CID 0100 FMI 04
Conditions Which Generate This Code:
The Electronic Control Module (ECM) detects the following conditions:
- The signal voltage from the engine oil pressure sensor is less than 0.1 Volts DC for more than eight seconds.
- The ECM has been powered for at least two seconds.
- The engine is running.
System Response:
The ECM will log the diagnostic code. If equipped, the diagnostic lamp will flash. The ECM will set data for engine oil pressure to the default value. The electronic service tool will display "Voltage Below Normal" on the status screens.
None
This diagnostic code can be caused by a short to ground or a shorted sensor.
Test Step 1. Perform the following diagnostic procedure: Engine Pressure Sensor Open or Short Circuit - Test
Results:
- OK - STOP
Caterpillar Information System:
C6.6 Generator Set CID 0100 FMI 03
C6.6 Generator Set CID 0004 FMI 06
C6.6 Generator Set CID 0004 FMI 05
C6.6 Generator Set CID 0004 FMI 02
Track, Track Roller, and Track Idler Cycle Times {4159, 4169, 4170, 4171, 4180} Track, Track Roller, and Track Idler Cycle Times {4159, 4169, 4170, 4171, 4180}
2010/01/14 New Communication Software for the PL1000T Is Now Used on Commercial Engines {7606, 7620}
3508, 3512 and 3516 Generator Set Engines Camshaft Bearings - Install
C6.6 Generator Set CID 0003 FMI 06
C6.6 Generator Set CID 0003 FMI 05
C6.6 Generator Set CID 0003 FMI 02
3508, 3512 and 3516 Generator Set Engines Camshaft Bearings - Remove
C6.6 Generator Set CID 0002 FMI 06
C6.6 Generator Set CID 0100 FMI 10
C6.6 Generator Set CID 0110 FMI 03
C6.6 Generator Set CID 0110 FMI 04
C6.6 Generator Set CID 0168 FMI 00
3508, 3512 and 3516 Generator Set Engines Crankshaft - Remove
C6.6 Generator Set CID 0168 FMI 01
C6.6 Generator Set CID 0168 FMI 02
C6.6 Generator Set CID 0172 FMI 03
C6.6 Generator Set CID 0172 FMI 04
C6.6 Generator Set CID 0190 FMI 08
C6.6 Generator Set CID 0247 FMI 09
C9.3 Engines for Caterpillar Built Machines Idle Speed Is High