EMCP 4.4 1G1U (Single Generator, Single Utility) Checklist {7002} Caterpillar


EMCP 4.4 1G1U (Single Generator, Single Utility) Checklist {7002}

Usage:

SR4 5CK
Electric Power Generation
SR4B (S/N: 5CK1-UP)

Introduction

This document is intended to be used as reference to aid in the commissioning of a generator set with the 1G1U feature. It is not intended to be a complete system checklist. Use the Genset Commissioning Checklist for the complete package as well as this checklist. Refer to local requirements and installation for complete system requirements. Only qualified personnel shall perform this work. Use proper Personal Protective Equipment (PPE) when working at the installation. Verify that measuring equipment is within calibration and in proper operating order for the job required.

This checklist assumes that the control panel already has the required wiring and terminals installed either from the factory, or otherwise. Refer to LEXE1426, "EMCP 4.4 1G1U (Single Generator, Single Utility) Commissioning Guide" for more information at Cat® Electronic Media Center.

https://emc.cat.com/QuickSearch.aspx

Safety Section

------ WARNING! ------

Before servicing/performing maintenance on the machine, electrical power must be physically disconnected; battery plugs must be disconnected from the batteries, or the trailing cable must be unplugged, and warning tags and padlocks shall be applied by a certified electrician. Certified electricians shall perform or direct any electrical work, including any energized testing, repair work in controllers, motors, or other approved compartments, and shall insure that all compartments are properly closed and inspected prior to re-energization. All applicable lock out and tag out procedures must be followed.


Customer Information

Customer ____________________________________________________________________________________________________

Site Contact ________________________________________________________________________________

Location ____________________________________________________________________________________________________

Work Order # ________________________________________________________________________________

________________________________________________________________________________________________________________________

Technician ____________________________________________________________________________________________________

Hour Meter ____________________________________________________________________________________________________

PM Level ____________________________________________________________________________________________________

Engine Model ________________________________________________________________________________

Engine Serial # ________________________________________________________________________________

Checklist

Table 1
Wiring 
1. Generator Set Wiring 
A. Bus Sensing  Yes  No  N/A 
1. The voltage of the utility as seen by the EMCP is <= 600V L-L, or else a potential transformer is installed between the utility and the EMCP utility voltage sensing inputs       
2. If the EMCP utility voltage sensing wires come from the same potential transformer that feed the transducer, the burden of the PTs is not exceeded       
3. If the EMCP utility voltage sensing wires come from a potential transformer, that potential transformer is not adding an unintended phase shift       
4. Generator bus sensing is moved from the output of the generator set circuit breaker to the utility side of the utility breaker (from the control panel bus sensing fuses to utility voltage sensing)       
B. Utility Breaker Requirements  Yes  No  N/A 
1. The utility breaker is able to close within 5 to 6 cycles, has the abilitytoelectrically open and close, and has Aux contacts (a and b)       
2. The utility breaker has both a powered shunt (DC) and/or undervoltage trip       
C. Utility Breaker Control  Yes  No  N/A 
1. The utility breaker Aux contacts are wired between the EMCP Digital Inputs and the utility breaker       
2. The utility UV trip, shunt close, and shunt trip signals are wired between the EMCP relays and the utility breaker       
3. The utility CB Bell Alarm and Utility Relay signals are wired between the EMCP Digital Inputs and the utility breaker       
4. The utility circuit breaker Close and Trip command outputs from the EMCP are wired to relays that can handle the current draw from the utility circuit breaker trip unit       
D. Other  Yes  No  N/A 
1. Utility Breaker Request (optional) – A control switch is wired between the EMCP Digital Inputs and the utility breaker       
2. If connecting to a live system, the utility shunt trip is connected as the last step of the commissioning       
Notes:




 

