ELECTRONIC MODULAR CONTROL PANEL (EMCP) Caterpillar


Testing And Adjusting

Usage:

Troubleshooting

Introduction

On the pages that follow are two lists of possible problems; Diagnosed Problems List and Undiagnosed Problems List. Before checking the list of problems, check the ECM display for any diagnostic codes. These codes aid in finding the problem (see Diagnosed Problems List).


NOTICE

Before checking the list of problems, check the battery voltage of all electronic controls. At the power terminal connections, the required voltage measured between battery positive (B+) and battery negative (B-) is from +15 to +45 DCV. It is possible for battery voltages below +15 DCV to cause temporary failures of the electronic controls. It is possible for battery voltages above +45 DCV to cause permanent damage of the electronic controls and require correcting before troubleshooting any further. To locate the power terminal connections, refer to the following chart and the Schematics And Wiring Diagrams section.


Before replacing anything, inspect all control, component and harness connections. Loose connections could cause electrical problems. Make sure the connections are tight before testing continues.

More than one faulty component or control could cause electrical failures. Find and correct the cause of an electrical failure before making any replacements.

Identify the particular type of problem from the Problem List, then go directly to that problem. However, when beginning the procedure for that problem, start at Step 1 and follow through the step by step procedure. The Steps in a particular problem provide a definite sequence for a logical, one by one elimination of many variables. These steps are arranged in order from the more probable/easiest to check, to the less probable/more complex to check.

When the cause of the problem is found and corrected, stop the test. Do NOT continue through the complete procedure.

------ WARNING! ------

When servicing or repairing electric power generation equipment, do the following:

a. Make sure the unit is off-line (disconnected from utility power service and/or other generators), and either locked out or tagged DO NOT OPERATE.

b. Make sure the generator engine is stopped.

c. Make sure all batteries are disconnected.

d. Make sure all capacitors are discharged.

When power generation equipment is in operation to make tests and/or adjustments, high voltage and current are present. Make sure the testing equipment is designed for and correctly operated for the high voltage and current tests. Failure of improper test equipment presents a high voltage shock hazard to its user.

--------WARNING!------

------ WARNING! ------

When the engine-generator, or any source to which the engine-generator is synchronized to, is operating, voltages up to 600V are present in the control panel.

Do NOT short these terminals with line voltage to ground with any part of the body or any conductive material. Loss of life or injury could result from electrical shock or injury from molten metal.

--------WARNING!------

------ WARNING! ------

Do NOT connect generator to a utility electrical distribution system, unless it is isolated from the system. Personal injury or death is possible by electrical feedback into the distribution system.

Open and secure main distribution system switch or, if the connection is permanent, install a double throw transfer switch to prevent electrical feedback. Some generators are specifically approved by a utility to run in parallel with the distribution system and isolation is NOT required. Always check with the utility as to the applicable circumstances.

--------WARNING!------

Test Instruments

Caterpillar Digital Multimeter (6V7070) Or Equivalent - is used for many of the voltage and resistance checks. Rectifiers are also checked with the special diode function. For further information on using the digital multimeter, see Special Instruction, Form No. SEHS7734.

NOTE: See the following WARNING if generator is rated over 600 volts.

------ WARNING! ------

On generators with higher than 600 volts rating, do NOT use direct-reading test equipment to measure the voltage or line current, (even though the instrument has higher voltage capacity). Only use voltage and current transformers with a high voltage reading. On power circuits higher than 600 volts, insulation failure is possible on direct reading meters and present a high voltage shock to the user.

--------WARNING!------

Problems

The engine control module (ECM) provides built-in diagnostic capabilities. The diagnostics are designed to make service and maintenance of the system as simple as possible. Faults that are diagnosed by the ECM are listed in the Diagnosed Problems List. Faults that are NOT diagnosed by the ECM are listed in the Undiagnosed Problems List.

Diagnosed Problems

For diagnosed problems, the diagnostic codes are displayed on the same display as the service hours, engine speed, battery voltage, engine oil pressure, and engine coolant temperature. When a diagnostic code is displayed, the arrow that indicates which of the above parameters are displayed is missing and a flashing "dIAG" is displayed. If several faults are present, the diagnostic codes are displayed in sequence. The diagnostic code is cleared from display by turning the engine control switch (ECS) to the OFF/RESET position. Before attempting a repair, move the ECS to the OFF/RESET position and restart engine to see if problem recurs.

Diagnosed Problems List

Problem A - ECM Display = 01 dIAG, no magnetic speed pickup (speed sensor) signal.

Problem B - ECM Display = 02 dIAG, no oil pressure/temperature module signal.

Problem C - ECM Display = 03 dIAG, a problem with inputs from the ECS.

Problem D - ECM Display = 04 dIAG, loss of setpoints programmed into the ECM memory.

Problem E - ECM Display = 05 dIAG, engine shuts down with no shutdown command from the ECM.

Problem F - ECM Display = 06 dIAG, internal failure of ECM or unstable voltage supply.

Problem G - ECM Display = 07 dIAG, internal ECM programming switch does NOT match program.

Problem H - ECM Display = 08 dIAG, temperature probe problem.

Problem I - ECM Display = 09 dIAG, oil pressure probe problem. ECM displays high oil pressure when the engine is NOT running and has cooled down.

Problem A

ECM Display = 01 dIAG, no magnetic speed pickup (speed sensor) signal.

Procedure

1. Disconnect the speed sensor leads from terminals 1 and 7 on the ECM. Measure the resistance between the speed sensor leads. Also measure the resistance between each speed sensor lead and ground.

* Resistance between leads is between 100 and 270 ohms. Also, the resistance between each lead and ground is above 5000 ohms.

Speed sensor wiring is okay. Go to Step 2.

* Resistance is below 100 ohms.

Short circuit in wiring or sensor. Repair wiring or replace speed sensor as needed.

* Resistance is above 270 ohms.

Wire is broken or connector is defective. Repair broken wire or bad connection or replace speed sensor as needed.

* Resistance between sensor leads and ground is below 5000 ohms.

Speed sensor is grounded. Repair wiring harness or replace speed sensor as needed.

2. Reconnect speed sensor leads to terminals 1 and 7 on the ECM. Measure the AC voltage across terminals 1 and 7 on the ECM while cranking the engine. In order to perform this Step, a crank speed of 250 rpm or greater is required.

* Speed sensor voltage is 1.0 ACV or greater.

Attempt to start. If 01 dIAG reappears, replace speed sensor. If 01 dIAG still appears after replacing the sensor, replace ECM.

* Speed sensor voltage is below 1.0 ACV.

Adjust speed sensor gap (see Service Procedure F). If speed sensor voltage is still low, replace speed sensor.

Problem B

ECM Display = 02 dIAG, no oil pressure/temperature module signal.

Problem B is divided into separate procedures for the two different style pressure/temperature modules used.

* Procedure B1 is used for the earlier pressure/temperature modules (engine oil line connects to the module).
* Procedure B2 is used for the current pressure/temperature modules (no engine oil line connects to the module, wires connect the engine oil pressure sensor to the pressure/temperature module).

NOTE: Without oil pressure protection the ECM shuts down the generator set. During troubleshooting or in an emergency situation, it is possible to operate with no oil pressure or coolant temperature protection by reprogramming the ECM (see Service Procedure A). Install oil pressure and coolant temperature gauges to give the operator an indication of engine conditions. After the problem is fixed, make sure to reprogram the ECM.

If the ECM is programmed to operate with no oil pressure and water temperature protection and the 02 dIAG occurs, it is possible the ECM does NOT reset. However, the engine continues to run. Check for loose connections or low battery voltage before replacing ECM.

Procedure B1

1. Measure the voltage between terminal 4 of the ECM and battery negative (B-). Disconnect the 3 pin connector at the press/temp module and again measure the voltage between terminal 4 and battery negative (B-). Disconnect the wire from terminal 4 and again measure the voltage between terminal 4 of the ECM and battery negative (B-).

* Voltage is between 11 and 15 DCV in all cases.

The power supply is okay. Go to Step 2.

* Voltage is above 20 DCV in all cases.

Replace ECM. It is likely that the press/temp module is damaged also.

* Voltage is above 15 DCV but below 20 DCV in all cases or below 11 DCV in all cases.

Replace ECM.

* Voltage goes from below 11 DCV to between 11 and 15 DCV when the 3 pin connector is disconnected.

Replace press/temp module.

* Voltage goes from below 11 DCV to between 11 and 15 DCV when wire to terminal 4 is disconnected.

Repair grounded wiring between ECM and press/temp module.

* Voltage is above 15 DCV initially but is between 11 and 15 DCV when wire to terminal 4 is disconnected.

Repair wiring between ECM and press/temp module. If wire is shorted to battery positive (B+), failure of the press/temp module is probable and replacement is advised.

2. Reconnect any wires that were disconnected in Step 1. Measure the voltage on terminal 5 of the ECM with respect to battery negative (B-).

* Voltage is 4 to 8 DCV.

