UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Caterpillar


Gen Set Module Circuit Breaker (Input/Output Cabinet)

Usage:

UPS 600G DLD

Description



Illustration 1g03604657

I/O cabinet

Generator set module (GSM) option

The generator set module start option (1) adds the following breakers to the I/O cabinet:

  • One breaker

  • Two breakers (CB11 and CB21)

The breakers are located on the front panel at the bottom of the cabinet behind the door. Refer to Illustration 1 for the location. The GSM start option (1) allows the UPS to control generators in cases of lost utility power. Also, the GSM start option (1) allows the UPS to start the external generator set if power is lost.

Refer to the following list of characteristics for the circuit breakers:

  • 480 VAC

  • 40 A

  • 3 - pole

Removal Procedure

Refer to Systems Operation, Testing and Adjusting, UENR3954, "Internal Component Preremoval Steps (Input/Output Cabinet)" in order to shut down the system and gain access to internal components.

  1. Disconnect the six wires that lead to the circuit breaker and from the circuit breaker. Verify the labeling on the wires with the location of the wires. Verify the labeling on the cables for subsequent installation.

  2. Remove the four screws on the front of the breaker that secure the breaker to the rear of the cabinet.

Installation Procedure



    Illustration 2g01271290
    GSM panel
    (2) GSM breaker 1
    (3) GSM breaker 2

  1. Attach the GSM circuit breaker (1) to the panel of the cabinet with four screws. Refer to Illustration 2.


    Illustration 3g03797531
    Generator set module (GSM) breaker found in some units
    (4) Breaker attachment screws
    (5) Cable connector screws

  2. Connect the wires from the cable landing and the generator set. Verify the labeling of the wires with the location of the wires.

Caterpillar Information System:

UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies External Source Sync Relay and Terminal Block
C7.1 Engines Pistons and Connecting Rods - Remove
C7.1 Engines Pistons and Connecting Rods - Install
C7.1 Engines Pistons and Connecting Rods - Disassemble
C7.1 Engines Pistons and Connecting Rods - Assemble
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Fan (Input/Output Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Isolation Switches
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Fan Transformer
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System Fuse (Input/Output Cabinet)
C7.1 Engines Piston Cooling Jets - Remove and Install
C7.1 Engines Lifter Group - Remove and Install
C3.3B Tier 4 Final Engines for Caterpillar Built Machines Fuel Injector
C7.1 Engines Rear Power Take-Off (RPTO) - Install
C7.1 Engines Rear Power Take-Off (RPTO) - Remove
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies General Information (MMS System Cabinet)
C7.1 Engines Refrigerant Compressor - Remove and Install
C7.1 Engines Relief Valve (Fuel) - Remove and Install
C7.1 Engines Rocker Shaft - Assemble
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
C7.1 Engines Rocker Shaft - Disassemble
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System Fuses (MMS System Cabinet)
C7.1 Engines Rocker Shaft and Pushrod - Install
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Front Panel Display (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies General Purpose Interface PWA (MMS System Cabinet)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.