Table 2
Wiring 
2. Tranducer Wiring 
Note: This section is intended for the Caterpillar supplied transducer, but may be useful for others. 
A. Transducer Selection  Yes  No  N/A 
1. The transducer calculates both kW and kVar       
2. The transducer sends out both positive and negative values without requiring an additional signal       
3. The output ranges are within the EMCP Analog Input ranges       
B. Utility Side - Voltage Sensing  Yes  No  N/A 
1. The transducer voltage input is within the transducer limit (for the Caterpillar supplied transducer, <=480V L-L, nominal), or else a potential transformer is installed       
2. If the transducer voltage sensing wires come from the same potential transformer that feed the EMCP utility voltage sensing, the burden of the PTs is not exceeded       
3. Appropriately sized wires are connected between the utility voltage sensing points (or from utility PTs) and the appropriate inputs of the transducer       
4. Voltage sensing comes from the utility side of the utility breaker       
C. Utility Side - Current Sensing  Yes  No  N/A 
1. The utility sensing current transformers are sized appropriately to prevent saturation at full power and actual pf       
2. Appropriately sized wires are connected between the utility current transformers and the appropriate inputs of the transducer       
3. The secondary rating of the current transformers on the utility side of the utility breaker fall within the rating of the inputs on the transducer       
D. Generator Set Side  Yes  No  N/A 
1. The wiring to each EMCP Analog Input is shielded twisted cable, with a drain (connected at the EMCP end only)       
2. The kW and kVAr signals are wired to separate EMCP Analog Inputs       
E. Power  Yes  No  N/A 
1. Transducer supply power is connected       
Notes:




 

Table 3
Programming 
1. EMCP Programming  Yes  No  N/A 
1. Ensure the EMCP is flashed with software that contains the 1G1U feature       
2. The Utility Load Control set points (including Control Mode and mode-specific set points) are programmed       
3. The Utility AC Monitor set points are programmed       
4. The Utility protections (over/under Voltage/Frequency) set points are programmed       
5. The Event Response Configurations are programmed       
6. The Analog Inputs (kW/kVAr) are programmed       
7. The Analog Input Data Range Max and Data Range Min values (Utility kW, kVAr) are programmed       
8. The Digital Inputs (Request to Close Utility CB, Request to Trip Utility CB, Utility Breaker Aux A, Utility Breaker Aux B, Utility CB Bell Alarm - optional, Utility Relay - optional) are programmed       
9. The Digital Outputs (Utility CB Close/Trip) are programmed       
10. The Gen Load Control (for paralleling modes) set points are programmed       
Notes:




 
2. Transducer Programming  Yes  No  N/A 
1. If the transducer is not supplied from Caterpillar, all transducer set points are properly programmed       
Notes:




 

Table 4
Verification 
1. System  Yes  No  N/A 
1. Verify programming is correct for the site requirements       
2. Independently measured Utility kW and kVAr reasonably match the values shown on the EMCP screens       
3. Independently measured Utility voltage reasonably matches the value shown on the EMCP screen       
4. Values across the breakers are verified in phase, and with proper phase rotation, during synchronization, but before closing       
5. The Utility breaker request switch (optional) opens and closes the Utility breaker correctly       
6. Actual generator and Utility breaker positions match the indication on the EMCP screen for both open and closed       
7. All required paralleling modes operate as needed (Base, Open Transition, Closed Transition, Import, Export)       
Notes:




 

Caterpillar Information System:

