Digital Voltage Regulator Caterpillar


Troubleshooting

Usage:

SR4B 1BN

Table 1
Common Troubleshooting Procedures(1)(2) 
Problem  Troubleshooting Procedure 
Reverse Power Shutdown  Check CT polarity.
Check connections to the digital voltage regulator terminals 5 and 6. 
No Voltage
(50 ACV or Less) 
Check for the fault codes. Correct the fault codes.
Determine if DC voltage is properly connected ("B+"/"B-").
Check for loose sensing or PM wires.
Check for blown PM fuses.
Determine if underfrequency setpoint (parameter :10) is too high.
Temporarily disconnect battery from the digital voltage regulator. Then, connect battery to the regulator. Restart the regulator.
Check terminal 42. Battery voltage (24 VDC) should not be present. (Excitation disable circuit)
Check rotating diodes on the generator. 
Low Voltage
(Residual to Less Than Rated Output Voltage) 
Check for the fault codes. Correct the fault codes.
Determine if generator output voltage setpoint (parameter :01) is set too low.
Determine if droop setpoint (parameter :30) is set to zero. Droop setpoint should be 0.
Check parameter :03 for correct generator type.
Determine if parameter :06 is less than the expected generator operating frequency.
Check parameter :02 for the correct PT ratio. Check that parameter :02 is not doubled.
Check that one PM fuse is not blown.
Check rotating diodes on the generator. 
High Voltage
(Voltage Higher Than Range Allows) 
Check for the fault codes. Correct the fault codes.
Check parameter :02 for the correct PT ratio. Check that parameter :02 is not too low.
Check that parameter :15 (IR Compensation) is set to zero.
Determine if the generator output voltage setpoint (parameter :01) is set too high.
Determine if the minimum voltage setpoint (parameter :09) is set too high. 
Unstable Voltage
(Voltage Fluctuation Greater Than 0.25%) 
Check for the fault codes. Correct the fault codes.
Remove the remote voltage adjust rheostat.
Disconnect droop current transformer.
Check for loose wiring.
Check rotating diodes on the generator. 
Initial Voltage Overshoot  Check parameter :03 for correct generator type. 
(1) A regulator may fail to perform correctly if it is not properly connected. A regulator may also fail if there is a failure of downstream equipment, such as diodes.
(2) It is possible to get an unexplained reverse VAR fault if the CT is connected backward. Check the CT connection if this fault occurs.

This section provides troubleshooting procedures for generator voltage problems that are related to the digital voltage regulator.

Note: Before starting to troubleshoot, check the part number to determine if the digital voltage regulator being used is proper for the application. The part number label on the digital voltage regulator indicates the sensing voltage range and whether or not the regulator is the optional KVAR/PF model. Refer to the following chart.

Table 2
Digital Voltage Regulator Application Chart 
Regulator Version  Voltage Range  Early Part Number  Former Part Number  Current Part Number 
Basic  79 to 124 Volt
3 phase sensing 
116-7480   130-3471   155-3831  
Basic  125 to 249 Volt 3 phase sensing  116-7481   130-3472   155-3832  
Basic  250 to 600 Volt 3 phase sensing  116-7482   130-3473   155-3833  
KVAR/PF
Optional Version 
79 to 124 Volt
3 phase sensing 
116-7483   130-3474   155-3834  
KVAR/PF
Optional Version 
125 to 249 Volt 3 phase sensing  116-7484   130-3475   155-3835  
KVAR/PF
Optional Version 
250 to 600 Volt 3 phase sensing  116-7485   130-3476   155-3836  
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.