Winding Data for 173-7078 Generator through 194-6563 Generator
173-7078 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 304.8 mm (12 inch)     |
304.8 mm (12 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1-2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 25 of #14     | #6-1/2 Rd     | |||||
Mean Length Turn     | 1460.50 mm (57.5 inch)     |
1079.50 mm (42.5 inch)     |
|||||
Copper Weight     | 82.5 kg (182 lb)     |
4683.76 mm (184.4 inch)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 of #00 (24 TOTAL)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00319 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.175 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 # 16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82000 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 of #10     |     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
173-7080 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 304.8 mm (12 inch)     |
304.8 mm (12 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1-2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 25 of #14     | #6-1/2 Rd     | |||||
Mean Length Turn     | 1460.50 mm (57.5 inch)     |
1079.50 mm (42.5 inch)     |
|||||
Copper Weight     | 82.5 kg (182 lb)     |
4683.76 mm (184.4 inch)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 of #00 (24 TOTAL)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00319 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.175 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 # 16     | 4 - # 18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82000 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 of #10     | 3-1 of #14 (3 total)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
178-1618 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 381.0 mm (15 inch)     |
393.70 mm (15.5 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 31 of # 13     | 1 of #6 square     | |||||
Mean Length Turn     | 1617.98 mm (63.7 inch)     |
1330.96 mm (52.4 inch)     |
|||||
Copper Weight     | 99.7 kg (220 lb)     |
161.4 kg (356 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12 - 4 of #2/0     | 1 of #8 Ld     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00172 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 18     | 12     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     | 4 - # 18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     | 3-1 of #14 (3 total)     |
Show/hide table
( 4 ) | Special Resistance is for Global design with 1320.8 mm (52 inch) Leads. |
( 3 ) | Winding 12 layers with 18 turns per layer = 216 turns. Insert 12.70 mm (0.5 inch) vent spacer after layers 6 and 6 in the coil heads |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
188-9842 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 172.72 mm (6.8 inch)     |
172.72 mm (6.8 inch)     |
|||||
Slots     | 48     | 4     | |||||
Coil Throw     | (A) 1-9 (B) 1-9     | 1-2     | |||||
Turns/Coil     | (A) 48 (B) 48     | -     | |||||
Turns/Pole     | (A) 5-6-5-6 (B) 6-5-6-5     | 130 (3)     | |||||
No. & Wire Size     | (A) 6#16 (B) 3#16     | #8 Square     | |||||
Mean Length Turn     | 922.02 mm (36.3 inch)     |
    | |||||
Copper Weight     | 25.94 kg (57.2 lb)     |
35.69 kg (78.7 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | 4 Pole Series     | |||||
Line Leads (No. & Size)     | 6-2 of #2 (12 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
(A) 0.027100 ohms (B) 0.051400 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 0.753 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 120 Hz     | ||||
Exciter Poles     | 6     | 6     | 8     | ||||
Stack Length     | 76.2 mm (3 inch)     |
76.2 mm (3 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 6     | 36     | 24     | ||||
Turns (Coils)     | 150     | 7     | 12     | ||||
No. & Size Wire     | #16     | 2 of #151/2     | 2#18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 363.22 mm (14.3 inch)     |
325.12 mm (12.8 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.295 ohms     | 0.083 ohms     | 0.551 ohms     | ||||
Copper Weight     | 3.85 kg (8.5 lb)     |
2.17 kg (4.8 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 4 ) | Dual Winding Label Wind A and Label Wind B |
( 3 ) | Layer wound 12.70 mm (0.5 inch) vent openings to divide layers 3-4-3 in coil heads. 10 Layers 13 turns/layer - 130 total turns/pole. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
188-9848 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 495.30 mm (19.5 inch)     |
495.30 mm (19.5 inch)     |
|||||
Slots     | 48     | 4     | |||||
Coil Throw     | 1-10     | 1-2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     |     | 130     | |||||
No. & Wire Size     | 18 # 14     | #8 Square     | |||||
Mean Length Turn     | 1623.06 mm (63.9 inch)     |
1397.0 mm (55 inch)     |
|||||
Copper Weight     | 52.93 kg (116.7 lb)     |
66.40 kg (146.4 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 # 1/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00377 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.4 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 120 Hz     | ||||
Exciter Poles     | 6     | 6     | 8     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 1     | 2     | 24     | ||||
Turns (Coils)     | 150     | 8     | 12     | ||||
No. & Size Wire     | #16     | 2 of #16     | 2#18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 388.62 mm (15.3 inch)     |
419.10 mm (16.5 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.63 ohms     | 0.115 ohms     | 0.551 ohms     | ||||
Copper Weight     | 4.12 kg (9.1 lb)     |
2.35 kg (5.2 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 4 ) | When specified on process sheets: Place 120 V tap lead (X1) seven turns from neutral (Start) in coil group 10. Voltage will be 121.2(117.6/124.8) |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
188-9849 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 495.30 mm (19.5 inch)     |