The voltage level is okay. Go to Step 3.

* Voltage is above 8 DCV.

Go to Step 4.

* Voltage is below 4 DCV.

Recheck supply voltage to the press/temp module (Step 1). If okay, disconnect wire to terminal 5 of ECM. If voltage at terminal 5 now goes above 8 DCV, replace the press/temp module. If voltage at terminal 5 remains low, replace the ECM.

3. Reconnect any wires that were previously disconnected. Disconnect the 3 pin connector at the pressure/temperature module. Measure the voltage between battery negative (B-) and pin 1 of the wiring harness connector. Also measure resistance between battery negative (B-) and pin 2 of this connector.

* Voltage is between 11 and 15 DCV and resistance is below 1 ohm.

Supply to press/temp module okay. Replace press/temp module.

* Voltage is below 11 DCV.

Repair wiring between ECM and press/temp module.

* Resistance is above 5 ohms.

Repair wiring between press/temp module and battery negative (B-).

4. Reconnect any wires that were previously disconnected. Disconnect the 3 pin connector at the pressure/temperature module. Measure the voltage between battery negative (B-) and pins 1 and 3 of the wiring harness connector. Also measure resistance between battery negative (B-) and pin 2 of this connector.

* Voltage at pin 1 is below 11 DCV or voltage at pin 3 is below 8 DCV.

Repair wiring between ECM and press/temp module.

* Resistance is above 5 ohms.

Repair wiring between press/temp module and battery negative (B-).

* Voltage at pin 1 is between 11 and 15 DCV; and voltage at pin 3 is above 8 DCV; and resistance is below 1 ohm.

Replace the press/temp module.

Procedure B2

1. Measure the voltage between terminal 4 and battery negative (B-) of the ECM. Disconnect the 3 pin connector at the press/temp module and again measure the voltage between terminal 4 and battery negative (B-). Disconnect the wire from terminal 4 and again measure the voltage between terminal 4 of the ECM and battery negative (B-).

* Voltage is between 11 and 15 DCV in all cases.

The power supply is okay. Go to Step 2.

* Voltage is above 20 DCV in all cases.

Replace ECM. It is likely that the press/temp module is also damaged.

* Voltage is above 15 DCV but below 20 DCV in all cases or below 11 DCV in all cases.

Replace ECM.

* Voltage goes from below 11 DCV to between 11 and 15 DCV when the 3 pin connector is disconnected.

Replace press/temp module.

* Voltage goes from below 11 DCV to between 11 and 15 DCV when wire to terminal 4 is disconnected.

Repair grounded wiring between ECM and press/temp module.

* Voltage is above 15 DCV initially but is between 11 and 15 DCV when wire to terminal 4 is disconnected.

Repair wiring between ECM and press/temp module. If wire is shorted to battery positive (B+), failure of the press/temp module is probable and replacement is advised.

2. Reconnect any wires that were disconnected in Step 1. Measure the voltage on terminal 5 of the ECM with respect to battery negative (B-).

* Voltage is 4 to 8 DCV.

The voltage level is okay. Go to Step 3.

* Voltage is above 8 DCV.

Go to Step 4.

* Voltage is below 4 DCV.

Recheck supply voltage to the press/temp module (Step 1). If okay, disconnect wire to terminal 5 of ECM. If voltage at terminal 5 now goes above 8 DCV, replace the press/temp module. If voltage at terminal 5 remains low, replace the ECM.

3. Reconnect any wires that were previously disconnected. Disconnect the 3 pin connector at the pressure/temperature module. Measure the voltage between battery negative (B-) and pin 1 of the wiring harness connector. Also measure resistance between battery negative (B-) and pin 2 of this connector.

* Voltage is between 11 and 15 DCV and resistance is below 1 ohm.

Supply to press/temp module okay. Go to Step 5

* Voltage is below 11 DCV.

Repair wiring between ECM and press/temp module.

* Resistance is above 5 ohms.

Repair wiring between press/temp module and battery negative (B-).

4. Reconnect any wires that were previously disconnected. Disconnect the 3 pin connector at the pressure/temperature module. Measure the voltage between battery negative (B-) and pins 1 and 3 of the wiring harness connector. Also measure resistance between battery negative (B-) and pin 2 of this connector.

* Voltage at pin 1 is below 11 DCV or voltage at pin 3 is below 8 DCV.

Repair wiring between ECM and press/temp module.

* Resistance is above 5 ohms.

Repair wiring between press/temp module and battery negative (B-).

* Voltage at pin 1 is between 11 and 15 DCV. Also, voltage at pin 3 is above 8 DCV. Also, resistance is below 1 ohm.

Go to Step 5.

5. Reconnect any wires that were previously disconnected. At the pressure/temperature module, disconnect the 3 pin harness connector that goes to the engine oil pressure sensor. At the module harness connector, measure the voltage between pin A (red power wire) and pin B (yellow ground wire).

* Voltage is less than 4.5 DCV.

Repair wiring between module and pressure sensor. If a wiring problem is NOT found, replace the pressure/temperature module.

* Voltage is greater than 4.5 but less than 6.0 DCV.

Replace the engine oil pressure sensor which is located on the engine.

* Voltage is greater than 6.0 DCV.

Replace the pressure/temperature module. It is likely that the pressure sensor is also damaged.

Problem C

ECM Display = 03 dIAG, a problem with inputs from the ECS.

Procedure

The engine control switch (ECS) must connect ECM terminal 9 or 10 or 11 or 12 to battery negative (B-). If both 9 and 11 are connected to negative, auto start occurs. Any wiring error or loose connection causes an 03 dIAG code. Check ECS and wiring from ECS to ECM repair as needed.

* Wiring and ECS check okay.

Replace the ECM.

* Wiring or ECS check bad.

Repair or replace components as necessary.

Problem D

ECM Display = 04 dIAG, loss of setpoints programmed into the ECM memory.

Procedure

Reprogram the ECM (see Service Procedure A) and turn the ECS to reset.

* 04 dIAG does NOT recur.

Problem solved.

* 04 dIAG recurs.

Replace ECM.

Problem E

ECM Display = 05 dIAG, engine shuts down with no shutdown command from the ECM.

NOTE: The following Steps are labeled ETS and/or ETR. Perform the Steps which apply to the corresponding type of system. In the following procedures, consider latching fuel systems as ETS fuel systems. See Service Procedure A on how to identify energize to run (ETR) or energize to shutdown (ETS) systems.

Procedure

1. (ETS Or ETR System). Crank the engine by moving the ECS to the MANUAL position and observe the action of the governor and fuel rack. Also observe the position of the air shutoff (if so equipped). If engine does NOT crank, troubleshoot starting system according to Undiagnosed Problem 2.

If an electronic governor is used, measure the voltage supplied to the governor.

* Fuel rack and governor moves in Fuel On direction, and air shutoff lever is in RUN position.

The problem is in the engine or fuel system. Refer to engine portion of the Service Manual.

* Fuel rack does NOT move or is NOT possible to observe. Governor does NOT move in Fuel On direction or is NOT possible to observe.

Check fuel level. Fill and prime fuel system if level was low. Go to Step 2A (ETS) or Step 2B (ETR) if level was low.

* Air shutoff is in the SHUTOFF position.

Reset air shutoff. Go to Step 4 if shutoff does NOT reset or if it trips on each attempt to start.

* An electronic governor is used and supply voltage is greater than 15 volts.

Problem is in governor or actuator system. For Woodward 2301 Electric Governor, refer to SENR2928 service manual. For Woodward 2301A Speed Control, refer to SENR4676 service manual. For Woodward 2301A Load Sharing Governor, refer to SENR3585 service manual.

* An electronic governor is used and the supply voltage is less than 15 volts.

Problem is in wiring to the electronic governor. Go to Step 3.

2A (ETS). Remove fuse F6 (fuse between terminals R and S) from back of ECM. Prepare to use manual shutoff if needed. Crank the engine.

* Engine starts and runs.

The fuel relay (FCR) is energizing the shutoff (or latching) solenoid. Check resistance between terminals S and 23. If it is below 5 ohms, go to Service Procedure B. If not, look for wiring errors that might supply voltage to shutoff solenoid. On 3408 and 3412 engines, it is possible the auxiliary fuel control relay is energizing the fuel solenoid. Check relay contacts and wiring. Replace if necessary.

* Engine does NOT start.

The shutoff solenoid is stuck or the fuel rack is stuck in the SHUTOFF position or solenoid is NOT correct for the application. Find the source of the problem and correct.

2B (ETR). Connect a jumper between terminals S and 23 of the terminal strips on the back of the ECM and crank the engine. Prepare to use manual shutoff if needed.

* Engine starts and runs.

The fuel control relay (FCR) relay was NOT energizing the fuel solenoid. Check FCR (see Service Procedure B).

* Engine does NOT start.

The fuel solenoid is defective or stuck, or solenoid is NOT correct, or the fuel rack is stuck in the SHUTOFF position. If there is no voltage at terminal S, check fuse F6 and replace if open. Find the source of the problem and correct.

