Snubber Assembly
Show/hide table
Illustration 1 | g01275457 |
(1) Heat Sink (2) Upper Mounting Bracket (3) Gate Lead Terminal Blocks (4) Snubber Assemblies (5) Lower Mounting Bracket (6) Clear Shield (7) Output Bus Bar (8) Input Bus Bar |
There are two Snubber Assemblies that are connected between the input of each static switch and output of each static switch. The assemblies are arranged across the input and output in opposing orientations.
The snubber assemblies prevent a false turn on of the Static Switch caused by voltage transients.
Removal
- Perform steps in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Static Switch Cabinet)" in order to de-energize the system and gain access to internal components.
- Cut the tie wrap that holds the Snubber Assembly to the clear shield.
- Remove the two bolts that connect the ends of the Snubber Assembly to the input and output bus bars of the static switch.
Refer to Illustration 2.
Show/hide table
Illustration 2 | g01275566 |
- Remove the Snubber Assembly.
Installation
- Place the Snubber Assembly in position as shown in Illustration 2.
- Attach the lugs of the snubber caps to the input and output power connectors using one bolt on each connector.
Refer to Illustration 3 for hardware installation.
Show/hide table
Illustration 3 | g01275575 |
(15) Nut (18) Bus Bars (19) Bolt (21) Split Washer (22) Flat Washer (27) Snubber Lug |
- Attach the Snubber Assembly to the clear shield with a new tie wrap so that the Snubber Assembly is not touching the bus bars.
Caterpillar Information System:
G3600 Engines Aftercooler
Machine Start Switch Key May Not Fit Properly{1416} Machine Start Switch Key May Not Fit Properly{1416}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Static Switch
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Universal Static Switch Interface PWA
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys System Fuse (Static Switch Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (Static Switch Cabinet)
TH48-E80 Petroleum Transmission Burn Prevention
G3600 Engines Exhaust Bypass Valve
C27 Industrial Engine and C27 Locomotive Engine Fuel System - Prime
TA19-M2WD and TA19-M4WD Agricultural Transmissions Relief Valve (Charge Pressure)
TA19-M2WD and TA19-M4WD Agricultural Transmissions Modulating Valve
TA22-4WD Agricultural Transmission Transmission Clutch
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Zig Zag Circuit Breaker
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Zig Zag Overload Relay
C9 On-highway Engine Valve Actuator
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Zig Zag Transformer
C280 Marine Auxiliary Engines System Configuration Parameters
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Current Transformer (Static Switch Cabinet)
C7 On-Highway Engine Camshaft - Remove
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Internal Component Preremoval Steps (Flywheel Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fuse (Flywheel Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Front Panel Display (Flywheel Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Purpose Interface PWA (Flywheel Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies EPO Reset Switch (Flywheel Cabinet)