495.30 mm (19.5 inch)     |
|||||
Slots     | 48     | 4     | |||||
Coil Throw     | 1-10     | 1-2     | |||||
Turns/Coil     | 2.5 (3-2-3-2) (4)     | -     | |||||
Turns/Pole     |     | 130     | |||||
No. & Wire Size     | 14 - #14     | #8 Square     | |||||
Mean Length Turn     | 1649.730 mm (64.95 inch)     |
1397.0 mm (55 inch)     |
|||||
Copper Weight     | 51.43 kg (113.4 lb)     |
66.40 kg (146.4 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 4-1 of #0000     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0215 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.4 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 120 Hz     | ||||
Exciter Poles     | 6     | 6     | 8     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 1     | 2     | 24     | ||||
Turns (Coils)     | 150     | 8     | 12     | ||||
No. & Size Wire     | #16     | 2 of #16     | 2#18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 388.62 mm (15.3 inch)     |
419.10 mm (16.5 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.63 ohms     | 0.115 ohms     | 0.551 ohms     | ||||
Copper Weight     | 4.12 kg (9.1 lb)     |
2.35 kg (5.2 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 4 ) | When p/s specify: Tap X1, X2, and X3 leads #10 wire in pole group 10, 8, and 12 seven turns away from start(neutral) end. Tap 20, 22, 24 leads eighth (8) turns from neutral (star) in coil groups 6, 4, 2 respectively. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
193-8723 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 304.8 mm (12 inch)     |
304.8 mm (12 inch)     |
|||||
Slots     | 48     | 4     | |||||
Coil Throw     | 1-10     | 1-2     | |||||
Turns/Coil     | 2.5 (2-3-2-3)     | -     | |||||
Turns/Pole     |     | 130     | |||||
No. & Wire Size     | 12 # 14 (2-3-2-3)     | #8 Square     | |||||
Mean Length Turn     | 1244.6 mm (49 inch)     |
1016.0 mm (40 inch)     |
|||||
Copper Weight     | 33.5 kg (74 lb)     |
48.30 kg (106.5 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-1 # 4/0 (12 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00529 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 0.963 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 120 Hz     | ||||
Exciter Poles     | 6     | 6     | 8     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 1     | 1     | 24     | ||||
Turns (Coils)     | 150     | 18     | 12     | ||||
No. & Size Wire     | #16     | 2 of #16.5     | 2#18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 388.62 mm (15.3 inch)     |
374.650 mm (14.75 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.63 ohms     | 0.155 ohms     | 0.551 ohms     | ||||
Copper Weight     | 4.12 kg (9.1 lb)     |
2.17 kg (4.8 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
193-8731 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.68 mm (14.2 inch)     |
360.68 mm (14.2 inch)     |
|||||
Slots     | 48     | 4     | |||||
Coil Throw     | 1-10     | 1-2     | |||||
Turns/Coil     | 2.5 (2-3-2-3)     | -     | |||||
Turns/Pole     |     | 130     | |||||
No. & Wire Size     | 12 # 14     | #8 Square     | |||||
Mean Length Turn     | 1353.82 mm (53.3 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 40.14 kg (88.5 lb)     |
53.61 kg (118.2 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-1 # 3/0 (12 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00574 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.115 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 120 Hz     | ||||
Exciter Poles     | 6     | 6     | 8     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 1     | 1     | 24     | ||||
Turns (Coils)     | 150     | 18     | 12     | ||||
No. & Size Wire     | #16     | 2 of #16.5     | 2#18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 388.62 mm (15.3 inch)     |
374.650 mm (14.75 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.63 ohms     | 0.155 ohms     | 0.551 ohms     | ||||
Copper Weight     | 4.12 kg (9.1 lb)     |
2.17 kg (4.8 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4571 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 20 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 48.5 kg (107 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     | 120 Hz     | 120 Hz     | ||||
Exciter Poles     | 8     | 8     | 8     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 8     | 48     | 24     | ||||
Turns (Coils)     | 178     | 10     | 12     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16.5     | 2 of #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     | 0.551 ohms     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 4 ) | When required, place 120 V tap leads (X1) 6 turns from neutral (start) in coil group 10. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4575 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 20 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 48.5 kg (107 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     |     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
    | ||||
Coils/Group     | 8     | 2     |     | ||||
Turns (Coils)     | 178     | 10     |     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     |     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10     |     |
Show/hide table
( 4 ) | When required, place 120 V tap leads (X1) 6 turns from neutral (start) in coil group 10. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4583 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 20 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 48.5 kg (107 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     | 120 Hz     | 120 Hz     | ||||
Exciter Poles     | 8     | 8     | 8     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 8     | 48     | 24     | ||||
