G343 INDUSTRIAL ENGINE Caterpillar


Three Phase Neutral Connections

Usage:

Single Units

Three Wire: In a three phase, three wire system, the generator should normally be grounded according to local wiring codes. In some cases, however, it is undesirable to ground the neutral wire. For example, on boats a grounded neutral may increase the problem of electrolysis. In applications where definite measures are taken to prevent grounds to the load leads, an ungrounded neutral can be used. Be sure to check your local wiring codes.

Four Wire: In a three phase, four wire system, the neutral wire should be grounded according to local wiring codes. For only single unit operation, there should never be a need for a disconnect switch, or device, in the neutral line.

Multiple Units

Operation of multiple generators in parallel, having all neutrals grounded, may result in current circulating through the neutral connections. To eliminate the possibility of circulating currents, ground the neutral of only one generator. If multiple generators are alternated on line, a single pole single throw knife switch should be installed in the neutral ground circuit of each generator, so all but one neutral ground circuit can be opened. Be sure one neutral ground circuit is closed.