144-1666 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 558.8 mm (22 inch)     |
571.50 mm (22.5 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1 - 2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 53 of #13     | 1 of #6 Square     | |||||
Mean Length Turn     | 1966.214 mm (77.41 inch)     |
1686.56 mm (66.4 inch)     |
|||||
Copper Weight     | 147.8 kg (326 lb)     |
216.3 kg (477 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-8 of #1 (48 Total)     | 1 of #8 Ld     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00324 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.66 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 3 ) | Winding table: Wind 12 layers with 18 turns per layer = 216 turns. Insert 12.70 mm (0.5 inch) vent spacer after layers 6 and 6 in the coil heads |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1668 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 596.90 mm (23.5 inch)     |
609.6 mm (24 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     |     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 62 OF #13     | #6 Square     | |||||
Mean Length Turn     | 2301.24 mm (90.6 inch)     |
1755.902 mm (69.13 inch)     |
|||||
Copper Weight     | 228.6 kg (504 lb)     |
225.4 kg (497 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 62 OF #13     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.686 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | Special Res for Global designs. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 6-6 in coil head. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1674 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 520.70 mm (20.5 inch)     |
533.4 mm (21 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1-2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 216.5 (3)     | |||||
No. & Wire Size     | 40 #13     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2118.36 mm (83.4 inch)     |
1638.30 mm (64.5 inch)     |
|||||
Copper Weight     | 241.7 kg (533 lb)     |
371.9 kg (820 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-8 #1/0 Leads (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00231 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 0.9324 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | For SE machines, install tap leads at 5-turns from neutral in coil groups 1, 3, and 5. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent opening to be divided at layers 9-8 in the coil head. (wind 9 layers - put in spacer - wind last 8-layers) |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1678 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 584.2 mm (23 inch)     |
596.90 mm (23.5 inch)     |
|||||
Slots     | 96     | 4     | |||||
Coil Throw     | 1-19     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5 (3)     | |||||
No. & Wire Size     | 41 #13     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2580.64 mm (101.6 inch)     |
1765.30 mm (69.5 inch)     |
|||||
Copper Weight     | 299.36940 kg (660 lb)     |
400.06638 kg (882 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-8 #2/0 Leads (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00188 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.003 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | For SE generators only: Voltage regulator leads 20, 22, 24 are to be tapped 4 turns from neutral in pole groups 3, 1 and 5 respectively. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent opening to be divided at layers 9-8 in the coil head. (wind 9 layers - put in spacer - wind last 8-layers) |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1680 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 660.4 mm (26 inch)     |
673.10 mm (26.5 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-16     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5 (3)     | |||||
No. & Wire Size     | 58 #14     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch) Heavy Film     |
|||||
Mean Length Turn     | 2550.16 mm (100.4 inch)     |
1917.70 mm (75.5 inch)     |
|||||
Copper Weight     | 235.8 kg (520 lb)     |
435.44640 kg (960 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6 - 8 of # 3/0     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00147 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.12 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | For SE Generators Only: Voltage regulator leads 26, 28, 30 are to be tapped 3 turns from neutral in pole groups 3, 1, and 5 respectively. 26, 28, 30 used for power only. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent opening to be divided at layers 9-8 in the coil head. (wind 9 layers - put in spacer - wind last 8 layers) |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1686 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 330.2 mm (13 inch)     |
342.9 mm (13.5 inch)     |
|||||
Slots     | 96     | 4     | |||||
Coil Throw     | 1-18     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 27 #13     | #6 Square     | |||||
Mean Length Turn     | 1798.32 mm (70.8 inch)     |
1229.36 mm (48.4 inch)     |
|||||
Copper Weight     | 111.5 kg (246 lb)     |
157.8 kg (348 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 1/0 (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00205 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.166 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 3 ) | 12 layers, 18 turns per layer. Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1688 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 368.30 mm (14.5 inch)     |
381.0 mm (15 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-16     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 27 #13     | #6 Square     | |||||
Mean Length Turn     | 1752.6 mm (69 inch)     |
1298.702 mm (51.13 inch)     |
|||||
Copper Weight     | 95.2 kg (210 lb)     |
166.64897 kg (367.4 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 2/0 (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00191 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1692 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 381.0 mm (15 inch)     |
393.70 mm (15.5 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-16     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 31 #13     | 1 - #6 Square     | |||||
Mean Length Turn     | 1823.72 mm (71.8 inch)     |
1330.96 mm (52.4 inch)     |
|||||
Copper Weight     | 113.3 kg (250 lb)     |
