Alarm List Colors
- Alarm and shutdown (automatic stop) entries are displayed in red. A warning is displayed in yellow.
- New alarms (unacknowledged) are displayed in bold text, and acknowledged alarms are displayed in normal text.
- An alarm that is not acknowledged, then goes inactive, is displayed in normal text on a gray background.
Note: Red text color indicates an alarm or shutdown. Yellow text color indicates a warning.
Alarm Color Chart     | ||
---|---|---|
Alarm or Shutdown     | New active alarm     | Red background     |
Acknowledged active alarm | Red background     | |
Unacknowledged inactive alarm | Red text, gray background     | |
Warning     | New active warning     | Yellow background     |
Acknowledged active warning | Yellow background     | |
Unacknowledged inactive warning | Yellow text, gray background     | |
Diagnostic     | New White Diagnostic     | White background     |
Acknowledged white diagnostic | White background     | |
Unacknowledged inactive diagnostic | Black text, gray background     |
Alarm List Access
Illustration 1 | g02459820 |
To view the alarm list, press the "Alarm List" soft key.
Press the button again to exit the alarm list, or press the Exit button.
New Alarms
New alarms are displayed in bold text. As in Illustration 1, the alarm "Engine Stop Failed" is new. The alarm is unacknowledged.
Once the alarm is acknowledged, the alarm text is no longer bold.
Filter Alarms
The alarm list can filter alarms in three groups:
All Alarms - all alarms and diagnostics
Panel Alarms - all alarms, no diagnostics
Diagnostics - diagnostics only
To switch between the different views, press the corresponding soft key 2 and/or soft key 3.
Silence the Buzzer
Illustration 2 | g02517259 |
Alarm List Button |
If the buzzer sounds, press the alarm list button to silence the buzzer.
If the display does not already show the alarm list, the alarm will cause the display to open the alarm list automatically.
If the alarm list is already open when the buzzer sounds, pressing the alarm list button to silence the buzzer will not exit the alarm list. Pressing the alarm list button will only silence the buzzer.
Acknowledge Alarms
Illustration 3 | g02459822 |
Use the following procedure to acknowledge a single alarm.
- With the alarm list open, select the desired alarm that is to be acknowledged by using the arrow buttons.
The selected alarm line will expand to reveal additional information, if there is any.
- Press the "Acknowledge" button to acknowledge the selected alarm.
Acknowledge All Alarms
Open the alarm list. Press and hold the "Acknowledge" button for 1 second. All alarms will be acknowledged.
Note: Alarms that are still active will still be displayed in the screen. The active alarms will remain displayed until the alarm is inactive.