C9.3 Marine Auxiliary and Generator Set Engine Caterpillar


Engine Monitoring System

Usage:

C9.3 C93
The Electronic Control Module (ECM) provides a comprehensive, programmable engine monitoring system for this engine. The ECM monitors specific engine operating parameters in order to detect abnormal conditions that may develop. The ECM will generate an event code if a specific engine parameter exceeds an acceptable range that is defined by the engine monitoring system. The ECM will react with an action that is dependent on the severity of the condition.

The following actions may be initiated by the ECM. These actions are dependent on the severity of the condition.

  • Illumination of a warning lamp or warning alarm

  • Engine derate

  • Engine shutdown

Three possible responses may be available for each parameter. Some of the responses are not available for some of the parameters. Refer to Table 1.

Table 1
Indicators 
Warning Category Indicator  Severity 
(15) or (17)  Least Severe 
(16) or (18)  Moderate Severity 
(0) or (1)  Most Severe 

Use Caterpillar® Electronic Technician (Cat ET) to perform the following activities for the monitoring system:

  • Viewing parameters

  • Parameter programming

  • Set delay times

The default settings for the parameters are programmed at the factory. To accommodate unique applications and sites, some of the parameters may be reprogrammed with Cat ET. Use Cat ET to modify the monitoring system parameters.

Note: Some parameters do not require a password in order to be changed. Other parameters can be changed with customer passwords. Some of the parameters are protected by factory passwords. Some parameters cannot be changed. Some applications do not allow any changes to the programmable monitoring system. Parameters that are protected by factory passwords can only be changed by dealer personnel.

Viewing or Changing the Settings of the Monitoring System

Use the following procedure in order to view the parameter settings and/or change the parameter settings:

  1. Select the "Service/Monitoring System" screen on Cat ET.

    Note: Ensure that you select the correct ECM for the parameters that are being changed before continuing.

  2. Highlight the desired parameter. Then click the "Change" button in the lower left corner of the screen.

    The "Change Monitor System" screen will appear.

  3. Change the "State" of the parameter.

  4. Set the "Trip Point" and the "Delay Time" according to the "Allowed Values" that are displayed in the lower half of the screen.

  5. Click the "OK" button.

    If a password is required, the "Enter Passwords" screen will appear. Enter the correct passwords and then click the "OK" button.

    Note: If a factory password is required, the "Enter Factory Passwords" screen will appear. Refer to Troubleshooting, "Factory Passwords" for information that is related to obtaining factory passwords.

    The new settings will be effective immediately.

Note: Factory passwords are only available to service technicians from an authorized Caterpillar Dealership. Customers of Caterpillar do not have access to the Caterpillar Feature Protection System (FPS).