161.4 kg (356 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-4 # 2/0 (48 total)     | 1-of #8 Ld     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0019 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | Special Res. for Global Design with 1320.8 mm (52 inch) leads. |
( 3 ) | Wind 12 layers with 18 turns per layer = 216 turns. Insert 12.70 mm (0.5 inch) vent spacer after layers 6 and 6 in the coil heads. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 65 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1694 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 381.0 mm (15 inch)     |
393.70 mm (15.5 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-16     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 31 #13     | 1 - #6 Square     | |||||
Mean Length Turn     | 1823.72 mm (71.8 inch)     |
1330.96 mm (52.4 inch)     |
|||||
Copper Weight     | 113.3 kg (250 lb)     |
161.4 kg (356 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-4 # 2/0 (48 total)     | 1-of #8 Ld     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0019 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | Special Res. for Global Design with 1320.8 mm (52 inch) leads. |
( 3 ) | Wind 12 layers with 18 turns per layer = 216 turns. Insert 12.70 mm (0.5 inch) vent spacer after layers 6 and 6 in the coil heads. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 65 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1696 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.850 mm (17.75 inch)     |
463.550 mm (18.25 inch)     |
|||||
Slots     | 72     | 4     | |||||
Coil Throw     | 1-14     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 37 #13     | #6 Square     | |||||
Mean Length Turn     | 1925.32 mm (75.8 inch)     |
1463.04 mm (57.6 inch)     |
|||||
Copper Weight     | 141.5 kg (312 lb)     |
187.7 kg (414 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 2/0 (48 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00141 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.389 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | Special Res. for Global Design with 1320.8 mm (52 inch) leads. |
( 3 ) | Wind 12 layers with 18 turns per layer = 216 turns. Insert 12.70 mm (0.5 inch) vent spacer after layers 6 and 6 in the coil heads. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1698 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.850 mm (17.75 inch)     |
463.550 mm (18.25 inch)     |
|||||
Slots     | 72     | 4     | |||||
Coil Throw     | 1-14     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 37 #13     | #6 Square     | |||||
Mean Length Turn     | 1925.32 mm (75.8 inch)     |
1463.04 mm (57.6 inch)     |
|||||
Copper Weight     | 141.5 kg (312 lb)     |
187.7 kg (414 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 2/0 (48 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00141 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.389 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 4 ) | Special Res. for Global Design with 1320.8 mm (52 inch) leads. |
( 3 ) | Wind 12 layers with 18 turns per layer = 216 turns. Insert 12.70 mm (0.5 inch) vent spacer after layers 6 and 6 in the coil heads. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1700 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20 inch)     |
520.70 mm (20.5 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 41 #13     | #6 Square Heavy Film     | |||||
Mean Length Turn     | 1191.26 mm (46.9 inch)     |
1584.96 mm (62.4 inch)     |
|||||
Copper Weight     | 113.3 kg (250 lb)     |
215.4 kg (475 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 3/0 (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00119 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.488 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 6-6 in coil head. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1702 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20 inch)     |
520.70 mm (20.5 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 41 #13     | #6 Square Heavy Film     | |||||
Mean Length Turn     | 1191.26 mm (46.9 inch)     |
1584.96 mm (62.4 inch)     |
|||||
Copper Weight     | 113.3 kg (250 lb)     |
215.4 kg (475 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 3/0 (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00119 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.488 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 18     |     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     |     |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to divide layers 6-6 in coil head. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1704 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 558.8 mm (22 inch)     |
571.50 mm (22.5 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 53 #13     | 1 of #6 Square     | |||||
Mean Length Turn     | 2128.52 mm (83.8 inch)     |
1686.56 mm (66.4 inch)     |
|||||
Copper Weight     | 161.0 kg (355 lb)     |
216.3 kg (477 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-8 # 1 (48 total)     | 1 of #8 Ld     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0034 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.66 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 18     | 12     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     | 3-1 OF #14 (3 total)     |
( 4 ) | Special Res. for Global Design with 1320.8 mm (52 inch) leads. |
( 3 ) | Wind 12 layers with 18 turns per layer = 216 turns. Insert 12.70 mm (0.5 inch) vent spacer after layers 6 and 6 in the coil heads. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1705 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 596.9 mm (23.5 inch)     |
609.6 mm (24 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 62 - #13     | #6 SQ     | |||||
Mean Length Turn     | 2301.2 mm (90.6 inch)     |
-     | |||||
Copper Weight     | 204.1 kg (450 lb)     |
225.4 kg (497 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00292 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.666 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 2     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 9     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 1 - #16 1 - #16.5     |
4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 515.6 mm (20.3 inch)     |
431.8 mm (17 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 6.0 kg (13.3 lb)     |
3.1 kg (6.9 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 61 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1708 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 469.90 mm (18.5 inch)     |