On 3408 and 3412 engines, it is possible the auxiliary fuel control relay is faulty. Check relay contacts and wiring. Replace if necessary. Also check fuses F6 and F10 on subpan. Replace if necessary.

3 (ETS or ETR System). Crank the engine and measure the DC voltage between the following points and battery negative (B-): the battery positive (B+) terminal on the preregulator (located under 2301 in control panel), terminal 1 of the F9 fuse if preregulator is NOT used, terminal 20 on the ECM, terminal M on the ECM and terminal L on the ECM.

* Voltage is below 15 DCV at all of these points.

Battery voltage is low or wiring from battery to control panel is defective. Charge battery or repair wiring as needed.

* Voltage is above 15 DCV on terminal L of ECM only. Voltage is low at all other points.

Fuse F4 is blown. Replace fuse.

* Voltage is above 15 DCV on terminals M and L of the ECM. Voltage is low at all other points.

Run Relay contact is NOT closing. Check the ECM for diagnostic codes before checking the relay. (See Service Procedure B.)

* Voltage is above 15 DCV on terminals M and L and 20 of the ECM. Voltage is low at all other points.

Check the wiring between terminal 20 of the ECM and the battery positive (B+) terminal on the preregulator or F9 fuse if preregulator is NOT used. Repair as needed.

* All voltages are above 15 DCV. The voltage at the electronic governor remains low.

The preregulator fuse or the F9 fuse or the preregulator or wiring is defective. Repair as needed.

STEP 4. Check for another diagnostic code. If none is displayed, remove fuse F7 (between terminals T and U) from back of ECM.

* Air shutoff does NOT trip and engine starts.

The air shutoff relay (ASR) is energizing the solenoid. Check resistance between terminals U and 24 on the ECM. If it is below 5 ohms, go to Service Procedure B. If not, look for wiring errors that might supply voltage to shutoff solenoid.

* Air shutoff continues to trip.

The air shutoff is defective. See the air shutoff section of the Engine Service Manual.

* Air shutoff does NOT trip and engine does NOT start.

Check diagnostic code and return to Step 1 if code 05 dlAG is still displayed.

Problem F

ECM Display = 06 dlAG, internal failure of ECM or unstable voltage supply.

Procedure

Reset and wait 90 seconds. Restart to see if problem re-occurs. If it does, look for possible sources of electrical noise such as loose connections in supply to ECM. Install jumper between terminals D and F of the ECM. Reset and start engine.

* 06 dlAG recurs only when engine is running.

Loose connection between battery positive (B+) or battery negative (B-) to ECM is still likely. Run separate supply wires. Replace ECM if this fails to correct problem.

* 06 dlAG recurs when engine is NOT running.

Loose connection still possible but less likely. Replace ECM unless an external electrical noise source is identified.

* 06 dlAG does NOT recur.

Check crank termination relay (CTR) or fuel control relay (FCR) contacts or leave jumper (D to F) connected if battery drain is NOT a problem.

* 06 dlAG reoccurs when engine is starting and engine cranks slowly or NOT at all.

Battery voltage is low. Charge and/or replace batteries.

Problem G

ECM Display = 07 dlAG, internal ECM programming switch does NOT match program.

The 07 dlAG code simply indicates that the setpoint value programmed into setpoint 02 does NOT match the position of the rotary switch.

NOTE: After programming, it is possible for the 07 dlAG code to appear if the system is NOT reset.

Procedure

Turn the ECS to the OFF/RESET position. Next, turn the ECS to the RUN position.

* 07 dlAG code is NOT present.

There is no 07 dlAG code failure.

* 07 dlAG code is still present.

The value of setpoint 02 does NOT match the rotary switch position. See Service Procedure A.

Problem H

ECM Display = 08 dlAG, temperature probe problem.

Procedure

If ambient temperature is near -40°C (-40°F), use heaters to warm up the engine before startup. If temperature is warmer, check connectors between oil pressure/temperature transducer (sensor) and the temperature probe before going to Service Procedure G.

Problem I

ECM Display = 09 dlAG, ECM displays high oil pressure when the engine is NOT running and has cooled down.

NOTE: Problem I (09 dlAG) applies only to the current pressure/temperature modules (no engine oil line connects to the module, wires connect the engine oil pressure sensor to the pressure/temperature module).

Procedure

Record the oil pressure the ECM is displaying. Disconnect the harness connector of the engine oil pressure sensor. Record the oil pressure the ECM is now displaying.

* Both pressures displayed are above 965 kPa (140 psi).

In the wiring from the pressure/temperature module to the pressure sensor, check for a short between the green signal wire (pin C) and the red power wire (pin A).

* The first displayed pressure is above 480 kPa (70 psi) but below 760 kPa (110 psi). Also, the second displayed pressure is 0 kPa (0 psi).

In the harness connector, check for an open ground circuit (pin B, yellow wire).

* The first displayed pressure is 965 kPa (140 psi). Also, the second displayed pressure is 0 kPa (0 psi).

Check the pressure sensor wiring and correct as needed. If no wiring problem found, replace the engine oil pressure sensor.

* Both pressures are above 0 kPa (0 psi) but below 965 kPa (140 psi).

Replace the pressure/temperature module.

Undiagnosed Problems

Undiagnosed problems are those problems which are indicated by incorrect operation or the fault LED's on the ECM. Undiagnosed problems are NOT indicated on the LCD display of the ECM. When an undiagnosed problem occurs, see the Undiagnosed Problems List and perform the corresponding problem procedure.

Undiagnosed Problems List

Problem 1 - Engine cranks but does NOT start or shuts down immediately after starting.

Problem 2 - Engine does NOT crank.

Problem 3 - Starting motor remains engaged or continues to run after engine has started.

Problem 4 - Engine shutdown occurs, all six LED fault indicators on the ECM flash.

Problem 5 - LED fault indicator on the ECM does NOT reset.

Problem 6 - Engine shutdown occurs, overcrank LED is lit.

Problem 7 - Engine shutdown occurs, overspeed LED is lit.

Problem 8 - Engine shutdown occurs, low oil pressure LED is lit.

Problem 9 - Engine shutdown occurs, high coolant temperature LED is lit.

Problem 10 - Engine shutdown occurs, emergency stop LED is lit.

Problem 11 - Engine shutdown occurs, reverse power relay LED is lit.

Problem 12 - No engine shutdown when a fault occurs.

Problem 13 - Engine shutdown with no LED's lit or diagnostic codes on ECM.

Problem 14 - Remote annunciator or control panel alarm module data link controlled LED's all flash at a rate of once per two seconds (0.5 Hz).

Problem 15 - ACM displays all dashes "---".

Problem 16 - ACM Hz displays "LO" and voltmeter displays "0".

Problem 1

Engine cranks but does NOT start or shuts down immediately after starting.

Procedure

Look at the ECM Display.

* Overcrank LED's is lit (is on).

Reset control and check cycle crank time and overcrank time setpoints (see Service Procedure A). Normally both times are 5 seconds or more. If engine does NOT start in 5 seconds, troubleshoot engine/fuel system/governor.

* Overcrank LED did NOT light (if off). If the engine started and then shut down, an 05 dlAG code is displayed.

Go to Diagnosed Problem E, diagnostic code 05, regardless if 05 dlAG is displayed or not.

* Some other diagnostic code is displayed.

Go to Diagnosed Problem List and do problem indicated by the diagnostic code.

Problem 2

Engine does NOT crank.

Procedure

1. Look at ECM Display.

* Display is completely blank regardless of the engine control switch setting.

Go to Step 2.

* All 6 LED fault indicators are on.

Go to Undiagnosed Problem 4, all six LED fault indicators are on.

* One or more but NOT all of the 6 LED fault indicators are flashing.

There is a shutdown fault. Go to Undiagnosed Problem List and do the corresponding problem.

* A diagnostic code is displayed.

Go to Diagnosed Problem List and do problem indicated by the diagnostic code.

* No LED fault indicators are lit and no diagnostic code is displayed.

Defect is in the starting circuit. Allow five minutes for CB2 in control panel to cool down and automatically reset. Attempt to start the engine. If engine does NOT crank go to Step 4.

2. Turn the engine control switch to Stop. Measure the voltage and check the polarity at terminals 1 and F of the ECM. With the positive meter lead on terminal F and the negative meter lead on terminal 1, the correct voltage is between +15 and +45 DCV.

* Polarity and voltage are correct.

Replace the ECM.

* Polarity is correct, but voltage level is below +15 DCV.

Check the battery voltage and check the wiring from the battery to the ECM. As needed, recharge or replace the batteries and repair the wiring. Refer to the DC Schematic in the Schematics And Wiring Diagrams section.

* Polarity is NOT correct.

Check and correct any improper connections between the battery and the ECM. Refer to the DC Schematic in the Schematics And Wiring Diagrams section. Go to Step 3.

3. Check the part number on the back of the relay housing located on the rear of the ECM.. The part number is 9W2126-XX, where XX is a number greater than 01.

