Usage:
140-8416 Switch
Terminal A is normally open below actuation temperature.
Terminal B is common.
Terminal C is normally closed below actuation temperature.
With a temperature increase to 111.5 to 113.5°C (233 to 236°F), terminal A closes and terminal C opens.
With a temperature decrease to 105.5°C (222°F), terminal A opens and terminal C closes.
(1) Tighten switch assembly to a torque of ... 52 ± 8 N·m (38 ± 6 lb ft)
5N8857 Switch
Terminal A is normally open below actuation temperature.
Terminal B is common.
Terminal C is normally closed below actuation temperature.
With a temperature increase to 96.5 to 99.5°C (206 to 211°F), terminal A closes and terminal C opens.
With a temperature decrease to 91°C (196°F), terminal A opens and terminal C closes.
(1) Tighten switch assembly to a torque of ... 52 ± 8 N·m (38 ± 6 lb ft)
8N1693 Switch For Ether Starting Aid
Switch must open between ... 35 to 41°C (95 to 106°F)
Switch must close at a minimum of ... 27°C (81°F)
3N7442 Switch
Switch must open between ... 24 to 29°C (75 to 84°F)
Switch must close at a minimum of ... 18 to 24°C (64 to 75°F)
Oil Pressure Switch
3E6455 Switch
Terminal A is normally open below actuation temperature.
Terminal B is common.
Terminal C is normally closed below actuation temperature.
With pressure increase, terminal B closes and terminal C opens at ... 90 ± 21 kPa (13 ± 3 psi)
With pressure decrease, terminal B opens and terminal C closes at ... 70 ± 21 kPa (10 ± 3 psi)