plate Locations and Film Locations
C3.4B Engines Sensor (Data Link Type) - Test - Ammonia Sensor
C4.4 Engines for Caterpillar Built Machines Nitrogen Oxide Sensor - Remove and Install - Nitrogen Oxide Sensor Positioned in Original Equipment Manufacture (OEM) Exhaust Tube Assembly
794 AC Off-Highway Truck Machine Systems Service and Parking Brake (Front) - Remove and Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.