* XX is the number 07 or less.

Do NOT try to start the engine. Replace the ECM.

* XX is the number 08 or higher.

Try to start the engine. If engine still does NOT crank and the display is not blank, go back to Step 1.

4. Look at the battery voltage displayed on the ECM Display.

* Voltage is low (1 to 20 volts).

Charge the battery or repair loose connections between battery cable terminal and battery.

* Voltage is above 20 volts.

Go to Step 5.

5. Prepare for the engine to crank. Momentarily connect a wire between terminals 1 and 5 on the generator mounted terminal strip (TS1).

* Engine cranks.

Go to Step 6.

* Engine does NOT crank.

Check to see if terminals 4 and 5 on TS1 are jumpered together. If so, the magnetic switch (see Service Procedure E) or the pinion solenoid or the starting motor is defective. Repair or replace as required.

NOTE: Terminals 4 and 5 are NOT jumpered together when the optional prelube pump is installed. When oil pressure is 1 psi or greater during the cranking cycle, the prelube pump pressure switch closes. This connects terminal 4 and 5 together. First ensure that the prelube system operates properly. Then, go to Step 6. Refer to the Schematics And Wiring Diagrams section.

6. Attempt to start engine (ECS in manual) and measure voltage between ECM terminal 25 and battery negative (B-), terminal W and battery negative (B-), battery positive (B+) and battery negative (B-).

* All voltages are below 20 DCV.

Battery or wiring to ECM is defective. Repair or replace defective parts.

* Only the voltage on terminal 25 is below 20 DCV.

Check the starting motor relay (SMR) (see Service Procedure B).

* The voltage on terminals 25 and W are below 20 DCV. The battery voltage is above 20 DCV.

Replace fuse F8. Also check wiring from terminal W to battery positive (B+).

Problem 3

Starting motor remains engaged or continues to run after engine has started.

Procedure

1. Turn the engine control switch to Stop. Check the polarity at terminals 1 and F of the ECM. With the positive meter lead on terminal F and the negative meter lead on terminal 1, the correct voltage is between +15 and +45 DCV.

* Polarity is correct.

Go to Step 2.

* Polarity is NOT correct.

Check and correct any improper connections between the battery and the ECM. Refer to the DC Schematic in the Schematics And Wiring Diagrams section. Replace the ECM.

2. Check for diagnostic codes on the ECM display and go to that respective problem. If no diagnostic codes are shown, shut the engine down and check the voltage between terminals 5 and 2 (5 is positive) on the generator terminal strip (TS1).

* Engine continues to crank and 15 DCV or more is measured.

Go to Step 3.

* Engine no longer cranks.

Check crank terminate setpoint (see Service Procedure A). If setpoint is okay, go to Diagnosed Problem A under 01 dlAG. If speed sensor signal is good and shielded wire is in good condition, replace the ECM.

* Engine continues to crank and there is less than 1 DCV between terminals 5 and 2.

Problem is in magnetic switch (see Service Procedure E) or in starting motor or pinion solenoid. Repair as required.

3. Disconnect wire No. 5 on the generator terminal strip TS1.

* Engine no longer cranks and also the voltage between terminals 5 and 2 on generator terminal strip is still above 15 DCV.

Check resistance between terminals W and 25 on ECM. If it is below 5 ohms, go to Service Procedure B. If not, check for shorts or incorrect wiring that supplies voltage to terminal 5.

* Engine continues to crank.

Problem is in magnetic switch (see Service Procedure E) or in starting motor or pinion solenoid. Repair as required.

Problem 4

Engine shutdown occurs, and/or all six LED fault indicators on the ECM are on.

Procedure

Make sure that the control panel lamp test switch (LTS) is NOT activated. Disconnect wires from terminal 8 on the ECM. Measure the DC voltage between battery positive (B+) and battery negative (B-) on ECM.

* Fault LED's do NOT turn on.

Test switch (LTS) or wiring is grounded. Correct the problem.

* Fault LED's remain ON. Battery voltage is 15 DCV or less.

Battery voltage is low. Charge battery or correct wiring problem as required.

* Fault LED's remain ON. Battery voltage is above 15 DCV.

Replace the ECM.

Problem 5

LED fault indicator on the ECM does NOT reset.

Procedure

Move the engine control switch (ECS) to the OFF/RESET position. If the LED does NOT go out, connect a jumper wire between terminal 12 on the ECM and battery negative (B-). Disconnect jumper wire.

* LED resets (goes out) when jumper wire is connected.

Problem is in ECS or wiring to the ECS. Repair as required.

* LED does NOT reset (still lit).

Make sure that the fault condition no longer exists. (Example: Engine high coolant temperature LED is lit and engine is cool). If fault does NOT reset, replace the ECM.

Problem 6

Engine shutdown occurs, overcrank LED is lit.

Procedure

Turn ECS to the OFF/RESET position. If the overcrank LED does NOT go out, do Undiagnosed Problem 5. If the LED goes out, do Undiagnosed Problem 1.

Problem 7

Engine shutdown occurs, overspeed LED is lit.

Procedure

Turn ECS to the OFF/RESET position. If the overspeed LED does NOT go out, do Undiagnosed Problem 5. If the LED goes out, check for possible causes of overspeed. If no causes are found, check the overspeed setpoint and the ring gear teeth setpoint according to Service Procedure A. Attempt to start engine by moving the ECS to the MANUAL position.

* Overspeed LED resets and engine starts and runs. Overspeed setpoint is correct.

Hold the verify switch on back of the ECM in the VERIFY position and increase speed until shutdown occurs. If shutdown speed is 75% of overspeed setpoint, the overspeed function is okay. Look for governor or system problems. If shutdown speed is incorrect, go to Service Procedure F. Replace the ECM if no speed sensor problem is found.

* Overspeed LED resets and engine starts, but overspeeds again.

If speed goes above overspeed setpoint, repair governor or system problem. If speed does NOT go high, go to Service Procedure F. Replace the ECM if no speed sensor problem is found.

* Overspeed setpoint is below specifications.

Program the correct setpoint according to Service Procedure A.

Problem 8

Engine shutdown occurs, low oil pressure LED is lit.

Problem 8 is separated into two procedures for the different pressure/temperature modules.

* Procedure 8A is used for the earlier pressure/temperature modules (engine oil line connects to the module).
* Procedure 8B is used for the current pressure/temperature modules (no engine oil line connects to the module, wires connect the engine oil pressure sensor to the pressure/temperature module).

Procedure 8A - Earlier Module

1. Monitor the low oil pressure LED. Turn ECS to the OFF/RESET position.

* The LED does NOT go out.

Do Undiagnosed Problem 5.

* The LED goes out.

Check for possible causes of low oil pressure. If no causes are found, go to Step 2.

2. Check that the following setpoints, which are programmed in the ECM, agree with the specified setpoints: oil step speed, idle speed oil pressure shutdown and rated speed oil pressure shutdown (see Service Procedure A).

* The setpoints agree.

Go to Step 3.

* The setpoints do NOT agree.

Reprogram the ECM to the specified setpoints. See Service Procedure A.

3.

NOTE: Without oil pressure protection the ECM shuts down the generator set. During troubleshooting or in an emergency situation, it is possible to operate with no oil pressure or coolant temperature protection by reprogramming the ECM (see Service Procedure A). Install oil pressure and coolant temperature gauges to give the operator an indication of engine conditions. After the problem is fixed, make sure to reprogram the ECM.

Install a reliable oil pressure gauge. Start the engine. At idle and rated speed, check to see if the gauge and ECM display are the same. If the oil pressure is low, do NOT continue. Shut the engine down and repair the problem in the engine lube system.

* Gauge and ECM display are the same.

Go to Step 4.

* Gauge and ECM display are NOT the same.

Check the wiring and oil supply to the pressure/temperature module. If no problem is found, replace the pressure/temperature module.

4. At idle and rated speed, compare the measured oil pressure to the programmed setpoints.

* Pressure is less than the setpoints.

The problem is in the engine. Refer to the engine service manual.

* Pressure is the same or above the setpoints.

Check the wiring and oil supply to the pressure/temperature module. If no problem is found, replace the ECM.

Procedure 8B - Current Module

1. Monitor the low oil pressure LED. Turn ECS to the OFF/RESET position.

* The LED does NOT go out.

Do Undiagnosed Problem 5.

* The LED goes out.

Check for possible causes of low oil pressure. If no causes are found, go to Step 2.

2. Check that the following setpoints, which are programmed in the ECM, agree with the specified setpoints: oil step speed, idle speed oil pressure shutdown and rated speed oil pressure shutdown (see Service Procedure A). The specified setpoints are shown in the Identification section (fifth character) and Service Procedure A.

* The setpoints agree.

Go to Step 3.

* The setpoints do NOT agree.

Reprogram the ECM to the specified setpoints. See Service Procedure A.

3.

