INSTALLATION AND OPERATION LOAD SHARING MODULE Caterpillar


Appendix A. - LSM Control Specifications

Usage:

POWER SUPPLY = 18-32 Vdc, approximately 5 W. Protected against undervoltage, overvoltage to +80 Vdc, reverse voltage to -32 Vdc.

INPUTS

3-phase PT inputs = 100-240 Vac line-to-line, 50-400 Hz. PT input burden is between 1.5 VA and 1.7 VA per phase at 240 Vac, and between 0.4 VA and 0.5 VA per phase at 120 Vac

3-phase CT inputs = 3-7 Arms at full load, CT input burden at full load is 0.1 VA per phase.

Load Sharing Input = 0-3 Vdc into 25 k ohms impedance in isochronous mode, open circuit in droop mode.

Sync Input = Compatible with optional Woodward SPM-A Synchronizer, 0.38% speed change* per volt input.

Speed Trim = ± 10 % minimum speed change* with an external 10 k ohm potentiometer.

Droop Switch = The external droop switch is to be wired in series with the auxiliary circuit breaker contact between terminals 13 and 14. Droop mode is selected when either the droop switch or the auxiliary circuit breaker is open.

OUTPUTS

Load Signal = DC signal proportional to total real current measured by the Load Sharing Module. Load Gain adjustable over minimum range of 0.86 to 2.0 Vdc/Arms.

PWM Output = Pulse width modulated square wave, 500 ± 100 Hz. Zero error output duty cycle + 69.8 ± 2.0 %. Minimum V (hi) + 10.0 Vdc, maximum V (lo) = 0.5 Vdc when driving external 5.1 K load to 13.0 Vdc external pull-up.

ADJUSTMENTS

Droop = Provides 0 to 9% speed reduction* between no load and full load conditions.

Load Gain = Provides adjustment of the load on an individual generator when two or more generators are paralleled. Adjusts specified full load condition from 3 to 7 Arms.

ENVIRONMENTAL

Operating Temperature = -40 to +70°C (-40 to +158°F)

Salt Fog = Tested at 5% NaCl, 35°C, 48 hrs wet, 48 hrs dry

Humidity = Tested at 95% RH, 65°C, non-condensing, 5 cycles at 24 hr/cycle.

Vibration = Swept sine: 4 G, 5 mm, 5-2000 Hz, 3 hr min/axis, including four 30-minute dwells at resonant frequencies.

Shock = 40 G, 11 ms sawtooth pulse.

Installation Overvoltage Category = Category III

Air Quality = Pollution Degree 2.

DIMENSIONS

Linear (maximum) = Length: 273.6 mm (10.77 in), Width: 214.1 mm (8.43 in), Height: 59.2 mm (2.33 in)

Weight = 1397 g (49.3 oz) approximate

SAFETY AND EMC STANDARDS COMPLIANCE

Conforms to EMC Directive 89/336/EEC. Conformity established by testing.

Conforms to Low Voltage Directive 73/23/EEC when used in accordance with instructions. Conformity established by testing.

Listed to UL and cUL Industrial Control Equipment (UL508).

*-When used with a speed control having a gain of 0.382% speed change per 1% duty cycle change.

Caterpillar Information System:

INSTALLATION AND OPERATION LOAD SHARING MODULE Chapter 5 - Troubleshooting
INSTALLATION AND OPERATION LOAD SHARING MODULE Chapter 4 - Theory Of Operation
INSTALLATION AND OPERATION LOAD SHARING MODULE Chapter 3 - Setup and Calibration
INSTALLATION AND OPERATION LOAD SHARING MODULE Chapter 2 - Installation
INSTALLATION AND OPERATION LOAD SHARING MODULE Chapter 1 - General Information
INSTALLATION AND OPERATION LOAD SHARING MODULE Electrostatic Discharge Awareness
VISATRON OIL MIST DETECTORS VN115/87PLUS, VN116/87 PLUS, VN2 Service Partners
VISATRON OIL MIST DETECTORS VN115/87PLUS, VN116/87 PLUS, VN2 Technical data
VISATRON OIL MIST DETECTORS VN115/87PLUS, VN116/87 PLUS, VN2 Optional Spare Parts and Accessories
VISATRON OIL MIST DETECTORS VN115/87PLUS, VN116/87 PLUS, VN2 Functional test
VISATRON OIL MIST DETECTORS VN115/87PLUS, VN116/87 PLUS, VN2 Maintenance procedures
VISATRON OIL MIST DETECTORS VN115/87PLUS, VN116/87 PLUS, VN2 Troubleshooting
INSTALLATION AND OPERATION LOAD SHARING MODULE Appendix B. - Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, & Modules
INSTALLATION AND OPERATION LOAD SHARING MODULE Appendix C. - EMI Control in Electronic Governing Systems
CX28 On-Highway Transmission Electrical System 311-7810-01 CX28 On-Highway Transmission Electrical System 311-7810-01
CX35 On-highway Transmission Electrical System 311-6527-00 CX35 On-highway Transmission Electrical System 311-6527-00
TA22-M4WD Agricultural Tansmission Electrical System (Interactive) 291-4080 TA22-M4WD Agricultural Tansmission Electrical System (Interactive) 291-4080
TH48 - E70 Petroleum Transmission Electrical System (Interactive) 320-8181-01 TH48 - E70 Petroleum Transmission Electrical System (Interactive) 320-8181-01
TH55 - E70 and TH55-E90 Petroleum Transmission Electrical System (Interactive) 292-0053-03 TH55 - E70 and TH55-E90 Petroleum Transmission Electrical System (Interactive) 292-0053-03
TH48 - E80 OEM Transmission Electrical System (Interactive), 317-1655-01 TH48 - E80 OEM Transmission Electrical System (Interactive), 317-1655-01
SCR System for Stationary Engines Electrical System SCR System for Stationary Engines Electrical System
C13 On-highway Engine Electrical System (LEE1-840) 238-6712-11 C13 On-highway Engine Electrical System (LEE1-840) 238-6712-11
C15 On-Highway Truck Engine Electrical System (For Serial Numbers SDP1-822) (Interactive) 265-9115-12 C15 On-Highway Truck Engine Electrical System (For Serial Numbers SDP1-822) (Interactive) 265-9115-12
C32 Marine Engine Electrical System (For Serial Numbers RNX1-296, RNY1-780, RNZ1-371)All Other Serial Numbers 1-UP) C32 Marine Engine Electrical System (For Serial Numbers RNX1-296, RNY1-780, RNZ1-371)All Other Serial Numbers 1-UP)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.