Brake the flywheel if the unit is going to be shut down over 20 minutes. Simultaneously press the "Ctrl" key and the "X" key on a PC that is connected to the UPS through UPS View.
- Shut down the UPS.
The UPS needs shut down before any work is done to the cabinet. Refer to the information in the Systems Operation, Testing and Adjusting, "UPS Shutdown".
- Make sure the unit is either locked out or tagged DO NOT OPERATE.
- Remove all fuses.
- Make sure the generator engine is stopped.
- Make sure all batteries are disconnected.
- Make sure all capacitors are discharged.
- Make sure residual voltage in the rotor, stator and the generator is discharged.
- Discharge the capacitors.
Allow the capacitor banks in the UPS to purge down for 10 minutes.
When servicing or repairing electric power generation equipment: Failure to do so could result in personal injury or death. |
When servicing or repairing electric power generation equipment: Make sure the unit is off-line (disconnected from utility and/or other generators power service), and either locked out or tagged DO NOT OPERATE. Remove all fuses. |
- Unlock and Open Doors.
Open the doors of the cabinet using a 127.00 mm (5/16 inch) hex key on the upper and lower latches.