NOTE: Without oil pressure protection the ECM shuts down the generator set. During troubleshooting or in an emergency situation, it is possible to operate with no oil pressure or coolant temperature protection by reprogramming the ECM (see Service Procedure A). Install oil pressure and coolant temperature gauges to give the operator an indication of engine conditions. After the problem is fixed, make sure to reprogram the ECM.

Install a reliable oil pressure gauge. Start the engine. At idle and rated speed, check to see if the gauge and ECM display are the same. If the oil pressure is low, do NOT continue. Shut the engine down and repair the problem in the engine lube system.

* Gauge and ECM display are the same.

Go to Step 4.

* Gauge and ECM display are NOT the same.

Go to Step 5.

4. At idle and rated speed, compare the measured oil pressure to the programmed setpoints.

* Pressure is less than the setpoints.

The problem is in the engine. Refer to the engine service manual.

* Pressure is the same or above the setpoints.

Replace the ECM.

5. A poor connection or short could cause the problem. Check, repair if necessary, the wiring and harness connector from the pressure/temperature module to the engine oil pressure sensor. Check if problem is still present.

* Problem is no longer present.

The harness was the cause of the problem.

* Problem is still present.

Replace the oil pressure sensor. If low oil pressure problem still exists, replace the press/temp module.

Problem 9

Engine shutdown occurs, high coolant temperature LED is lit.

Procedure

1. Turn ECS to the OFF/RESET position. Allow engine to cool down.

* The high coolant temperature LED does NOT go out after engine is cool.

Perform Undiagnosed Problem 5.

* The high coolant temperature LED goes out.

Check for possible causes for high coolant temperature. If no causes are found go to Step 2.

2. Check the coolant temperature setpoint programmed into the ECM (see Service Procedure A). Make sure it is set for the specific engine model. See the Identification section.

* The programmed coolant temperature setpoint is below the proper shutdown setpoint.

Temperature setpoint is NOT correct. Reprogram setpoint. See Service Procedure A.

* The programmed coolant temperature setpoint agrees with the proper shutdown setpoint.

Temperature setpoint is correct. Go to Step 3.

3. Install an accurate coolant temperature gauge with the sensing bulb in an area of high coolant flow, as close to temperature probe as possible.

NOTE: Without oil pressure protection the ECM shuts down the generator set. During troubleshooting or in an emergency situation, it is possible to operate with no oil pressure or coolant temperature protection by reprogramming the ECM (see Service Procedure A). Install oil pressure and coolant temperature gauges to give the operator an indication of engine conditions. After the problem is fixed, make sure to reprogram the ECM.

Start the engine and allow coolant temperature to stabilize. If necessary, apply a load to the generator.

* Temperature displayed by ECM and by gauge agree and it is above the temperature setpoint. Setpoint is correct and high coolant temperature LED is still lit.

Engine is overheating. Troubleshoot cooling system.

* Temperature displayed by ECM is 5°C (9°F) or higher than the temperature displayed by the gauge.

Check temperature probe (see Service Procedure G). If it is good, repeat test. Make sure the gauge is accurate. If ECM continues to read high, replace the pressure/temperature module.

* Temperature displayed by ECM and by gauge agree and are below the temperature setpoint.

Go to Undiagnosed Problem 5.

* Temperature displayed on the ECM is the word "HI" and the temperature on the gauge is below 98°C (208°F).

Check for shorts in wiring to the pressure/temperature module. Also check the temperature probe (see Service Procedure G).

Problem 10

Engine shutdown occurs, emergency stop LED's is lit.

Procedure

Reset the emergency stop pushbutton by rotating the knob until it pops out. Turn the ECS to OFF/RESET position. Disconnect the wire from terminal 14 on the ECM if LED remains on after attempting to reset.

* Emergency stop LED goes out when wire is disconnected.

Emergency stop switch is stuck closed or grounded or wire is grounded. Repair as required.

* Emergency stop LED remains on.

Move ECS to reset and back to the MANUAL position. If LED remains on, go to Undiagnosed Problem 5.

Problem 11

Engine shutdown occurs, optional reverse power relay LED is lit.

Procedure

Turn the ECS to the OFF/RESET position. If the reverse power LED does NOT go out, disconnect wire from terminal 13 on the ECM.

* Reverse power LED goes out (resets) after resetting.

Problem was reverse power fault. Control panel is okay.

* Reverse power LED goes out when wire is disconnected from terminal 13.

Reverse power relay does NOT reset. Check wiring to reverse power relay. If required, replace the reverse power relay.

* Reverse power LED remains lit.

Go to Undiagnosed Problem 5.

Problem 12

No engine shutdown when a fault occurs.

Look at the ECM Display. If there is a diagnostic code displayed or a fault LED lit and the engine is NOT shutdown, go to Procedure 1A (ETS) or Procedure 1B (ETR) or Procedure 1C (3500 engine with electronic governor). In the following procedures, consider latching fuel systems as ETS fuel systems. If there is no diagnostic code or fault displayed, go to Procedure 2.

Procedure 1A (ETS)

Check the DC voltage relative to battery negative (B-) on TS1 terminal 7 in the generator and on terminals 23, S and R on the ECM. During this procedure, the engine is running with a fault LED lit.

* All voltages are above 20 DCV.

The wire from terminal 7 in generator to solenoid is open or fuel shutoff solenoid is defective or NOT adjusted correctly. Repair as required.

* Voltage at terminal 7 in generator is below 20 DCV. The other voltages are above 20 DCV.

The wire from terminal 7 in generator to terminal 23 in the ECM is open. Repair wire or connection.

* Voltage of terminal 23 in ECM and terminal 7 in the generator is below 20 DCV. The other voltages are above 20 DCV.

Check the FCR relay for stuck open contacts. Go to Service Procedure B.

* All voltages are below 20 DCV except for Terminal R on the ECM.

Replace Fuse F6. If problem continues, check for shorted solenoid or grounded wiring. Repair as required.

* All voltages are below 20 DCV.

Connection from battery positive (B+) to terminal R is defective. Repair as required.

Procedure 1B (ETR)

Remove fuse F6.

* Engine shuts down.

Fuel control relay (FCR) contact is stuck closed. Check resistance between terminals S and 23 on ECM. If it is below 5 ohms, go to Service Procedure B. If not, look for wiring errors that might supply voltage to fuel control solenoid.

* Engine continues to run.

Fuel control solenoid is stuck in the RUN position. Shut engine down manually and troubleshoot solenoid and linkage.

Procedure 1C (3500 Engine With Electronic Governor)

Remove Fuse 4.

* Engine shuts down.

Run relay (RR) contact is stuck closed. Check resistance between terminals M and 20 on ECM. If it is below 5 ohms go to Service Procedure B. If not, look for wiring errors that might supply voltage to electronic governor.

* Engine continues to run.

Rack or electric actuator is stuck in fuel ON position. Shut engine down manually and troubleshoot governor linkage.

Procedure 2 (No Code Or Fault Displayed)

Record all of the readings from the ECM display. Shut engine down and check the setpoint (see Service Procedure A) of the parameter that is supposed to shut the engine down.

NOTE: If setpoint 02 is programmed to 2 or 3, the engine does NOT shut down during an engine oil pressure or coolant temperature fault. See Service Procedure A.

* Readings from the display are within allowed setpoints.

There is no problem.

* Readings from the display are NOT within allowed setpoints.

Replace ECM.

Problem 13

Engine shutdown with no LED's lit or diagnostic codes on ECM.

Procedure

Check to make sure ECM terminal 15 is NOT receiving a signal to shutdown (connect to battery negative, B-).

* Terminal 15 connected to battery negative (B-).

Problem is in wiring, find defect and repair or replace it.

* Terminal 15 NOT connected to battery negative (B-).

If no other defects are found replace the ECM.

Problem 14

Remote annunciator or control panel alarm module, data link controlled LED's all flash at a rate of once per two seconds (0.5 Hz).

Procedure

STEP 1. Momentarily disconnect the battery or wire 1 at TS1-1 that is used to power the ECM. If the LED's stop flashing after the battery is reconnected, the problem is solved. If the LED's still flash, check to make sure serial data link wire 18 has good continuity from ECM terminal 6 to alarm module terminal 2. Also, ensure that there is at least 20K ohms of resistance between wire 18 and both battery positive (B+) and battery negative (B-).

* Wire 18 is either open or has less than 20K ohms of resistance to B+ or B-.

Repair or replace defective wire.

* Wire 18 has continuity and at least 20K ohms of resistance to both B+ and B-.

Go to Step 2.

STEP 2. Measure the DC voltage between terminal 7 and terminal 1 on the annunciator (terminal 1 is positive).

* Terminal 1 measures +15 DCV or more.

Go to Step 3.

* Terminal 1 measures less than +15 DCV.

Check the battery voltage. Check the wiring between the battery, the ECM, and the annunciator. As needed, recharge or replace the batteries and repair the wiring. Refer to the DC Schematic in the Schematics And Wiring Diagrams section.

3.

