Electronic Modular Control Panel II (EMCP II) for EUI Engines Caterpillar


AC Offset Adjustment OP10

Usage:

3516B 1NW

Table 1
OP10 Setpoints (1) - AC Offset Adjustment    
Setpoint     Name     Description     Range Of Value     Factory Default    
PH A     Phase A Voltage Adjustment     Value used by the GSC in order to offset the voltmeter (for the phase A to neutral reading) from the actual voltage measurement.     -5.0% to +5.0% of measured voltage in increments of 0.04%     0    
PH B     Phase B Voltage Adjustment     Value used by the GSC to offset the voltmeter (for the phase B to neutral reading) from the actual voltage measurement.     -5.0% to +5.0% of measured voltage in increments of 0.04%     0    
PH C     Phase C Voltage Adjustment     Value used by the GSC to offset the voltmeter (for the phase C to neutral reading) from the actual voltage measurement.     -5.0% to +5.0% of measured voltage in increments of 0.04%     0    
PH A-B     Phase A-B Voltage Adjustment     Value used by the GSC to offset the voltmeter (for the phase A to phase B reading) from the actual voltage measurement.     -5.0% to +5.0% of measured voltage in increments of 0.04%     0    
PH B-C     Phase B-C Voltage Adjustment     Value used by the GSC to offset the voltmeter (for the phase B to phase C reading) from the actual voltage measurement.     -5.0% to +5.0% of measured voltage in increments of 0.04%     0    
PH C-A     Phase C-A Voltage Adjustment     Value used by the GSC to offset the voltmeter (for the phase C to phase A reading) from the actual voltage measurement.     -5.0% to +5.0% of measured voltage in increments of 0.04%     0    
( 1 ) The setpoints are programmed to the default value at the factory. The setpoints may be changed in order to satisfy the customer requirements or the application requirements.

OP10 is the option for adjusting the voltmeter readings of the GSC. This adjustment may be necessary when generator sets are operated in parallel. The GSC AC voltage measurements are calibrated at the factory. An accurate standard is used. However, when two generator sets are paralleled, the application may require the paralleled generator sets to have exactly the same voltage value. The AC offset of one GSC is changed to match the voltage value of another generator set.

Note: It is NOT recommended that the AC offset be altered under any other circumstances. Performing this procedure takes the GSC out of factory calibration.

Procedure For Voltmeter Offset Adjustment

The paralleled generator sets must be running at rated speed. The generator sets can then have the voltage adjustment made.

Note: Service mode cannot be entered when the ECS is in the AUTO position.

  1. Enter service mode on the GSC that is being adjusted. Enter the password. "OP 1" is showing on lower display. For more information, see the Systems Operation, "Password Entry OP3".

  1. Press "SCROLL UP" key nine times. "OP 10" is showing on the lower display.

  1. Press "SELECT" key. "AC CAL" is showing on lower display. The present A-B voltage value is showing on the upper display.

  1. Press "SELECT" key. The voltage value is flashing.

  1. Press the "SCROLL UP" key or press the "SCROLL DOWN" key in order to adjust the voltage. Adjust the value to exactly match the other generator set(s) that are running in parallel. Voltage value continues to flash.

  1. Press "ENTER" key. The value of the setpoint stops flashing.

  1. Press "SCROLL UP" key. Repeat steps 3, 4, 5 and 6 for the B-C voltage and the C-A voltage.

  1. Press "EXIT" key. "OP 1" is showing on the lower display.

  1. Press "EXIT" key. The display returns to the normal state.

Caterpillar Information System:

Electronic Modular Control Panel II (EMCP II) for EUI Engines Engine Setpoint Verification OP9
Electronic Modular Control Panel II (EMCP II) For MUI Engines Voltmeter/Ammeter Programming OP8
G3606 and G3608 Engines Engine Supervisory System
Electronic Modular Control Panel II (EMCP II) for EUI Engines Hourmeter Programming OP7
Electronic Modular Control Panel II (EMCP II) for EUI Engines Spare Input/Output Programming OP6
Electronic Modular Control Panel II (EMCP II) for EUI Engines Engine/Generator Programming OP5
Electronic Modular Control Panel II (EMCP II) For MUI Engines Fault Log Clearing OP4
Electronic Modular Control Panel II (EMCP II) For MUI Engines Password Entry OP3
G3520C and G3520E Engines Flywheel Housing Cover
Electronic Modular Control Panel II (EMCP II) For MUI Engines Engine/Generator Setpoint Viewing OP2
Electronic Modular Control Panel II (EMCP II) For MUI Engines Fault Log Viewing OP1
Electronic Modular Control Panel II (EMCP II) For MUI Engines Service Mode
Electronic Modular Control Panel II (EMCP II) for EUI Engines Fault Description
Electronic Modular Control Panel II (EMCP II) for EUI Engines AL Fault Codes
Electronic Modular Control Panel II (EMCP II) for EUI Engines SP Fault Codes
G3606 and G3608 Engines Ignition System
120H and 135H Motor Graders Power Train Duo-Cone Conventional Seals - Install
3406E Marine Engine Engine Design
Electronic Modular Control Panel II (EMCP II) for EUI Engines Diagnostic Codes
C27 PET GEN SET Electric Power Generation and C27 KNOCKDOWN K Petroleum Power Train Package Crankshaft Vibration Damper - Inspect
3600 Heavy Fuel Engines Cooling System Coolant (DEAC) - Change
3512 and 3516 EUI Engines and 784B, 785B, 789B and 793B Off-Highway Truck/Tractors Cylinder Block
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Alarm Modules
3600 Heavy Fuel Engines Cylinders - Inspect
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.