340 Excavator Mirror
Installation Procedure for 2nd Auxiliary Lines Kit on Certain Mini Hydraulic Excavators {5057} Installation Procedure for 2nd Auxiliary Lines Kit on Certain Mini Hydraulic Excavators {5057}
Inspection of the Rear of the Engine on Certain C4.4 Machines {1201} Inspection of the Rear of the Engine on Certain C4.4 Machines {1201}
Certain Cat&reg; Product Link A6 Platform Network Managers May Stop Reporting and Loses Communication {7606} Certain Cat&reg; Product Link A6 Platform Network Managers May Stop Reporting and Loses Communication {7606}
The 521-5433 Fuel Pump Gp May Fail on Certain 3500 Industrial Engines {1256} The 521-5433 Fuel Pump Gp May Fail on Certain 3500 Industrial Engines {1256}
Improved Assembly Process for the Pin in the Windshield Group Is Now Available for Certain Excavators {7310} Improved Assembly Process for the Pin in the Windshield Group Is Now Available for Certain Excavators {7310}
Improved Attachment Valve (F2) Is Now Used on Certain 320, 320 GC and 323 Excavators {5051} Improved Attachment Valve (F2) Is Now Used on Certain 320, 320 GC and 323 Excavators {5051}
New Resistance Temperature Device (RTD) Module Software Is Now Used for Certain Engines {1920} New Resistance Temperature Device (RTD) Module Software Is Now Used for Certain Engines {1920}
Inspect the 144-0367 Hose Clamps Between the Sea Water Pump Outlet and Aftercooler Inlet on Certain C18 Marine Engines {1063, 3319} Inspect the 144-0367 Hose Clamps Between the Sea Water Pump Outlet and Aftercooler Inlet on Certain C18 Marine Engines {1063, 3319}
New Engine Software is Now Used For Certain G3520 Generator Sets {1920} New Engine Software is Now Used For Certain G3520 Generator Sets {1920}
New Air Shutoff Valve on Certain 3500 Engines {1078, 1439} New Air Shutoff Valve on Certain 3500 Engines {1078, 1439}
New Tooling and Installation Process for Crankshaft Seal on C27 and C32 Engines {0701, 1160, 1161} New Tooling and Installation Process for Crankshaft Seal on C27 and C32 Engines {0701, 1160, 1161}
Diesel Exhaust Fluid (DEF) Pump on Certain C4.4 Engines {108U, 1439} Diesel Exhaust Fluid (DEF) Pump on Certain C4.4 Engines {108U, 1439}
Premature Nose-Cone and King-Pin Wear May Occur on Certain 794, 796, and 798 Off-Highway Trucks {3260, 4314} Premature Nose-Cone and King-Pin Wear May Occur on Certain 794, 796, and 798 Off-Highway Trucks {3260, 4314}
An Improved Cooling System Venting Procedure is Now Available in the Operation and Maintenance Manual for Certain C175 Off-Highway Truck Engines {0374, 1350} An Improved Cooling System Venting Procedure is Now Available in the Operation and Maintenance Manual for Certain C175 Off-Highway Truck Engines {0374, 1350}
New Hard Washers are Used for the Mounting Hardware on the Oil Scavenge Pump for Certain C175 Off-Highway Truck Engines {1312} New Hard Washers are Used for the Mounting Hardware on the Oil Scavenge Pump for Certain C175 Off-Highway Truck Engines {1312}
An Improved Fuel Injector is Now Used on Certain C9.3 Machine Engines {1251, 1254, 1290, 1713} An Improved Fuel Injector is Now Used on Certain C9.3 Machine Engines {1251, 1254, 1290, 1713}
New Engine Software Is Now Used for Certain C175 Locomotive Engines {1920} New Engine Software Is Now Used for Certain C175 Locomotive Engines {1920}
Identifying Oil Leaks on Certain 3500 Mining Machine Engines {1151, 1348} Identifying Oil Leaks on Certain 3500 Mining Machine Engines {1151, 1348}
New Tooling and Installation Process for Crankshaft Seal on C27 and C32 Engines {0701, 1160, 1161} New Tooling and Installation Process for Crankshaft Seal on C27 and C32 Engines {0701, 1160, 1161}
Improved Auxiliary Sea Water Pump Group is Now Used on Certain C12 Marine Engines {1371} Improved Auxiliary Sea Water Pump Group is Now Used on Certain C12 Marine Engines {1371}
New Shipping Procedure Is Now Used for Stick Cylinder Pinned in Shipping Position on Certain 308 and 309 Mini Hydraulic Excavators {0355} New Shipping Procedure Is Now Used for Stick Cylinder Pinned in Shipping Position on Certain 308 and 309 Mini Hydraulic Excavators {0355}
New Solenoid Assembly is Now Used on Fuel Injectors for Certain C9.3 Industrial Engines {1251, 1290} New Solenoid Assembly is Now Used on Fuel Injectors for Certain C9.3 Industrial Engines {1251, 1290}
New Engine Software for Certain C7.1 Engines {1920} New Engine Software for Certain C7.1 Engines {1920}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.