- Engine:
- C3.3 (S/N: N3C1-UP)
- C4.4 (S/N: D4B1-UP; N4D1-UP; N4E1-UP)
ReferenceRefer to Testing and Adjusting, RENR7902, "EMCP3" for the proper test and adjust procedures.
Description of Change: The setting for the Low Coolant Temperature (LCT) alarm will be changed from zero seconds to thirty seconds. The function that controls the LCT is varied between the number of inputs for the Electronic Modular Control Panel 3 (EMCP 3) and the priority of the inputs. The LCT will then be controlled by "Function 3" or "function 4".
Illustration 1 | g02073294 |
Typical screen shot of input function 3 (1) Event display function for the inputs (2) Input function 3 for the LCT |
Illustration 2 | g02073317 |
Typical screen shot of input function 4 (1) Event display function for the inputs (3) Input function 4 for the LCT |
Adaptable To: The new instruction for changing the event notification delay time for the LCT is adaptable to the following machines:
- C3.3 (S/N: N3C1-699)
- C4.4 (S/N: D4B1-404)
- C4.4 (S/N: N4D1-1199)
- C4.4 (S/N: N4E1-1199)
- C3.3 (S/N: N3C700-UP)
- C4.4 (S/N: D4B405-UP)
- C4.4 (S/N: N4D1200-UP)
- C4.4 (S/N: N4E1200-UP)