NOTE: The maximum number of modules, alarm or CIM, connected to the serial data link is three. The maximum distance between a module and the ECM is 305 m (1000 ft). If these specifications are NOT met, it is possible for the alarm module LED's to flash. This indicates the alarm module is NOT reading the information from the data link. If NOT in compliance with the specifications, reduce the number of modules and/or shorten the distance.

If there is more than onn annunciator connected to the ECM, replace the one that has the flashing LED's. Otherwise, measure the DC voltage between ECM terminal 6 and B- and also the DC voltage between annunciator terminal 2 and B-.

* Both voltages are above 8 DCV.

Replace the ECM.

* Both voltages change from 2 to 10 DCV.

Replace the annunciator.

* Both voltages are below 2 DCV.

Go to Step 4.

* The two voltages are NOT the same.

Wire 18 is faulty. Repair or replace wire 18.

4. Remove connections on terminal 2 of the annunciator. Measure the DC voltage between annunciator terminal 2 and B-.

* Voltage is above 8 DCV.

Replace the ECM.

* Voltage is below 2 DCV.

Replace the annunciator.

Problem 15

ACM displays all dashes "---".

Procedure

Disconnect the DC power to the ACM for a moment by turning the ECS to the OFF/RESET position. Start and run the engine if the dashes do NOT go away replace the ACM.

Problem 16

ACM Hz displays "LO" and voltmeter displays "0".

Procedure

1. Make sure the AVS is NOT in the 0 position. Check AC volts connections to ACM terminals 1 and 2 to make sure the generator AC voltage is present.

* Generator AC voltage is measured at terminals 1 and 2.

Go to Step 2.

* Generator AC voltage is NOT measured at terminals 1 and 2.

Check fuses F11, F12, F13 AVS and wiring for defect. Repair or replace any defective part.

2. With the engine started check the DC voltage connected to ACM terminals 5 and 12 (terminal 12 is positive). For this Step, the proper DC voltage is above 15 volts.

* DC voltage is below 15 volts.

Check batteries and charging system for cause of low batteries.

* DC voltage is above 15 volts.

Replace the ACM.

Service Procedures

Service Procedures List

* Service Procedure A - Programming the ECM.
* Service Procedure B - Relay Module.
* Service Procedure C - Programming the ACM.
* Service Procedure D - Alarm Module (DC Voltage Alarm Setpoint Adjustment).
* Service Procedure E - Magnetic Switch Test (24V).
* Service Procedure F - Speed Sensor Adjustment.
* Service Procedure G - Temperature Sensor Resistance.
* Service Procedure H - Verify Overspeed Shutdown.
* Service Procedure I - Verify High Coolant Temperature Shutdown.
* Service Procedure J - Verify Low Oil Pressure Shutdown.

Service Procedure A - Programming The ECM

The set points programmed into the ECM are factory set. However, the set points are changed to conform to the appropriate specifications when the ECM is moved from one engine type to another or when a special setting (usually overcrank or cycle crank) is needed.

NOTE: For the correct setpoints, always check print 7C1000 that is included with he EMCP.

Programmability


Programming Cover Location
(1) Cover.


Programming Components Location
(2) Potentiometer. (3) Rotary switch. (4) Momentary switch.

Setpoint information is stored then used in the control strategy of the ECM. To program, perform the following:

1. Turn the ECS to the STOP position.

NOTE: Do NOT open cover (1) in a humid environment. Replace cover (1) as soon as possible.

2. Remove access cover (1) on the backside of the ECM. Potentiometer (2), rotary switch (3) and momentary switch (4) are visible.

3. Note the positon of rotary switch (3). Turn rotary switch (3) to the position that corresponds to the setpoint needing adjustment. The LCD display now shows the position of the rotary switch and the related data.

4. Press momentary switch (4). The data information corresponding to the position of the potentiometer flashes.

5. Adjust potentiometer (2) to change the flashing data as desired. Once the data is correct, press momentary switch (4). The data information stops flashing. Reprogramming of the setpoint is now complete.

6. Return the rotary switch to position 0 if the system has an energize to run fuel solenoid or position 1 if the system has an energize to stop fuel solenoid.

NOTE: The engine does NOT run when in the program mode or if the position of the rotary switch does NOT correspond to the operating mode programmed into setpoint 02. Consult Caterpillar Inc. concerning alterations to the specified setpoints for the engine.

7. Turn the ECS to the OFF/RESET position.

8. Apply a continuous bead of 6V6640 Gasket Maker to the seal surface of cover (1). Install cover (1). Install an 8C4653 Security Seal on access cover (1) to prevent unauthorized tampering.

Setpoints

NOTE: For the correct setpoints, always check print 7C1000 that is included with the EMCP.

02 - ETR/ETS And Latching: This setpoint value describes the operating mode (type of fuel solenoid) of the ECM. The 6th character of the model number specifies the fuel solenoid setpoint. Refer to the Identification section.

0 or 2 programs the ECM to operate with an energize to run (ETR) fuel solenoid.

1 or 3 programs the ECM to operate with an energize to shutdown (ETS) fuel solenoid or latching fuel solenoid.

2 or 3 programs the ECM to ignore pressure/temperature module faults: i.e. high coolant temperature, low oil pressure and module malfunction do NOT shut down the engine.

03 - Metric/English: A setpoint value of 0 commands the ECM to display engine parameters in English units of measurement. A setpoint value of 1 displays metric units of measurement. The 16th character of the model number specifies the units setpoint. Refer to the Identification section. See the Table that follows for the units of measurement for each parameter.

04 - Ring Gear Teeth: This setpoint value is the same as the number of teeth on the ring gear. The range of value are 110 to 260. The 7th character of the model number specifies this setpoint. Refer to the Identification section.

05 & 06 - Overspeed: The overspeed shutdown setpoint is programmed with the rotary selector switch in the 05 or 06 position. Position 05 has a range of 400 to 2890 rpm. Position 06 has a range of 2450 to 5000 rpm in increments of 10 rpm. Place the rotary selector switch in 05 or 06 position whichever corresponds with the specified overspeed shutdown setpoint. Program this position to the specified engine speed at which an overspeed shutdown occurs. The 5th character of the model number specifies the overspeed setpoint. Refer to the Identification section.

NOTE: After programming the 05 or 06 setpoint, both setpoints are the same value.

The overspeed is factory set at:

Overspeed = 1.18 × rated speed.

NOTE: On certain 50 Hz applications the overspeed setpoint is 1.25 × rated speed. These special 50 Hz generator set applications are: 3114 BSSB and PP; 3116 BSSB and PP; 3208 BSSB; 3306 BSSB; 3406 BSSB.

07 - Crank Termination Speed: Once the engine speed passes this setpoint, the starting motor is no longer energized. The range is 100 to 1000 rpm in increments of 10 rpm.

The crank termination speed is factory set at 400 rpm.

08 - Oil Step Speed: Once the engine speed increases past this setpoint, then the ECM considers the engie is above the low idle condition in regard to low oil pressure shutdown and alarm. The range is 400 to 1800 rpm in increments of 10 rpm. The 5th character of the model number specifies the crank termination setpoint. Refer to the Identification section.

09 - Rated Speed Oil Pressure Shutdown: If the engine lube pressure drops below the setpoint and the engine speed exceeded the oil step speed for 9 seconds, then the ECM enters a low oil pressure shutdown condition. The range is 34 to 420 kPa (5 to 60 psi). Alarm signal sent to annunciator module occurs at 34 kPa (5 psi) above the shutdown. The 5th character of the model number specifies the rated speed oil pressure shutdown setpoint. Refer to the Identification section.

10 - Idle Speed Oil Pressure Shutdown: If the engine lube pressure drops below this setpoint and the engine has run for more than 9 seconds and the engine speed is below the oil step speed, then the ECM enters a low oil pressure shutdown condition. The range is 20 to 336 kPa (3 to 50 psi). The alarm signal sent to annunciator module occurs at 34 kPa (5 psi) above the shutdown. The 5th character of the model number specifies the idle speed oil pressure shutdown setpoint. Refer to the Identification section.

11 - High Coolant Temperature Shutdown: If the engine coolant temperature has exceeded the setpoint for 10 seconds, then the ECM enters a high coolant temperature shutdown condition. The range is 95 to 120°C (203 to 248°F). Alarm signal sent to annunciator module occurs at 6°C (11°F) below the shutdown temperature. The 5th character of the model number specifies the high coolant temperature shutdown setpoint. Refer to the Identification section.

12 - Low Coolant Temperature Alarm: If the engine coolant temperature is less than this setpoint for two seconds, then the ECM sends an alarm signal to the annunciator module. The range is 10 to 30°C (50 to 86°F). Factory set at 21°C (70°F).

13 - Overcrank Time: Total time to start the engine (from when first asked to start until overcrank is indicated). The range is 5 to 120 seconds. Factory setting is 90 seconds.

14 - Cycle Crank: The amount of time the starting motor cranks. Also, the amount of time the starting motor rests during a cycle crank. The range is 1 to 60 seconds. Factory setting is 10 seconds.