Turns (Coils)     | 178     | 10     | 12     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     | 2 of #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     | 0.551 ohms     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 4 ) | When required, place 120 V tap leads (X1) 6 turns from neutral (start) in coil group 10. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4587 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 20 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 48.5 kg (107 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     |     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
    | ||||
Coils/Group     | 8     | 2     |     | ||||
Turns (Coils)     | 178     | 10     |     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     |     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10     |     |
Show/hide table
( 4 ) | When required, place 120 V tap leads (X1) 6 turns from neutral (start) in coil group 10. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4588 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 20 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 48.5 kg (107 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     |     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
    | ||||
Coils/Group     | 8     | 2     |     | ||||
Turns (Coils)     | 178     | 10     |     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     |     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10     |     |
Show/hide table
( 4 ) | When required, place 120 V tap leads (X1) 6 turns from neutral (start) in coil group 10. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4589 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 48     | 4     | |||||
Coil Throw     | 1-9     | 1-2     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 12 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1600.2 mm (63 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 51.7 kg (114 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00795 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     |     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
    | ||||
Coils/Group     | 8     | 2     |     | ||||
Turns (Coils)     | 178     | 10     |     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     |     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10     |     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 seven (7) turns from neutral in coil groups 3, 1, and 5 respectively. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4590 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1-2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 15 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1617.98 mm (63.7 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 54.65 kg (120.5 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00536 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     |     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
    | ||||
Coils/Group     | 8     | 2     |     | ||||
Turns (Coils)     | 178     | 10     |     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     |     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10     |     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 eight (8) turns from neutral in coil groups 6, 8, and 10 respectively. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4591 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 20 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 48.5 kg (107 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     | 120 Hz     | 120 Hz     | ||||
Exciter Poles     | 8     | 8     | 8     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 8     | 48     | 24     | ||||
Turns (Coils)     | 178     | 10     | 12     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     | 2 of #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     | 0.551 ohms     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 4 ) | When required, place 120 V tap leads (X1) 6 turns from neutral (start) in coil group 10. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-4594 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.050 mm (20.75 inch)     |
527.050 mm (20.75 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1-2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     |     | 138 (3)     | |||||
No. & Wire Size     | 15 of # 14     | #8 Square     | |||||
Mean Length Turn     | 1617.98 mm (63.7 inch)     |
1447.8 mm (57 inch)     |
|||||
Copper Weight     | 54.65 kg (120.5 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | Leadless     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00536 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.58 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 120 Hz     | 120 Hz     | 120 Hz     | ||||
Exciter Poles     | 8     | 8     | 8     | ||||
Stack Length     | 50.8 mm (2 inch)     |
50.8 mm (2 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 8     | 48     | 24     | ||||
Turns (Coils)     | 178     | 10     | 12     | ||||
No. & Size Wire     | 1 of #14.5     | 2 of #16     | 2 of #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 304.8 mm (12 inch)     |
330.2 mm (13 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.38 ohms     | 0.177 ohms     | 0.551 ohms     | ||||
Copper Weight     | 10.25 kg (22.6 lb)     |
3.71 kg (8.2 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 eight (8) turns from neutral in coil groups 6, 8, and 10 respectively |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 2-3-3-3 in coil head. Winding table: Start- 9 layers of 13 turns/layer, 1 layer of 12 turns/layer, 1 layer of 9 turns/layer. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
194-6560 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.1 mm (20.75 inch)     |
527.1 mm (20.75 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 138     | |||||
No. & Wire Size     | 19 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1605.3 mm (63.2 inch)     |
-     | |||||
