Generator Set Control Panel for Switchgear Conversion Caterpillar


CID 0821 FMI 04 Display Power Supply Voltage Below Normal - Test

Usage:

3412C 4BZ



Illustration 1g00565164

Schematic For The Display Power Supply

This diagnostic code is recorded when the main display module reads a below normal voltage of the display power supply circuit. Normal display power supply voltage is 9.0 ± 0.5 DCV. The schematic that is shown above represents a typical installation of the component. Verify the connector contact and wire numbers by using the Electrical System Schematic for the engine that is being serviced.

  1. Check The Voltage At The Main Display.

    1. Use the 7X-1710 Multimeter Probe Group. Check the voltage at the connector for the main display module. Measure the voltage from Contact 34 to Contact 2 (ground).

    1. DO NOT disconnect the harness from the Main Display Module.

      Expected Result: The voltage measures 9.0 ± 0.5 DCV.

      Results:

      • OK: The voltage is 9.0 ± 0.5 DCV. The display power supply voltage is correct. Check the main display module for the same diagnostic code. If the service code indicator is still ON, the main display module is faulty. Replace the module. See Testing and Adjusting, "Module - Replace". STOP.

      • Not OK: The voltage is NOT 9.0 ± 0.5 DCV. The display power supply voltage is NOT correct. Proceed to Step 2.

  1. Disconnect The Display Modules.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Disconnect the Gauge Cluster Modules.

    1. Turn the "ECS" switch to the "COOLDOWN/STOP" position.

    1. Continue to measure the voltage at the connector for the Main Display Module. Measure the voltage from Contact 34 to Contact 2.

    1. Reconnect the Gauge Cluster Modules from the engine harness one at a time. Between reconnections, measure the display's power supply voltage.

      Expected Result: The voltage that is measured is 9.0 ± 0.5 DCV.

      Results:

      • OK: The voltage is 9.0 ± 0.5 DCV. The display power supply is correct. Proceed to Step 3. STOP.

      • NOT OK: The voltage is NOT 9.0 ± 0.5 DCV after reconnecting one of the Gauge Cluster Modules. The Gauge Cluster Module that was just reconnected has a problem. Replace the Gauge Cluster Module. For more information on this subject, see Testing And Adjusting, "Module - Replace"." for a short to ground". Proceed to Step 3.

  1. Check For A Short To Ground.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Disconnect the engine harness from the main display module.

    1. Turn the "ECS" switch to the COOLDOWN/STOP position.

    1. At the engine harness connector for the main display module, measure the resistance between connector Contact 34 and Contact 2.

      Expected Result: The resistance that is measured is less than 5000 ohms.

      Results:

      • OK: The resistance is less than 5000 ohms. The engine harness is faulty. Repair the harness or replace the harness. STOP.

      • NOT OK: The resistance is greater than 5000 ohms. The harness circuit resistance is correct. The main display module is faulty. Replace the module. See Testing and Adjusting, "Module - Replace". STOP.

Caterpillar Information System:

Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines General Troubleshooting Information
G3606 and G3608 Engines Valve Mechanism - Install
Generator Set Control Panel for Switchgear Conversion CID 0821 FMI 03 Display Power Supply Voltage Above Normal - Test
797 Off-Highway Truck Power Train Relief Valve (Torque Converter Inlet)
Generator Set Control Panel for Switchgear Conversion CID 0819 FMI 02 Display Data Link Incorrect - Test
Generator Set Control Panel for Switchgear Conversion CID 0460 FMI 08 Pressure Sensor (Fuel) Abnormal Signal - Test
Generator Set Control Panel for Switchgear Conversion CID 0248 FMI 02 CAT Data Link Incorrect - Test
Generator Set Control Panel for Switchgear Conversion CID 0175 FMI 08 Temperature Sensor (Engine Oil) Abnormal Signal - Test
G3606 and G3608 Engines Valve Mechanism - Remove
Electric Protection System Energize-To-Shutoff (ETS) For Generator Set, Industrial and Marine Diesel Engines Troubleshooting the ETS Partial Protection System (OP, WT) - 3200-3400 Engines
Generator Set Control Panel for Switchgear Conversion CID 0172 FMI 04 Temperature Sender (Inlet Air) Voltage Below Normal - Test
Generator Set Control Panel for Switchgear Conversion CID 0110 FMI 08 Temperature Sensor (Engine Coolant) Abnormal Signal - Test
3412E, C30 and C32 Marine Engines Alternator - Remove and Install
797 Off-Highway Truck Power Train Relief Valve (Torque Converter Outlet)
Generator Set Control Panel for Switchgear Conversion CID 0827 FMI 08 Temperature Sensor (Left Exhaust) Abnormal Signal - Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Electric Protection System Functional Test
Generator Set Control Panel for Switchgear Conversion CID 0828 FMI 08 Temperature Sensor (Right Exhaust) Abnormal Signal - Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Overspeed Verification Test
3500B High Displacement Generator Set Engines Air Starting Motor - Inspect
3500B and 3500 Marine Propulsion Engines with EUI Option Electric Starting Motor - Inspect
3508B, 3512B, and 3516B High Displacement Generator Sets Prelube Pump - Inspect
3500B Locomotive Engines Air Compressor - Inspect
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Overspeed Calibration
3508B, 3512B, and 3516B High Displacement Generator Sets Engine Oil Filter Differential Pressure - Check
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.