15 - Cooldown: The amount of time the engine is allowed to run after initiation of a normal shutdown. The range is 0 to 30 minutes. Factory set at 5 minutes.

Service Procedure B - Relay Module


Relay Housing Location (Typical Example)
(1) Relay housing. (2) Screws.

The relay module is the housing that contains the fuses and terminals 16-27 and is part of the back of the ECM.

1. Disconnect wire from terminal 1 in generator. Make sure there is NO voltage on the B+ terminal of the ECM. If necessary, remove some of the harness for easy accessibility. It is possible for moisture to enter the ECM when the relay housing is removed. Remove the relay housing in a dry environment. If relative humidity exceeds 60%, remove housing in an air conditioned area.

2. Remove screws (2) and washers that hold relay housing (1) to main housing. To open housing, install forcing screws in the two threaded holes. The threaded holes are on the ends of the housing flange and in the same bolt pattern as screws (2). Tighten the forcing screws. If necessary, insert a thin knife blade between relay housing (1) and the main housing. Drive it into the gap by tapping gently to break seal loose.

NOTE: On earlier relay housings (1), there are NO threaded holes as mentioned above. To open housing, insert a thin knife blade between the relay housing and main housing. Drive it into the gap by tapping gently to break seal loose.

3. Open the housing and locate the relay or relays that need changed. Relays are labeled K1 through K7 on the PC board.


Relay Locations (Typical Example)
(3) K7 - fuel control (FCR). (4) K6 - air shutoff (ASR). (5) K1 - 2301 Ramp (2301). (6) K5 - run (RR). (7) K2 - fault shutdown (ENFR). (8) K4 - starting motor (SMR). (9) K3 - crank termination (CTR).

4. Remove the relay clip and pull the relay straight out.

5. Do Relay Performance Test:

Check continuity with ohmmeter as follows:

A. With NO power on terminals 7 and 8, the correct resistance between terminals 1 and 5 is 1 ohm or less. The correct resistance between terminals 2 and 6 is 1 ohm or less. The correct coil resistance between terminals 7 and 8 is 140 to 180 ohms.

B. Apply 12 volts DC to terminals 7 and 8. The correct resistance between terminals 3 and 5 is 1 ohm or less. The correct resistance between terminals 4 and 6 is 1 ohm or less. The correct resistance between any other pairs of terminals is 100k ohm or more.

6. Replace the relay if it fails this test and put the clip back on.

7. Check the connector going from the main housing to the relay PC board to assure that it is still inserted properly.

8. If replacing the relay does NOT fix problem or if the relay is NOT defective, replace the entire relay module.

9. Clean and apply 6V1541 Primer to both housings' sealing surface.

10. Apply a continuous bead of 6V6640 Sealant to the main housing sealing surface.

11. Install relay housing (1) on the main housing and fasten with original washers and screws (2).

12. Reconnect the wires that were removed.

Service Procedure C - Programming The ACM

The AC meter module (ACM) is factory set to display AC voltages and AC currents as specified by the customer. If the current transformers (CT's) are replaced with CT's having another ratio or if the generator is reconnected for a different voltage, reprogram the ACM.

If the generator set is a rental unit that is frequently reconnected from high to low voltage, use the CT's needed for the high current connection and set the voltage range for the highest voltage expected. This avoids reprogramming the ACM every time the generator is reconnected.


ACM Programming Cover Location
(1) Cover.


ACM Programming Components Location (Typical Example)
(2) S2 switch. (3) S1 switch. (4) R6.

The ACM is programmed using two 16 position switches, S2 (2) for voltage and S1 (3) for current, to accommodate various voltmeter ranges and CT ratios. These switches are located under the access cover (1) in the rear of the ACM. The charts show the switch positions that correspond to the different voltmeter ranges and current transformer (CT) ratios used.

It is possible for moisture to enter the ACM when the access cover is removed. Remove the cover in a dry environment. Open this cover in an air conditioned area if relative humidity exceeds 60%. If necessary, remove the ACM from the panel for programming.

To program, remove cover and turn S1 and S2 to the positions indicated in the table. Make sure that the external jumper is also connected to the terminals indicated in the table. Do NOT adjust the two calibration potentiometers to the right of S1 and S2. These are factory set to calibrate the ACM against an accurate standard. When paralleling two generator sets, it is possible the voltage readings are different. In this case the upper potentiometer R6(4) is adjusted so that both voltage displays read the same.

After programming the ACM, replace cover (1). Use a continuous bead of 6V6640 Sealant to seal the cover.

Service Procedure D - Alarm Module (DC Voltage Alarm Setpoint Adjustment)


Alarm Module Plug Location (Typical Example)
(1) Plug.

For all alarm applications, the low DC volts alarm setpoint is adjusted by a potentiometer located under access plug (1) on the rear of the module. The adjustment range is 8 to 38 volts. The setpoint is factory set at 24 DCV. To adjust the low DCV alarm setpoint:

1. Remove plug (1) which covers the adjustment pot on the rear of the alarm module. It is possible for moisture to enter the ACM when the plug is removed. Remove the plug in a dry environment. Remove the plug in an air conditioned area if relative humidity exceeds 60%.

2. Disconnect wires on terminals 1 and 7. Connect a variable DC power supply to the alarm module (+ voltage to terminal 1, - voltage to terminal 7). Set the power supply voltage to the desired low DCV alarm setpoint (between 8 and 38 volts).

3. Turn the adjustment pot fully clockwise.

4. After one minute, the low DC volts LED flashes. Press the acknowledge/silence switch to get a steady low voltage light.

5. Turn the adjustment pot counterclockwise slowly until the LED goes out.

6. Replace the plug.

7. Disconnect the variable DC power supply and connect wires removed in Step 2.

Service Procedure E - Magnetic Switch Test (24V)


Magnetic Switches Location

1. Disconnect jumper wire between terminals 4 and 5 in the generator mounted terminal strip (TS1). Measure resistance between terminal 5 and terminal 2. The correct resistance is 26 to 33 ohms. On dual starting motor (dual magnetic switch) systems, the resistance is 13 to 17 ohms. If resistance is incorrect, replace the defective magnetic switch. If okay, go to Step 2.

2. Disconnect cable going from the pinion solenoid to the starting motor. Do this on both starting motors of a two starting motor system.

3. Connect a DC voltmeter: positive to terminal 24 and negative to terminal 25 in generator mounted terminal strip (TS1) (connect negative to terminal 26 if second magnetic switch is tested in a two switch system).

4. Connect a wire from terminal 1 to terminal 5 on generator mounted terminal strip (TS1). The correct voltmeter reading changes from approximately 24 DCV to approximately 2 DCV. If voltage exceeds 2 volts, replace magnetic switch. Disconnect this wire immediately after the voltage is measured (no more than 10 seconds).

5. If the switch passes the requirements of Step 1 and 4, it is okay. Reconnect wires and cables that were removed in this procedure.

Service Procedure F - Speed Sensor Adjustment


Magnetic Pickup
(1) Clearance dimension. (2) Locknut.

1. Remove the magnetic pickup from the engine flywheel housing and turn the flywheel until a gear tooth is directly in the center of the threaded opening for the magnet pickup. Install the magnetic pickup again in the threads of the flywheel housing.

2. Turn (by hand) in a clockwise direction until the end of the magnetic pickup just makes contact with the gear tooth. Now turn the magnetic pickup back out 1/2 turn (180° in the counterclockwise direction) to get the correct air gap [clearance dimension (1)]. Now tighten locknut (2) to a torque of 45 ± 7 N·m (33 ± 5 lb ft).

NOTE: Do NOT let the magnetic pickup turn while locknut (2) is tightened.

Service Procedure G - Temperature Sensor Resistance


Coolant Temperature Sensor
(1) Connectors to pressure/temperature module.

The resistance value of the sensor corresponds to the surrounding temperature. This test requires that the sensor is at room temperature.

1. Disconnect connectors (1).

2. There is one electrical connection in each connector (1). Measure the resistance between connectors (1). Make sure to make good contact to the connector pins.

3. Compare the measured resistance with that listed in the above chart.

* If the resistance values do NOT agree, check connectors (1) and repair any bad connections. If connectors are okay, replace the coolant temperature sensor.
* If the resistance values do agree, check the mating connectors at the pressure/temperature module. If connectors are okay, replace the pressure/temperature module.

Service Procedure H - Verify Overspeed Shutdown


Back Of ECM
(1) Overspeed verify switch.

The ECM allows the service personnel to verify (check) that the engine overspeed protection is functioning. Actual overspeeding of the engine is NOT required. Activation of the overspeed verify switch reduces the overspeed setpoint to 75% of the value programmed in the ECM. Therefore the overspeed verify speed is less than rated engine speed.

1. Operate the engine at rated speed. Monitor the fuel control solenoid (and the air shutoff solenoid, if equipped).

2. Press and hold overspeed verify switch (1). Release the switch after the engine stops.

3. Check that the fuel control solenoid (and the air shutoff solenoid, if equipped) cause the engine to shutdown. Also, check that the overspeed LED, on the ECM, is flashing.

4. Turn the ECS to the OFF/RESET position.

Service Procedure I - Verify High Coolant Temperature Shutdown


High Coolant Temperature Test Harness
C1 = Connector Housing 7N9737. C2 = Connector Housing 7N9738. R = 1000 ohm ten turn potentiometer.

This procedure enables service personnel to verify (check) that the engine high coolant temperature protection is functioning. Substituting a variable resistor (potentiometer) for the temperature sensor, allows testing of the circuit without overheating the engine.

NOTE: The low coolant temperature alarm on the alarm module is tested in a similar procedure. However, R is replaced with a 20 000 ohm potentiometer.

1. Determine the setpoint for high coolant temperature shutdown. See Service Procedure A.

2. Turn the ECS to the OFF/RESET position.

3. Disconnect the two harness connectors at the temperature probe. Set R to 1000 ohms. Connect the test harness to the disconnected vehicle harness connectors.

4. Start the engine. Depress the display hold switch when the engine coolant temperature is displayed. The correct displayed temperature is approximately 88°C (189°F).

NOTE: If equipped with an alarm module, the high coolant temperature LED and horn on the alarm module are activated prior to engine shutdown.

5. Slowly adjust R until the displayed temperature is the same as the setpoint temperature (of step 1).

6. When the displayed and setpoint temperature are the same, the engine shuts down. Check that the fuel control solenoid caused the engine shutdown. Also, check that the overtemperature LED, on the ECM, is flashing.

7. Turn the ECS to the OFF/RESET position.

Service Procedure J - Verify Low Oil Pressure Shutdown

This procedure is used for the current pressure/temperature modules (no engine oil line connects to the module, wires connect the engine oil pressure sensor to the pressure/temperature module).


Low Oil Pressure Test Harness
A = Socket A 8T8730. B = Socket B 8T8730. C = Socket C 8T8730. C1 = Connector 8T8731. R = Potentiometer, 1000 ohm, ten turn. NOTE: Socket C connects to the wiper of potentiometer R.

This procedure enables service personnel to verify (check) that the low engine oil pressure protection is functioning. This procedure controls the oil pressure signal to the pressure/temperature module without affecting the engine lubrication system. Engine shutdown and alarm are verified at idle speed and rated speed.

NOTE: The low oil pressure LED and horn on an alarm module, if equipped, activate 34 kPa (4.9 psi) above the engine shutdown value.

Idle speed oil pressure shutdown occurs when: the engine speed is less than the oil step speed value and the engine oil pressure is less than the idle speed oil pressure shutdown value. Rated speed oil pressure shutdown occurs when: the engine speed is greater than the oil step speed value and the engine oil pressure is less than the rated speed oil pressure shutdown value.

1. Determine the programmed ECM setpoint for: oil step speed, idle speed oil pressure shutdown and rated speed oil pressure shutdown. See Service Procedure A.

2. Turn the ECS to the OFF/RESET position.

3. Disconnect the engine oil pressure sensor connector from the pressure/temperature module. Connect the test harness to the pressure/temperature module connector.

4. Turn the ECS to the AUTO position. Monitor the engine oil pressure on the ECM display. Adjust potentiometer R until the pressure displayed is greater than the idle speed oil pressure shutdown value, but less than 345 kPa (50 psi).

NOTE: The ECM displays an 09 dlAG code, when the sensed oil pressure is greater than 345 kPa (50 psi) and the engine is NOT running. If an 09 dlAG code is present, clear it. To clear the diagnostic code, decrease the sensed oil pressure by adjusting potentiometer R and then turn the ECS switch to the OFF/RESET position.

5. Start and run the engine at idle speed. Keep the engine speed below the oil step speed setpoint.

6. Lower the oil pressure displayed on the ECM by slowly adjusting potentiometer R.

NOTE: The engine shuts down when the oil pressure decreases below the setpoint for idle speed oil pressure shutdown.

7. Verify that shutdown occurs when the displayed engine oil pressure is the same as (or slightly less than) the setpoint for idle speed oil pressure shutdown. Verify that the low oil pressure LED, on the ECM, is flashing.

NOTE: The low oil pressure LED and horn on an alarm module, if equipped, activate prior to engine shutdown.

8. Turn the ECS to the OFF/RESET position.

9. Turn the ECS to the AUTO position. Monitor the engine oil pressure on the ECM display. Adjust potentiometer R until the pressure displayed is greater than the rated speed oil pressure shutdown value, but less than 345 kPa (50 psi).

NOTE: The ECM displays an 09 dlAG code, when the sensed oil pressure is greater than 345 kPa (50 psi) and the engine is NOT running. If an 09 dlAG code is present, clear it. To clear the diagnostic code, decrease the sensed oil pressure by adjusting potentiometer R and then turn the ECS switch to the OFF/RESET position.

10. Start and run the engine at rated speed. Keep the engine speed above the oil step speed setpoint.

11. Lower the oil pressure displayed on the ECM by slowly adjusting potentiometer R.

NOTE: The engine shuts down when the oil pressure decreases below the setpoint for rated speed oil pressure shutdown.

12. Verify that shutdown occurs when the displayed engine oil pressure is the same as (or slightly less than) the setpoint for rated speed oil pressure shutdown. Verify that the low oil pressure LED, on the ECM, is flashing.

13. Turn the ECS to the OFF/RESET position to clear the ECM.

14. Remove the test harness. Reconnect the engine oil pressure sensor to the pressure/temperature module.

Schematics & Wiring Diagrams

Abbreviations

Symbols

How To Read Control Panel DC Schematics


Typical DC Schematic
(1) Symbol for terminal on control panel. (2) Pin identification on components. (3) Symbol for terminal on generator terminal strip. (4) Line numbers used for component location: for example SP is on line 26. (5) Pin identification on ECS switch.

AC Schematic (IEC)

AC Schematic (JIC)

DC Schematic - Air Start

DC Schematic - Prelube Pump

Wiring Diagram - Customer/Contractor

Wiring Diagram - Customer Interface Module (CIM)

Wiring Diagram - Harness

Wiring Diagram - Main Chassis

DC Schematic (IEC)

DC Schematic (JIC)

Wiring Diagram - 3500 Engines (With Air Starting)

Wiring Diagram - 3500 Engines (With Electric Starting)

Wiring Diagram - All Generator Sets (Except 3500 Engines)

Caterpillar Information System:

ELECTRONIC MODULAR CONTROL PANEL (EMCP) Systems Operation
3406B (PEEC) DIESEL TRUCK ENGINE Jacobs Engine Brake
3406B (PEEC) DIESEL TRUCK ENGINE Oil Pump (BrakeSaver)
3406B (PEEC) DIESEL TRUCK ENGINE Oil Pan (BrakeSaver)
3406B (PEEC) DIESEL TRUCK ENGINE BrakeSaver
3406B (PEEC) DIESEL TRUCK ENGINE BrakeSaver Control Valve
3406B (PEEC) DIESEL TRUCK ENGINE Flywheel (BrakeSaver)
3406B (PEEC) DIESEL TRUCK ENGINE Oil Cooler (BrakeSaver)
3406B (PEEC) DIESEL TRUCK ENGINE Pistons And Connecting Rod Assemblies
3406B (PEEC) DIESEL TRUCK ENGINE Cylinder Liners
3406B (PEEC) DIESEL TRUCK ENGINE Crankshaft Rear Seal And Wear Sleeve
3406B (PEEC) DIESEL TRUCK ENGINE Crankshaft Front Seal And Wear Sleeve
2301A ELECTRONIC GOVERNORS (LOAD SHARING) FOR GENERATOR SETS Installation And Operation
2301A ELECTRONIC GOVERNORS (LOAD SHARING) FOR GENERATOR SETS Installation And Operation
2301A ELECTRONIC GOVERNORS (LOAD SHARING) FOR GENERATOR SETS Chapter 5. Troubleshooting
2301A ELECTRONIC GOVERNORS (LOAD SHARING) FOR GENERATOR SETS Appendix A. Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, & Modules
2301A ELECTRONIC GOVERNORS (LOAD SHARING) FOR GENERATOR SETS Appendix B. EMI Control in Electronic Governing Systems
TROUBLESHOOTING GUIDE [ETR] FOR SPARK IGNITED ENGINES EQUIPP Electric Protection System Functional Test
TROUBLESHOOTING GUIDE [ETR] FOR SPARK IGNITED ENGINES EQUIPP Electrical Schematics
TROUBLESHOOTING GUIDE [ETR] FOR SPARK IGNITED ENGINES EQUIPP Troubleshooting Full Protection System
TROUBLESHOOTING GUIDE [ETR] FOR SPARK IGNITED ENGINES EQUIPP Service Procedures
3176 TROUBLESHOOTING INTRODUCTION Make Sure You Read This Page Before Proceeding To The Troubleshooting Modules
3208 INDUSTRIAL ENGINE Engine Design
3208 INDUSTRIAL ENGINE Fuel Injection Pump
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.