Electrical
Show/hide table
Specifications | |
---|---|
Regulation | 0.25% from no load to full load |
Regulator temperature drift | Less than 0.5% for any |
Configurable Volts/Hz characteristic | Two slope ranges adjustable from 1 to 10 V/Hz. See the Regulation Characteristic Illustration. |
Regulator response time | Maximum of 10 milliseconds. |
Regulator sensing | True RMS 3-phase sensing is standard. Single phase sensing is available. Variable sense range: 90 to 600 volts. |
Regulator stability | The regulator responds to the fundamental component of the sensed voltage and remains stable for total harmonic distortion of the generator output voltage waveform, up to 20%. |
Telephone influence factor (TIF) | Less than 50. Complies with MIL STD 461C Part 9 and VDE 0875 level N. |
Fine voltage adjust range | ± 10% of regulator sensing voltage. |
Regulator voltage gain (Line loss compensation) | Adjustable from 0 to 10%. |
Fault detection and identification | Diagnostics identify operation outside of programmed limits. Specific fault information is available even after the unit has been powered down. |
Regulator start-up voltage | Meets ISO8325-3 class G2 specifications. |
Harmonic tolerance | The digital voltage regulator maintains precise control of the generator output with up to 20% harmonic distortion in the generator output voltage. |
Reactive droop adjustment | Adjustable from 0 to 10%. |
Overexcitation protection | Shuts off generator output when excitation current exceeds normal operating currents for 15 seconds or instantaneous shutoff if output is shorted. |
Ambient operating temperature | |
Storage temperature range | |
Power dissipation | 5 watts at idle, 55 watts at rated output. |
Shock | Withstands up to 20 g's. |
Vibration | Withstands 4.5 g's at frequencies between 18 and 2000 Hz in three mutually perpendicular planes. |
Salt spray | Meets MIL-STD-810C, method 509.1. |
Sealing | Withstands up to |
Weight | |
Electromagnetic compatibility | Meets 89/336/EEC Electromagnetic Compatibility Directive. |
Power supply | 24 ± 6 volt DC power supply required (0.5 amp). |
Show/hide table
Illustration 1 | g00538141 |
Regulation Characteristic Illustration |
Show/hide table
Summary of Operating Parameters
For the 120 Volt PM and SE Generators |
|||
Power Input | V | 70-120
3 Ø |
|
Freq. Hz | 50-240 | ||
VA | 1500 | ||
Output Rating | Max. Continuous | V | 48 |
A | 12 | ||
Min. Forcing | V | 84 | |
A | 21 | ||
Sensing | V | 79 to 124 | |
Max. VA
Burden per Ø |
1 | ||
Reactive Droop Input | Max. Voltage | 5 | |
Max. VA
Burden |
1 | ||
Exciter Field Resistance | Min. Ohms | 3 | |
Max. Ohms | 10 |
Show/hide table
Summary of Operating Parameters
For the 240 Volt PM and SE Generators |
|||
Power Input | V | 70-120
3 Ø |
|
Freq. Hz | 50-240 | ||
VA | 1500 | ||
Output Rating | Max. Continuous | V | 48 |
A | 12 | ||
Min. Forcing | V | 84 | |
A | 21 | ||
Sensing | V | 125 to 249 | |
Max. VA
Burden per Ø |
1 | ||
Reactive Droop Input | Max. Voltage | 5 | |
Max. VA
Burden |
1 | ||
Exciter Field Resistance | Min. Ohms | 3 | |
Max. Ohms | 10 |
Show/hide table
Summary of Operating Parameters
For the 480 Volt PM and SE Generators |
|||
Power Input | V | 70-120
3 Ø |
|
Freq. Hz | 50 to 240 | ||
VA | 1500 | ||
Output Rating | Max. Continuous | V | 48 |
A | 12 | ||
Min. Forcing | V | 84 | |
A | 21 | ||
Sensing | V | 250 to 600 | |
Max. VA
Burden per Ø |
1 | ||
Reactive Droop Input | Max. Voltage | 5 | |
Max. VA
Burden |
1 | ||
Exciter Field Resistance | Min. Ohms | 3 | |
Max. Ohms | 10 |
Note: Permanent Magnet (PM) Generator
Note: Self-Excited (SE) Generator
Caterpillar Information System:
Digital Voltage Regulator Display and Keypad
Digital Voltage Regulator Dimensions
3412E and C30 Engines Heat Exchanger
Digital Voltage Regulator Customer Options
G3300 Engines Carburetor - Inspect/Recondition
3304B and 3306B Engines for Caterpillar Built Machines Exhaust Manifold - Remove and Install
G3408 and G3412 Engines Camshaft
G3300 Engines Belts - Replace
G3300 Engines Batteries - Replace
3412E and C30 Marine Engines Zinc Rods - Inspect/Replace
3126B Marine Engine Boost Pressure Sensor
3412E, C30 and C32 Marine Engines Aftercooler - Install
Digital Voltage Regulator Fault Classifications
Digital Voltage Regulator Fault Codes
Digital Voltage Regulator Fault Handling for Earlier Digital Voltage Regulators
Digital Voltage Regulator Fault Handling
Digital Voltage Regulator General Information
Digital Voltage Regulator General Information
Digital Voltage Regulator Loading and Stopping Profile
Digital Voltage Regulator Parameter Viewing and Configuring Procedure
Digital Voltage Regulator Parameters
G3306 Engine Gas Pressure Regulator - Check
Digital Voltage Regulator Remote Communication
Cat® Digital Voltage Regulator Service Tools