482.6 mm (19 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5 (3)     | |||||
No. & Wire Size     | 58 #13     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2092.96 mm (82.4 inch)     |
1536.70 mm (60.5 inch)     |
|||||
Copper Weight     | 174.6 kg (385 lb)     |
349.2 kg (770 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-8 # 1     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00292 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 0.876 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 18     | 12     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35 Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     | 3-1 OF #14 (3 total)     |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to be divided at layers 9-8 in the coil head. (wind 9 layers - put in spacer - wind last 8 layers) |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1713 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 520.7 mm (20.5 inch)     |
533.4 mm (21 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5     | |||||
No. & Wire Size     | 80 - #13     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2118.3 mm (83.4 inch)     |
-     | |||||
Copper Weight     | 241.7 kg (533 lb)     |
371.9 kg (820 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00231 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.9324 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 2     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 160     | 7     | 12     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13 inch)     |
368.3 mm (14.5 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel     | Series Wye     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 61 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1715 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 584.2 mm (23 inch)     |
596.9 mm (23.5 inch)     |
|||||
Slots     | 96     | -     | |||||
Coil Throw     | 1 - 20     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5     | |||||
No. & Wire Size     | 41 - #13     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2379.4 mm (93.68 inch)     |
-     | |||||
Copper Weight     | 221.3 kg (488 lb)     |
400.1 kg (882 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00190 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.003 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 2     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 160     | 7     | 12     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13 inch)     |
368.3 mm (14.5 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel     | Series Wye     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 29 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1717 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 660.4 mm (26 inch)     |
673.1 mm (26.5 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 16     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5     | |||||
No. & Wire Size     | 58 - #14     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2550.1 mm (100.4 inch)     |
-     | |||||
Copper Weight     | 235.8 kg (520 lb)     |
435.4 kg (960 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00147 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.077 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 2     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 160     | 7     | 12     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13 inch)     |
368.3 mm (14.5 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel     | Series Wye     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 29 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1723 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 558.8 mm (22 inch)     |
571.5 mm (22.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 53 - #13     | #6 SQ     | |||||
Mean Length Turn     | 2128.5 mm (83.8 inch)     |
-     | |||||
Copper Weight     | 161.0 kg (355 lb)     |
216.3 kg (477 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00319 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.660 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 2     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 9     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 1 - #16 1 - #16.5     |
4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 515.6 mm (20.3 inch)     |
431.8 mm (17 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 6.0 kg (13.3 lb)     |
3.1 kg (6.9 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 61 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1744 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 330.2 mm (13 inch)     |
342.90 mm (13.5 inch)     |
|||||
Slots     | 96     | 4     | |||||
Coil Throw     | 1-18     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 27 #13     | #6 Square     | |||||
Mean Length Turn     | 1798.32 mm (70.8 inch)     |
1229.36 mm (48.4 inch)     |
|||||
Copper Weight     | 111.5 kg (246 lb)     |
157.8 kg (348 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 1/0 (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00205 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.166 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 18     | 12     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35 Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     | 3-1 OF #14 (3 total)     |
( 3 ) | 12 layers, 18 turns per layer. Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1745 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 368.3 mm (14.5 inch)     |
381.0 mm (15 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 16     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 27 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1752.6 mm (69 inch)     |
-     | |||||
Copper Weight     | 95.2 kg (210 lb)     |
166.6 kg (367.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00623 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.232 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1747 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 368.3 mm (14.5 inch)     |
381.0 mm (15 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 16     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 27 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1752.6 mm (69 inch)     |
-     | |||||
Copper Weight     | 95.2 kg (210 lb)     |
