- Engine:
- 3508 (S/N: 23Z1-UP; CNF1-UP)
- Generator Set:
- 3508 (S/N: 5PW1-UP)
- Power Module:
- PM3508 (S/N: BLM1-UP)
- 3508B (S/N: S2A1-UP; S2B1-UP; 3DM1-UP; 3DW1-UP; CNB1-UP)
- 3512 (S/N: 24Z1-UP; CMJ1-UP)
- 3512B (S/N: CMC1-UP; S2G1-UP; S2H1-UP; 8EM1-UP; 1PW1-UP; BLF1-UP)
- 3516 (S/N: 25Z1-UP; 73Z1-UP; CMD1-UP)
- 3516B (S/N: 9AN1-UP; S2P1-UP; S2R1-UP; 2FW1-UP; BPJ1-UP; PPS1-UP)
- 3508B (S/N: 5KW1-UP; BGX1-UP)
- 3512 (S/N: 6WW1-UP; FDR1-UP; PTG1-UP; PTH1-UP)
- 3512B (S/N: 6GW1-UP; BRK1-UP; FDE1-UP; PTF1-UP; PTM1-UP)
- 3512C (S/N: SBG1-UP)
- 3516 (S/N: 8TW1-UP; CAL1-UP; PTD1-UP; RKT1-UP; GZX1-UP; GZR1-UP)
- 3516B (S/N: 8NW1-UP; FDN1-UP; FDX1-UP; GAR1-UP; GZS1-UP; GZT1-UP; LEK1-UP; PBR1-UP)
- 3516C (S/N: SBJ1-UP)
- PM3512 (S/N: BNR1-UP)
- PM3516 (S/N: BPD1-UP)
The following canister type of jacket water heaters are supplied without AC circuitry.
The customer must provide separate wiring and control. This information is stated in the price list.
In order to maximize the reliability of the jacket water heaters, the canister heaters must be turned off during operation of the generator set. If the AC power input is left on during engine operation, premature failure of the thermostat can occur due to vibration during generator set operation.
Add a contactor for control that is energized from the crank relay for the engine. This will ensure that the heater is turned off while the generator set is running. The contactor must be rated for either 3, 6 or 12 kW power requirement.
Illustration 1 | g01525127 |
Wiring for the contactor |
Refer to Illustration 2 in order to wire the 200-6504 Jacket Water Heater Gp and the 7E-6248 Jacket Water Heater Gp for 200 to 240 volt supply.
Illustration 2 | g01620614 |
200 to 240 volt single phase wiring for the 200-6504 Jacket Water Heater Gp and the 7E-6248 Jacket Water Heater Gp |
Refer to Illustration 3 in order to wire the 200-6504 Jacket Water Heater Gp and the 7E-6248 Jacket Water Heater Gp for 400 to 480 volt supply.
Illustration 3 | g01525129 |
400 to 480 volt single phase wiring for the 200-6504 Jacket Water Heater Gp and the 7E-6248 Jacket Water Heater Gp |
Refer to Illustration 4 in order to wire the 7E-6247 Jacket Water Heater Gp for 120 volt supply.
Illustration 4 | g01525132 |
120 volt single phase wiring for the 7E-6247 Jacket Water Heater Gp |
Refer to Illustration 5 in order to wire the 7E-6247 Jacket Water Heater Gp for 240 volt supply.
Illustration 5 | g01525133 |
240 volt single phase wiring for the 7E-6247 Jacket Water Heater Gp |
If you have any questions, route any related issues through your Technical Communicator to the Dealer Solution Network (DSN).