Improper PF Regulation or KVAR Regulation - Troubleshoot
- Stop the generator set.
- Check the wiring.
Expected Result: The wiring is correct.
Results:
- OK: Go to Step 2.
- NOT OK: The erroneous regulation may be observed if the CT polarity or PT polarity is incorrect. Reverse the polarity. See the proper wiring diagram for details. Refer to Testing And Adjusting, "Wiring Diagrams". STOP.
- Start the generator set and load with 25% to 50% of rated load. Use 0.8 power factor inductive load, if at all possible.
- Check the values in parameters :04 and :05.
Note: Parameter :52 (current) provides the measured value of the current in the "B" phase only.
- Measure the ampere load on the "B" phase.
- Measure the signal voltage level at regulator terminals 5 and 6.
- Verify that it is in correct proportion to load amperes and agrees with the settings of parameters :04 and :05.
Expected Result: Any parameters show negative numbers.
Results:
- OK: If any parameters show negative numbers, a CT or PT polarity is incorrect or the phase rotation is wrong. Verify the polarity and the rotation. STOP.
- NOT OK: Go to Step 3.
- Check the value in parameter :52.
Expected Result: Parameter :52 reads less than the actual generator current, which was measured by another meter.
Results:
- OK: Parameter :52 reads less than the actual generator current, which was measured by another meter. Slowly decrease parameter :05 until the currents match.
- NOT OK: Parameter :52 reads more than the actual generator current which is measured by another meter. Slowly increase parameter :05 until the currents match.
- On units with part numbers of 130-xxxx and older, check the value in parameter :16 and :17. Some combinations of gain parameters :16 and :17 may cause unstable operation. Try the default settings.
- On units with part numbers of 155-xxxx and newer, check the value in parameters :36 and :37. Some combinations of Gain parameters :36 and :37 may cause unstable operation. Try the default settings.
- If the problem only exists at low power levels, check the value in parameter :38. Try raising the value. This is not valid for the earlier digital voltage regulator, which does not have parameter :38.
Expected Result: The problem has been resolved.
Results:
- OK: The problem has been resolved. STOP.
- NOT OK: The problem has not been resolved. Go to Step 5.
- Remove the remote PF/KVAR adjust rheostat.
- Retry the operation of the generator set.
Expected Result: The problem has been resolved.
Results:
- OK: The problem has been resolved. STOP.
- NOT OK: The problem has not been resolved. Verify the CT sizing. The digital voltage regulator is sensitive to the CT sizing. The droop current transformer should be sized to provide no more than 5 VAC (RMS) at full rated load but not less than 3.5 VAC either. Proper sizing will significantly aid the accuracy at lower power levels. Go to Step 6.
- Turn the engine off.
- Disconnect all accessory wiring from terminals 3, 5, 6, 7, 40, 41, 42, 43, 44, 45, and 50. Remove the serial data link, if installed.
- Start the generator set and operate at "No Load".
Expected Result: The generator set operates properly.
Results:
- OK: The generator set operates properly. There is a problem with an accessory which has been disconnected. Reconnect one accessory. Operate the generator set again at "No Load". Continue this process of reconnecting one accessory at a time until the faulty accessory is found. STOP.
- NOT OK: If the generator set neutral is connected to ground or a neutral bus, then measure the neutral current. If a significant amount of circulating current is present, it may cause improper operation. A harmonic analysis is recommended in order to help determine the nature of the problem.
Caterpillar Information System:
Digital Voltage Regulator High Voltage - Troubleshoot
Digital Voltage Regulator Startup Profile Function
Cat® Digital Voltage Regulator Startup Procedure
Cat® Digital Voltage Regulator Service Tools
Digital Voltage Regulator Remote Communication
G3306 Engine Gas Pressure Regulator - Check
Digital Voltage Regulator Parameters
Digital Voltage Regulator Parameter Viewing and Configuring Procedure
Digital Voltage Regulator Loading and Stopping Profile
Digital Voltage Regulator General Information
Digital Voltage Regulator General Information
Digital Voltage Regulator Fault Handling
Digital Voltage Regulator Inaccurate Display - Troubleshoot
Digital Voltage Regulator Loss of Frequency Shutdown - Troubleshoot
Digital Voltage Regulator Low Voltage - Troubleshoot
Digital Voltage Regulator No Voltage - Troubleshoot
Digital Voltage Regulator Reverse VAR Condition - Troubleshoot
Digital Voltage Regulator Unstable Voltage - Troubleshoot
Digital Voltage Regulator Watchdog Alarm - Troubleshoot
Digital Voltage Regulator Troubleshooting
Digital Voltage Regulator Wiring Diagrams
G3300 Engines Governor - Inspect
3406E Generator Set Engines Hoses and Clamps - Replace
G3300 Engines Walk-Around Inspection - Exercise Inspection of Standby Generator Set Engines