- Electric Power Generation
- 3412 GENSET (S/N: DK61-UP)
Introduction
The problem that is identified below does not have a known permanent solution. Until a permanent solution is known, use the solution that is identified below.
Problem
Certain 3412 Generator Sets wiring is configured incorrectly, configuration for wiring on shopfloor papers did not match customer requirement.
Solution
Do not operate or work on this product unless you have read and understood the instruction and warnings in the relevant Operation and Maintenance Manuals and relevant service literature. Failure to follow the instructions or heed the warnings could result in injury or death. Proper care is your responsibility. |
Illustration 1 | g06403547 |
Generator set wiring |
Caterpillar is aware of this issue and is reworking in-house stock. Dealers facing the issue in the field can ensure that alternators are checked for being wired correctly. Refer to Illustration 1.
Ensure that the alternator is wired for series star or parallel star as shown in Illustration 1. Review Table 1 and 2 given below which confirms the wiring configuration for each alternator part number, giving particular attention to the dedicated windings for 380V parallel star.
Standard Windings: | Standard | CIP | PREMIUM | 60Hz | 50Hz | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Cat codes | 220 | 240 | 440 | 480 | 380 | 400 | 415 | ||||
ECO43-1S/4 | p.star | p.star | s.star | s.star | s.star | s.star | s.star | ||||
ECO43-2S/4 | p.star | p.star | s.star | s.star | s.star | s.star | s.star | ||||
ECO43-1M/4 | p.star | p.star | s.star | s.star | s.star | s.star | s.star |
Dedicated Windings: | Standard | CIP | PREMIUM | 60Hz | |
---|---|---|---|---|---|
380V 60Hz | Cat codes | 380 | |||
ECO43-1S/4 | p.star | ||||
ECO43-2S/4 | p.star | ||||
ECO43-1M/4 | p.star |