Electronic Modular Control Panel II (EMCP II) for EUI Engines Caterpillar


Engine/Generator Programming OP5

Usage:

3516B 1NW
OP5 is the option for programming the engine/generator setpoints. The engine/generator setpoints affect the proper operation and serviceability of the engine, and the accuracy of information shown on the display. The setpoints are programmed in the GSC at the factory.

The setpoints may require changing when the GSC is moved from one engine to another engine. Customer requirements and moving the GSC from one engine to another engine may require changes in the setpoints. The setpoints that are stored in the GSC must match the specified setpoints of the particular generator set. The setpoints are P01 to P24 and the setpoints are programmable. The setpoints are described in Table 1.

Procedure For Engine/Generator Programming

Note: Service Mode cannot be entered when the ECS is in the AUTO position.

Note: Any active shutdown fault (any shutdown indicator FLASHING) must be made inactive in order to access service mode. To temporarily change a shutdown fault from an active shutdown fault to an inactive shutdown fault, the shutdown fault must be no longer occurring. The fault must be corrected and the ECS must be turned to the OFF/RESET position. If the jumper from terminal 6 to terminal 9 is not installed on the ECS, the GSC does not power up in the OFF/RESET position and any active shutdown fault must be corrected before entering service mode.

  1. Turn the ECS to the STOP position in order to shut down the engine. Enter service mode and enter the password. OP 1 is showing on the lower display. See Systems Operation, "Procedure To Enter The Password" that is located within the topic Password Entry OP3 for more information.

  1. Press "SCROLL UP" key again. OP5 is showing on the lower display.

  1. Press "SELECT" key again. P01 is showing on the display. P01 is followed by the value of the setpoint.

  1. Press the "SCROLL UP" key or the "SCROLL DOWN" key. The next setpoint is showing with the value of the setpoint. Repeat this step until the desired setpoint is showing.

  1. Press the "SELECT" key. The value of the setpoint is flashing.

  1. Press the "SCROLL UP" key or "SCROLL DOWN" key in order to adjust the value of the setpoint.

    Note: Press and hold the appropriate "SCROLL" key in order to rapidly scroll through a large range of values.

  1. Press the "ENTER" key. The value of the setpoint stops flashing. Repeat steps 4, 5, 6 and 7 until all the desired setpoints are adjusted.

  1. Press "EXIT" key. "OP 1" is showing on the lower display.

  1. Press "EXIT" key. The display will return to the normal mode.

Table 1
OP5 Setpoints - Engine/Generator Programming (1)    
Setpoint     Name     Description     Range Of Value     Factory Default    
P01     Fuel Solenoid Type     Type of fuel system solenoid used on the generator set.     0 - ETR fuel solenoid
1 - ETS fuel solenoid    
0    
P02     Units Shown     Type of measurement units shown on the GSC display.     0 - English units (psi, degrees F)
1 - Metric units (kPa, degrees C)    
0    
P03     Shutdown Override For Engine Fault     GSC responds to a low engine oil pressure or high coolant temperature fault. (Determined by application or customer.)     0 - engine shutdown
1 - alarm only (shutdown override, no engine shutdown)    
0    
P04     Shutdown Enable For Sensor Fault     GSC responds to a diagnostic fault with the engine oil pressure sensor, coolant temperature sensor, oil temperature sensor, sensor power supply or coolant loss sensor. (Determined by application or customer.)     0 - alarm only (shutdown override, no engine shutdown)
1 - for engine shutdown    
0    
P05     Coolant Loss Sensor Installed     Tells whether or not the optional engine coolant loss sensor is installed on the generator set.     0 - generator sets without sensor
1 - generator sets with sensor    
0    
P06     Shutdown Override For Coolant Loss Fault     GSC+ responds to an engine coolant loss fault. (Determined by application or customer.)     0 - engine shutdown
1 - alarm only (shutdown override, no engine shutdown.)    
0    
P07     System Voltage     System voltage (battery voltage) of the generator set. (Determined by application or customer.)     0 - 24 DCV
1 - 32 DCV    
0    
P08     Upper Display Enable/Disable     Informs the GSC to enable or disable the showing of AC values on the upper display.     0 - upper display enabled
1 - upper display disabled    
0    
P09     Number Of Ring Gear Teeth     Number of teeth on the ring gear engine. Used by the GSC to determine engine speed.     95 to 350 teeth in increments of 1     183    
P10     Engine Overspeed     Engine speed used by the GSC to declare that an engine overspeed fault exists. The engine overspeed setpoint (for all 60 Hz applications) is 1.18 times the rated speed.     500 to 4330 rpm in increments of 10     2120 rpm    
P11     Crank Terminate Speed     Engine speed used by the GSC to disengage the starting motor during engine cranking.     100 to 1000 rpm in increments of 10     400 rpm    
P12     Oil Step Speed     Engine speed used by the GSC for distinguishing between rated speed and idle speed when a low oil pressure fault exists.     400 to 1800 rpm in increments of 10     1350 rpm    
P13 (2)     Low Oil Pressure Shutdown At Rated Speed     Oil pressure used by the GSC to declare that a low oil pressure shutdown fault exists with engine at rated speed (the engine must have exceeded the oil step speed for at least nine seconds).    
34 to 420 kPa (5 to 61 psi) in increments of one.    

