UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Caterpillar


AC Interface PWA (MMS System Cabinet)

Usage:

UPS 600G DLD

Description



Illustration 1g01273197
(1) AC interface board

The AC interface board (ACI) (1) monitors the voltages that are on the following nodes:

  • System output

  • System bypass

  • System input

The ACI (1) also monitors the bypass currents of the system output.

Removal Procedure

Refer to Systems Operation, Testing and Adjusting, UENR3954, "Internal Component Preremoval Steps (MMS System Cabinet)" in order to shut down the system and gain access to internal components.

Note: Always practice "Electrostatic Discharge" (ESD) prevention when handling printed circuit assemblies.



    Illustration 2g01273196
    AC interface board

  1. Disconnect all connectors. Refer to Illustration 2. Verify each labeling on the connector with the location of the wire. Verify each label on each connector.

  2. Disconnect the ten white plastic standoffs that connect the board (1) to the left panel.

    Note: The board (1) must be removed from the standoffs without bending the board (1).

Installation Procedure

  1. Position the board (1) in the cabinet over the ten white standoffs that are connected to the left panel.

  2. Push the board (1) onto all the standoffs simultaneously. Verify that all standoffs are locked in place.

  3. Connect the wire connectors into the correct connectors on the board (1). Check the labels on each connector for proper placement. Refer to Illustration 2.

  4. Calibrate the AC interface board. Refer to Systems Operation, Testing and Adjusting, UENR3954, "System Voltage - Calibrate" and Systems Operation, Testing and Adjusting, UENR3954, "System Output Current - Calibrate".

Table 1
Fuse  Type 
ACI-F1  250 VAC, 5 A 
ACI-F2  250 VAC, 5 A 
ACI-F3  250 VAC, 5 A 
ACI-F4  250 VAC, 5 A 
ACI-F6  250 VAC, 2 A 

Caterpillar Information System:

UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Power Distribution PWA (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Parallel Cabinet Interface PWA
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Parallel Cabinet Controller PWA
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Fan Monitor PWA (MMS System Cabinet)
2013/03/22 A New Turbo Kit is Available for Certain 3500B Engines {1052, 1053}
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies EPO Reset Switch (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies General Purpose Interface PWA (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Front Panel Display (MMS System Cabinet)
C7.1 Engines Rocker Shaft and Pushrod - Install
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System Fuses (MMS System Cabinet)
C7.1 Engines Rocker Shaft - Disassemble
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
C7.1 Engines Rocker Shaft and Pushrod - Remove
C7.1 Engines Turbocharger - Install - Turbocharger for Side Mounted Engines
C7.1 Engines Turbocharger - Remove - Turbocharger for Side Mounted Engines
C7.1 Engines Turbocharger - Install - Turbocharger for Top Mounted Engines
C7.1 Engines Turbocharger - Remove - Turbocharger for Top Mounted Engines
C7.1 Engines Valve Mechanism Cover - Remove and Install
C7.1 Engines Valve Mechanism Cover Base - Remove and Install
C7.1 Engines Vibration Damper and Pulley - Install
C7.1 Engines Vibration Damper and Pulley - Remove
C7.1 Engines Wastegate Solenoid - Remove and Install
C7.1 Engines Water Pump - Install
C7.1 Engines Water Pump - Remove
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.