Illustration 1 | g00912382 |
Illustration 2 | g00912383 |
There may be several specific messages on your equipment. The exact location and a description of the messages are reviewed in this section. Become familiar with all of the messages.
Ensure that all of the messages are legible. Clean the messages or replace the messages if the words cannot be read or if the illustrations are not visible. Use a cloth, water, and soap for cleaning the messages. Do not use solvents, gasoline, or other harsh chemicals. Solvents, gasoline, or harsh chemicals could loosen the adhesive that secures the messages. The messages that are loosened could drop off the engine.
Replace any message that is damaged or missing. If a message is attached to a part of the engine that is replaced, install a new message on the replacement part. Your Cat dealer can provide new messages.
Do not operate or work on this engine unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings could result in injury or death. Contact any Caterpillar dealer for replacement manuals. Proper care is your responsibility. |
The messages that may be attached on the engine are illustrated and described below.
(1) Manuals are Inside.
This message is located on the door of the box for the literature.
Illustration 3 | g00910409 |
The Operation and Maintenance Manuals are located inside this box.
(2) Permanent Magnet Exciter
These messages are located on both sides of the barrel of the generator.
Illustration 4 | g00910396 |
NOTICE |
---|
Avoid equipment damage. Disconnect and remove permanent magnet exciter stator before removing generator from engine. Refer to generator service manual for procedure. |
(3) Storage and Start-up Procedure
This message is located on the upper left side of the barrel of the generator.
Illustration 5 | g00910519 |
NOTICE |
---|
To prevent damage to generator: Storage and startup procedure Keep generator in a clean, dry place. Connect space heater. Operate space heater for a minimum of 24 hours before starting. Refer to SEHS9124 for other drying methods. Measure insulation resistance with megger before starting, following steps 1 through 14. Recommended insulation test procedure: 1. Take generator out of service. 2. Visually inspect for moisture. If moisture exists, do not megger. Dry unit first. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators" for drying procedure. 3. Inspect insulation to determine what equipment will be tested by the 142-5055 Megger . 4. Discharge the capacitance of the windings. 5. Disconnect "T0" from ground. 6. Disconnect regulator sensing lead wires (20,22,24). 7. Disconnect EMCP 3 transformer leads (T1, T2, T3). 8. Disconnect any sensing leads from switchgear or other devices. 9. Connect megger tester red "+" lead to unpainted area on generator frame. 10. Connect megger tester black "-" lead to (T0). 11. Set voltage to 500 V for generators that are 600 V or less. Set voltage to 1000 V for generators that are more than 600 V. 12. Use the 30 - 60 time resistance method. 13. Evaluate reading. See SEHS9124 for instruction. 14. Discharge leads and windings before disconnecting megger leads by switching megger to OFF. For additional information, refer to SEHS9124 in the service manual for megger testing procedure and repair procedure. |
(4) Neutral Floating
This message is located on the rear cover of the generator.
Illustration 6 | g00912573 |
Neutral is not grounded.