166.6 kg (367.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00623 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.232 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1749 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 368.3 mm (14.5 inch)     |
393.7 mm (15.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 15     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 40 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1833.8 mm (72.2 inch)     |
-     | |||||
Copper Weight     | 127.0 kg (280 lb)     |
170.7 kg (376.5 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00418 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 48     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1751 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 368.3 mm (14.5 inch)     |
393.7 mm (15.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 15     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 40 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1833.8 mm (72.2 inch)     |
-     | |||||
Copper Weight     | 127.0 kg (280 lb)     |
170.7 kg (376.5 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00418 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 48     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1753 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.8 mm (17.75 inch)     |
469.9 mm (18.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 14     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 37 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1925.3 mm (75.8 inch)     |
-     | |||||
Copper Weight     | 122.4 kg (270 lb)     |
189.6 kg (418 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00141 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.401 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1755 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.8 mm (17.75 inch)     |
469.9 mm (18.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 14     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 37 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1925.3 mm (75.8 inch)     |
-     | |||||
Copper Weight     | 122.4 kg (270 lb)     |
189.6 kg (418 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00141 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.401 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1757 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20 inch)     |
520.7 mm (20.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 40 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1953.2 mm (76.9 inch)     |
-     | |||||
Copper Weight     | 113.4 kg (250 lb)     |
203.6 kg (449 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00119 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.550 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1759 Generator
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20 inch)     |
520.7 mm (20.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 40 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1953.2 mm (76.9 inch)     |
-     | |||||
Copper Weight     | 113.4 kg (250 lb)     |
203.6 kg (449 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Wye     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00119 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.550 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.2 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (3.95 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Series Wye     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 49 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1768 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 381.0 mm (15 inch)     |
393.70 mm (15.5 inch)     |
|||||
Slots     | 84     | 4     | |||||
Coil Throw     | 1-15     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 31 #13     | 1 of #6 Square     | |||||
Mean Length Turn     | 1617.98 mm (63.7 inch)     |
1330.96 mm (52.4 inch)     |
|||||
Copper Weight     | 99.7 kg (220 lb)     |
161.4 kg (356 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12 - 4 of #2/0     | 1-of #8 Ld     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00172 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 18     | 12     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35 Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     | 3-1 OF #14 (3 total)     |
( 4 ) | Special Resistance is for Global design with 1320.8 mm (52 inch) Leads. |
( 3 ) | 12 layers, 18 turns per layer. Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1772 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.850 mm (17.75 inch)     |
463.550 mm (18.25 inch)     |
|||||
Slots     | 72     | 4     | |||||
Coil Throw     | 1-13     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 37 #13     | #6 Square     | |||||
Mean Length Turn     | 1739.90 mm (68.5 inch)     |
1463.04 mm (57.6 inch)     |
|||||
Copper Weight     | 109.7 kg (242 lb)     |
187.7 kg (414 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12 - 4 of # 2/0     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00145 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.389 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 18     | 12     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35 Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     | 3-1 OF #14 (3 total)     |
( 4 ) | Special Res. For Global Design. |
( 3 ) | 12 layers, 18 turns per layer. Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
144-1776 Generator Ar
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20 inch)     |
520.70 mm (20.5 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 41 #13     | #6 Square Heavy Film     | |||||
Mean Length Turn     | 1823.974 mm (71.81 inch)     |
1584.96 mm (62.4 inch)     |
|||||
Copper Weight     | 106.1 kg (234 lb)     |
215.4 kg (475 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 of #000 (48 Total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0012 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.488 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 120 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 18     | 12     | ||||
No. & Size Wire     | 2 of #16     | 4 #18     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35 Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.159 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
5.53 kg (12.2 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10 (3 Total)     | 3-1 OF #14 (3 total)     |
( 4 ) | Special Res. For Global Design. |
( 3 ) | 12 layers, 18 turns per layer. Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |