A New Instruction to Change the Configuration Settings Of Generator Reverse Reactive Power is Now Available On Certain Generator Sets {4490}
- Generator Set
- C4.4 GEN SET (S/N: LC41-UP; LC51-UP; D4B1-UP; GLD1-UP)
- C6.6 GEN SET (S/N: LC61-UP; N6D1-UP)
A new instruction to change the configuration settings of generator reverse reactive power is now available to the Gensets that are listed above. Changing the settings will eliminate the reverse KVAr shutdowns and alarms due to incorrect threshold levels within the EMCP 4.2 control panel configuration file.
Perform any one of the following instructions to change the configuration settings of generator reverse reactive power.
Option 1: Change the threshold set point for Reverse Reactive Power
- Connect the EMCP control panel to Cat ET.
Show/hide table
Illustration 1 g06019725 - From the menu bar select "Service" > "Configuration".
Show/hide table
Illustration 2 g06019728 - In "Generator Reverse Power", select "Generator Reverse Reactive Power Warning Event percentage".
Show/hide table
Illustration 3 g06019731 - Change the percentage value to 15%.
Show/hide table
Illustration 4 g06019732 - In "Generator Reverse Power", select "Generator Reverse Reactive Power Shutdown Event percentage".
Show/hide table
Illustration 5 g06019742 - Change the percentage value to 20%.
Show/hide table
Illustration 6 g06019733 - Now the settings are changed as shown in Illustration 6.
Option 2: Deactivate the Reverse Reactive Power Feature
- Connect the EMCP control panel to Cat ET.
Show/hide table
Illustration 7 g06019725 - From the menu bar select "Service" > "Configuration".
Show/hide table
Illustration 8 g06019734 - In "Event Response Configuration - Generator Protection Event".
Show/hide table
Illustration 9 g06019736 - Select "Generator Reverse Reactive Power Warning Event Response Configuration".
Show/hide table
Illustration 10 g06019737 - Change the setting to "Disable Condition".
Show/hide table
Illustration 11 g06019739 - Select "Generator Reverse Reactive Power Shutdown Event Response Configuration".
Show/hide table
Illustration 12 g06019740 - Change the setting to "Disable Condition".
Show/hide table
Illustration 13 g06019741 - Now the settings are changed as shown in Illustration 13.
Caterpillar Information System:
Crankshaft Pre-Assembly Instructions for Well Stimulation Pumps {1202} Crankshaft Pre-Assembly Instructions for Well Stimulation Pumps {1202}
G3500 Engines Fluid Recommendations
G3500 Engines Refill Capacities
G3500 Engines Manual Stop Procedure
793F and 797F Off-Highway Trucks Braking System MID 116 - CID 1674 - FMI 05
793F and 797F Off-Highway Trucks Braking System MID 116 - CID 1674 - FMI 04
793F and 797F Off-Highway Trucks Braking System MID 116 - CID 1674 - FMI 03
G3500 Engines Starting the Engine
G3500 Engines Cold Weather Starting
G3500 Engines Configuration Parameters
A New Crankshaft Is Available For Certain C4.4 Engines {1202} A New Crankshaft Is Available For Certain C4.4 Engines {1202}
Technical Analysis 1 (TA1) Visual Inspection for Cold Planer {0372, 1000, 7000, 753T, 7565} Technical Analysis 1 (TA1) Visual Inspection for Cold Planer {0372, 1000, 7000, 753T, 7565}
G3500 Engines Belts - Inspect/Adjust/Replace
G3500 Engines Compressor Bypass - Check
C7.1 Commercial Marine Engine Water Temperature Regulator - Test
C7.1 Commercial Marine Engine Position the Valve Mechanism Before Maintenance Procedures
C9.3 Tier 4 Final Engines Fuel Lines
349F and 352F Excavators Machine System Specifications Suspension Seat
C9.3 Tier 4 Final Engines Air Lines
C9.3 Tier 4 Final Engines Turbocharger
C9.3 Tier 4 Final Engines Diesel Exhaust Fluid Lines
C9.3 Tier 4 Final Engines Water Lines
C9.3 Tier 4 Final Engines Water Lines
A New Filter is Available for the DEF Tank Adaptor for C7.1 Machine Engines {108H} A New Filter is Available for the DEF Tank Adaptor for C7.1 Machine Engines {108H}