Copper Weight     | 54.9 kg (121 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | -     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00285 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.430 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
-     | ||||
Coils/Group     | -     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 178     | 12     | -     | ||||
No. & Size Wire     | 1 - #14.5     | 2 - #17.5     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 304.8 mm (12.0 inch)     |
1066.8 mm (42.0 inch)     |
-     | ||||
Copper Weight     | 10.3 kg (22.6 lb)     |
3.6 kg (7.9 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 64 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
194-6561 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.1 mm (20.75 inch)     |
527.1 mm (20.75 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 138     | |||||
No. & Wire Size     | 19 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1605.3 mm (63.2 inch)     |
-     | |||||
Copper Weight     | 54.9 kg (121 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | -     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00285 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.430 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
-     | ||||
Coils/Group     | -     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 178     | 12     | -     | ||||
No. & Size Wire     | 1 - #14.5     | 2 - #17.5     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 304.8 mm (12.0 inch)     |
1066.8 mm (42.0 inch)     |
-     | ||||
Copper Weight     | 10.3 kg (22.6 lb)     |
3.6 kg (7.9 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 64 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
194-6562 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.1 mm (20.75 inch)     |
527.1 mm (20.75 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 138     | |||||
No. & Wire Size     | 19 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1605.3 mm (63.2 inch)     |
-     | |||||
Copper Weight     | 54.9 kg (121 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | -     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00285 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.430 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
-     | ||||
Coils/Group     | -     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 178     | 12     | -     | ||||
No. & Size Wire     | 1 - #14.5     | 2 - #17.5     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 304.8 mm (12.0 inch)     |
1066.8 mm (42.0 inch)     |
-     | ||||
Copper Weight     | 10.3 kg (22.6 lb)     |
3.6 kg (7.9 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 64 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
194-6563 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 527.1 mm (20.75 inch)     |
527.1 mm (20.75 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 138     | |||||
No. & Wire Size     | 19 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1605.3 mm (63.2 inch)     |
-     | |||||
Copper Weight     | 54.9 kg (121 lb)     |
73.0 kg (161 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | -     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00285 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.430 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
-     | ||||
Coils/Group     | -     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 178     | 12     | -     | ||||
No. & Size Wire     | 1 - #14.5     | 2 - #17.5     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 304.8 mm (12.0 inch)     |
1066.8 mm (42.0 inch)     |
-     | ||||
Copper Weight     | 10.3 kg (22.6 lb)     |
3.6 kg (7.9 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 64 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
Caterpillar Information System:
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 164-0975 Generator through 164-4946 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 158-6410 Generator through 163-8546 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 149-2447 Generator through 150-9152 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1964 Generator through 144-2088 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6610 Generator through 136-6641 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1666 Generator through 144-1766 Generator
3512C Petroleum Engines with Dynamic Gas Blending Engine Shutdown Occurrence
312D2 and 313D2 Excavators System Pressure Release
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 141-5534 Generator through 142-9900 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6580 Generator through 136-6609 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 126-8022 Generator through 128-7424 Generator
C1.7, C1.8 and C2.4 Tier 4 Interim and EU Stage 3A Engines for Caterpillar Built Machines Engine Oil Pressure Switch
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 203-5749 Generator through 324-5120 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 6I-0053 Generator through 6I-4860 Generator
2013/11/11 An Improved ARD Combustion Head is Now Used on the Tier 4 Engines of Certain Machines {108B, 108E, 108M}
2013/11/21 An Improved ARD Combustion Head is Now Used on Certain Tier 4 Engines {108B, 108E, 108M}
Installation of G610 Hardware for Cat® Terrain for Motor Graders, Wheel Dozers, and Wheel Loaders {7605} Installation of G610 Hardware for Cat® Terrain for Motor Graders, Wheel Dozers, and Wheel Loaders {7605}
3512C Oil Well Service Engines Air Shutoff - Test
793F and 797F Off-Highway Trucks Braking System Automatic Retarder Control (ARC)
3500E EPA Tier 4 Final and IMO-II/III Switchable Marine Engines Sensor Calibration Required - Test
374F Excavator Hydraulic System General Information (Return System)
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 109-3776 Generator through 109-7874 Generator
2013/08/30 A New Adapter Is Used on Certain 3512C Petroleum Engines {1157}
966M Tier 4 and 972M Tier 4 Wheel Loaders Power Train Modulating Valve (Torque Converter Lockup Clutch) - Remove and Install