205 kPa (30 psi)    
P14 (2)     Low Oil Pressure Shutdown At Idle Speed     Oil pressure used by the GSC to declare that a low oil pressure shutdown fault exist with the engine at idle speed (the engine must have been running for at least nine seconds and the engine speed must be less than oil step speed).    
20 to 336 kPa (3 to 49 psi) in increments of 1    

70 kPa (10 psi)    
P15 (3)     High Water Temperature Shutdown     Coolant temperature used by the GSC to declare a high coolant temperature shutdown fault exists (after a 10 second delay).    
94 to 123°C (201 to 253° F) in increments of 1    

107°C (225°F)    
P16     Low Water Temperature Alarm     Coolant temperature used by the GSC to declare that a low temperature alarm fault exists (after a 2 second delay). (Determined by application or customer.)    
0 to 36°C (32 to 97°F) in increments of 1    

21°C (70°F)    
P17     Total Cycle Crank Time     Cycle crank time used by the GSC to declare that an overcrank fault exists. ( Determined by application or customer.)     5 to 360 seconds in increments of 1     90 seconds    
P18     Cycle Crank Time     Amount of time the GSC cranks and then rests the starting motor during a single crank cycle. Determined by application of customer.)     5 to 300 seconds in increments of 1     10 seconds    
P19     Cooldown Time     Amount of time the GSC allows the engine to run after a normal shutdown is initiated. (Determined by application or customer.)     0 to 30 minutes in increments of one     5 minutes    
P20 (4)     AC Voltage     Full scale AC voltage of the generator. The GSC measures the AC voltage and shows it on the display. (Determined by application or customer.)     700, 150, 300, 500, 600, 750, 3.0k, 4.5k, 5.25k, 9.0k, 15.0k, 18.0k, 30.0k     700    
P21     AC Current Full Scale     AC current full scale is the ratio of the current transformers (CT) based on a 5A secondary. It does not represent the maximum AC current of the generator. The GSC measures the current and shows it on the display.     75, 100, 150, 200, 300, 400, 600, 800, 1000, 1200, 1500, 2000, 2500, 3000, 4000A     600A    
P22     GSC Engine Number     Informs other devices on the CAT Data Link (for example, CCM) of the engine number for the GS (Determined by application or customer).     01 through 08     01    
P23     Engine Type     Identifies the engine as a mechanical unit injector (MUI) diesel, spark ignited (gas), or electronic unit injector (EUI) diesel engine.     0 - MUI diesel
1 - Gas
2 - EUI diesel    
0    
P24 (6)     Crank Time Delay     Amount of time the GSC delays activation of the fuel control relay (FCR) during a crank cycle. This setpoint is for gas engines only. (Determined by application or customer.)     0 to 20 seconds in increments of 1     5 seconds    
( 1 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
( 2 ) When oil pressure drops to within 34 kPA (5 psi)of the "P13" or "P14"setpoint, a low oil pressure alarm is issued by the GSC and the optional alarm module (with the exception of the NFPA 99 RAN).
( 3 ) When coolant temperature rises to within 6°C (11°F)of the "P15 "setpoint, a high water temperature alarm is issued by the GSC and the optional alarm module (with the exception of the NFPA 99 RAN).
( 4 ) The values other than the default (700V) are for switchgear applications and require the use of external potential transformers and the removal of the AC voltage range jumper located in the relay module. See the topic AC Voltage Range Selection in the Testing And Adjusting section.
( 6 ) The P24 setpoint only functions when the P23 setpoint is set to 1 (gas engine).

Caterpillar Information System:

Electronic Modular Control Panel II (EMCP II) For MUI Engines Fault Log Clearing OP4
Electronic Modular Control Panel II (EMCP II) For MUI Engines Password Entry OP3
G3520C and G3520E Engines Flywheel Housing Cover
Electronic Modular Control Panel II (EMCP II) For MUI Engines Engine/Generator Setpoint Viewing OP2
Electronic Modular Control Panel II (EMCP II) For MUI Engines Fault Log Viewing OP1
Electronic Modular Control Panel II (EMCP II) For MUI Engines Service Mode
Electronic Modular Control Panel II (EMCP II) For MUI Engines Shutdown Mode
Electronic Modular Control Panel II (EMCP II) For MUI Engines Alarm Mode
G3606 and G3608 Engines Engine Design
P16, P20, P25, P28, P40 and P60 Pulverizer Crusher Tooth and Cutting Edge Bolts - Tighten
Electronic Modular Control Panel II (EMCP II) for EUI Engines Normal Mode
Electronic Modular Control Panel II (EMCP II) for EUI Engines Modes Of Operation
Electronic Modular Control Panel II (EMCP II) for EUI Engines Spare Input/Output Programming OP6
Electronic Modular Control Panel II (EMCP II) for EUI Engines Hourmeter Programming OP7
G3606 and G3608 Engines Engine Supervisory System
Electronic Modular Control Panel II (EMCP II) For MUI Engines Voltmeter/Ammeter Programming OP8
Electronic Modular Control Panel II (EMCP II) for EUI Engines Engine Setpoint Verification OP9
Electronic Modular Control Panel II (EMCP II) for EUI Engines AC Offset Adjustment OP10
Electronic Modular Control Panel II (EMCP II) for EUI Engines Fault Description
Electronic Modular Control Panel II (EMCP II) for EUI Engines AL Fault Codes
Electronic Modular Control Panel II (EMCP II) for EUI Engines SP Fault Codes
G3606 and G3608 Engines Ignition System
120H and 135H Motor Graders Power Train Duo-Cone Conventional Seals - Install
3406E Marine Engine Engine Design
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.