XQ570 Rental Generator Set Caterpillar


Maintenance Interval Schedule - Standby

Usage:

C18 ME5
Ensure that all safety information, warnings, and instructions are read and understood before any operation or any maintenance procedures are performed. The user is responsible for the performance of maintenance, including all adjustments, the use of proper lubricants, fluids, and filters. The user is also responsible for the replacement of components due to normal wear and aging. Failure to adhere to proper maintenance intervals and procedures may result in diminished performance of the product and/or accelerated wear of components. Use fuel consumption, service hours, or calendar time, WHICH EVER OCCURS FIRST, to determine the maintenance intervals. Products that operate in severe operating conditions may require more frequent maintenance. Before each consecutive interval is performed, all maintenance from the previous interval must be performed.

When Required

Battery - Replace
Battery or Battery Cable - Disconnect
Fuel System - Prime
Generator - Dry
Generator Set - Test
Generator Set Alignment - Check

Daily

Coolant Level - Check
Engine Oil Level - Check
Generator Load - Check
Trailer - Inspect
Walk-Around Inspection

Every 6000 Service Hours or 3 Years

Coolant (ELC) - Change

Every Week

Automatic Start/Stop - Inspect
Battery Charger - Check
Electrical Connections - Check
Engine Air Cleaner Service Indicator - Inspect
Fuel System Water Separator - Check/Drain
Fuel Tank Water and Sediment - Drain
Generator - Inspect
Generator Bearing Temperature - Test/Record
Stator Winding Temperature - Test
Voltage and Frequency - Check

Every 250 Service Hours

Radiator - Clean

Every 250 Service Hours or 6 Months

Battery Electrolyte Level - Check

Every Year

Alternator - Inspect
Belts - Inspect/Adjust/Replace
Coolant Sample (Level 2) - Obtain
Engine - Clean
Engine Air Cleaner Element (Dual Element) - Inspect/Clean/Replace
Engine Mounts - Inspect
Engine Oil Sample - Obtain
Engine Oil and Filter - Change
Engine Valve Lash - Check
Fuel System Primary Filter (Water Separator) Element - Replace
Fuel System Secondary Filter - Replace
Fumes Disposal Filter Element - Replace
Generator Bearing - Lubricate
Generator Set Vibration - Test/Record
Hoses and Clamps - Inspect/Replace
Starting Motor - Inspect

Every 3 Years

Coolant Temperature Regulator - Replace

Every 3000 Service Hours or 3 Years

Coolant (DEAC) - Change
Coolant Extender (ELC) - Add

Caterpillar Information System:

XQ570 Rental Generator Set Maintenance Interval Schedule - Prime Power
Pre-Assembly of the Pinion Shaft For Well Stimulation Pumps {5070} Pre-Assembly of the Pinion Shaft For Well Stimulation Pumps {5070}
2015/09/10 An Improved Engine Prelube Pump Is Now Available for Certain Off-Highway Trucks {1307, 1319}
C8.7 Marine Engine Temperature and Pressure Sensor (Engine Oil) - Remove and Install
Installation of Remote Disable Module (RDM) Kit on Cat® and Non-Cat Equipment {7606} Installation of Remote Disable Module (RDM) Kit on Cat® and Non-Cat Equipment {7606}
New Nitrogen Oxide Sensor Groups Are Used for Certain G3400 and G3500 Engines {191N} New Nitrogen Oxide Sensor Groups Are Used for Certain G3400 and G3500 Engines {191N}
C18 Marine Generator Set Product Storage
C18 Marine Generator Set Voltage Regulators
797F Off-Highway Truck Diesel Exhaust Fluid Injector - Replace - Emission Related Component
C7.1 Commercial Marine Engine Cylinder Head - Inspect
C18 Marine Generator Set Additional Messages
C8.7 Marine Engine Fuel Pressure Regulator - Remove and Install
NEHS1249 100T Track Repair Group {0374, 0599, 0700, 0729, 4169, 4170} NEHS1249 100T Track Repair Group {0374, 0599, 0700, 0729, 4169, 4170}
C13 Industrial Engine Model View Illustrations
Torque Specifications Tie Rods
Torque Specifications Cable
C175 Oil&Gas Offshore Engine Speed/Timing - Test
C18 MAR GENSET Electric Power Generation Fan - Remove and Install
XQ400 Power Module Generator Operation
C18 MAR GENSET Electric Power Generation Fan Drive - Remove and Install
G3606 and G3608 Engines Manual Barring Group - Remove and Install
G3606 and G3608 Engines Engine Oil Coolers - Remove and Install
4C2980 Valve Projection Group (3600){0374, 0599, 0701, 0703} 4C2980 Valve Projection Group (3600){0374, 0599, 0701, 0703}
Reman Fuel Injectors Have Been Shipped Without Providing Trim Files for Certain C15 Engines{0785, 1290} Reman Fuel Injectors Have Been Shipped Without Providing Trim Files for Certain C15 Engines{0785, 1290}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.