Usage:
NOTE: Tap sender when checking calibration. Readings should be taken on decreasing pressure.
Typical Example
Resistance at:
0 kPa (0 psi) ... 0 to 3.0 Ohms
70 kPa (10 psi) ... 5 to 16 Ohms
550 kPa (80 psi) ... 90 Ohms
Temperature
5L7442
Resistance at:
93°C (200°F) ... 800 to 900 Ohms
5L7443
Resistance at:
38°C (100°F) ... 403 to 493 Ohms
71°C (160°F) ... 118 to 138 Ohms
104°C (220°F) ... 44 to 49 Ohms
6N5926
Inspection procedure: The resistance of sender must fall within the limits shown in chart at indicated bath temperature with sender in a continuous flow bath with series resistance and applied voltage specified in chart. Bath medium shall be U con oil spec. 50-HB-280X with flow controlled to 228.6 to 254.0 mm per second. Power shall be applied for minimum of seven minutes before inspection.