New Thermostats Are Used for Jacket Water Heaters on Some 3500 and C32 Engines for Electric Power Generation {1383}
- Engine:
- 3512B (S/N: S2M1-UP)
- Generator Set:
- C32 (S/N: SXC1-UP)
- Power Module:
- C32 (S/N: MED1-UP)
- 3508 (S/N: ZAB1-UP)
- 3508B (S/N: ZAD1-UP; 5KW1-UP)
- 3512 (S/N: ZAF1-UP)
- 3512B (S/N: ZAH1-UP; ZAJ1-UP; FDE1-UP; 6GW1-UP)
- 3512C (S/N: SBG1-UP)
- 3516B (S/N: FDN1-UP; PBR1-UP; 8NW1-UP)
- 3516C (S/N: SBJ1-UP)
- G3516B (S/N: ZBC1-UP)
- 3512 (S/N: BNR1-UP)
Description of Change: The new thermostats have dials for adjustment of the temperature. The former thermostat was pre-set at the factory. The new thermostats have improved accuracy and improved contact performance.
Adaptable To:
Show/hide table
Illustration 1 | g02309374 |
(1) 300-4967 Thermostat (2) 307-3274 Thermostat |
The new thermostats, the adjustable temperature ranges, and the former thermostat are listed in Table 1. The former thermostat is not canceled.
Show/hide table
New Part     | Range     | Former Part     |
300-4967     | 32.2 to 54.4° C (90 to 130° F)     |
237-4358 (1)     |
307-3274     | 48.9 to 71.1° C (120 to 160° F)     |
Show/hide table
( 1 ) | The pre-set temperature of the former thermostat is 48.9° C (120° F) |
Show/hide table
Heating Elements and Voltage Ratings     | |
---|---|
Element     | 9 KW Voltage Rating     |
307-3275 Jacket Water Heater Element     | 220 VAC     |
307-3276 Jacket Water Heater Element     | 240 VAC     |
325-6246 Jacket Water Heater Element     | 208 VAC     |
The new thermostats are effective with serial numbers that are listed in Table 3.
Show/hide table
Effectivity for the New Thermostats     |
S/N:ZAB167-UP     |
S/N:ZAD429-UP     |
S/N:ZAF761-UP     |
S/N:6GW1860-UP     |
S/N:FDE490-UP     |
S/N:S2M203-UP     |
S/N:ZAH1009-UP     |
S/N:ZAJ278-UP     |
S/N:SBG881-UP     |
S/N:8NW1139-UP     |
S/N:PBR675-UP     |
S/N:SBJ1128-UP     |
S/N:SXC5400-UP     |
S/N:ZBC215-UP     |
S/N:BNR354-UP     |
S/N:MED197-UP     |
Caterpillar Information System:
G3520E Generator Set Engines Engine Shutdown Occurs Intermittently
C9.3 Tier 4 Final Engines Exhaust Diffuser Adapter
2010/11/01 Improved Wiring Configuration for Circuit Breakers On Certain Cat Generator Sets {1408, 1420, 4459, 4461}
G3516 Power Module Voltage Regulators
G3516 Power Module Generator Operation
G3516 Power Module Parallel Operation
G3516 Power Module Emergency Stopping
G3516 Power Module Starting the Engine
G3516 Power Module Alarms and Shutoffs
G3516 Power Module Sensors and Electrical Components
725C2 Articulated Truck Engine Valve Lash - Check
G3516 Power Module Product Description
G3516 Power Module Makeup Oil Tank - Fill
PMG3516 Power Module Methane Gas Detector
G3520E Generator Set Engines Engine Overspeeds
G3512E Generator Set Engine Engine Shutdown Occurs Intermittently
G3516 Power Module Additional Messages
G3520E Generator Set Engines Generator Output Power Readings Do Not Match
G3520E Generator Set Engines Cat Data Link - Test
G3520E Generator Set Engines Detonation - Test
Instructions to Register the Retrofit and Submit Service Reporting {1000, 3000, 7000, 7570} Instructions to Register the Retrofit and Submit Service Reporting {1000, 3000, 7000, 7570}
G3520E Generator Set Engines Electrical Power Supply - Test
C15 and C18 Industrial Engines Diesel Particulate Filter
G3520E Generator Set Engines Fuel Control - Test