- Electric Power Generation:
- C2.2 GEN SET (S/N: GBE1-UP; XYE1-UP)
- C3.3 GEN SET (S/N: X3B1-UP; N3X1-UP)
- C4.4 GEN SET (S/N: XYC1-UP; XYD1-UP; GLE1-UP; N4X1-UP)
- C6.6 GEN SET (S/N: MRW1-UP)
- C3.3 GEN SET (S/N: X3B1-UP; N3X1-UP)
Introduction
This Special Instruction provides information in order to adjust the settings for the overload protection.
Important Safety Information
Do not perform any procedure in this Special Instruction until you have read this Special Instruction and you understand this information. Use only proper tools and observe all precautions that pertain to the use of those tools. Failure to follow these procedures can result in personal injury. The following procedures should also be observed.
Work safely. Most accidents that involve product operation, maintenance, and repair are caused by failure to observe basic safety rules or precautions. An accident can often be avoided by recognizing potentially hazardous situations before an accident occurs.
A person must be alert to potential hazards. This person should also have the necessary training, skills, and tools in order to perform these functions properly.
Safety precautions and warnings are provided in this instruction and on the product. If these hazard warnings are not heeded, bodily injury or death could occur to you or to other persons. Caterpillar cannot anticipate every possible circumstance that might involve a potential hazard.
Therefore, the warnings in this publication and the warnings that are on the product are not all inclusive. Ensure that any tool, procedure, work method, or operating technique you use that is not recommended by Caterpillar is safe.
Ensure that the product will not be damaged or the product will not be made unsafe by the operation, lubrication, maintenance, or repair procedures used.
When the engine is in the AUTOMATIC mode, the engine can start at any moment. To avoid personal injury, always remain clear of the the engine when the engine is in the AUTOMATIC mode. |
DANGER: Shock/Electrocution Hazard-Do not operate this equipment or work on this equipment unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings will result in serious injury or death. |
Do not connect generator to a utility electrical distribution system unless it is isolated from the system. Electrical feedback into the distribution system can occur and could cause personal injury or death. Open and secure main distribution system switch, or if the connection is permanent, install a double throw transfer switch to prevent electrical feedback. Some generators are specifically approved by a utility to run in parallel with the distribution system and isolation may not be required. Always check with your utility as to the applicable circumstances. |
Procedure
Illustration 1 | g02435456 |
- Remove the current transformers from the current positions of "T1", "T2", and "T3". Refer to Illustration 1.
- Install the current transformers "T1", "T2", and "T3" that were removed in Step 1 into the position of "T7", "T8", and "T9" respectively. Refer to Illustration 2.
For generators with the following serial numbers, use the information in ""Overload Protection Settings" " to check the relays.
- GBE1-UP
- GLE1-UP
- MRW1-UP
For generators with the following serial numbers, the dealer will need to order and install a new 334-3505 Relay prior to using the procedure in ""Overload Protection Settings" ".
- XYE1-UP
- N3X1-UP
- N4X1-UP
- X3B1-UP
- XYD1-UP
- XYC1-UP
- F4P1-UP
- RRT1-UP
- GBE1-UP
Illustration 2 | g02435457 |
Overload Protection Settings
For overload protection settings, refer to Table 1.
Switch Position     | Overload Setting     | ||||
XQ20 | XQ30     | XQ45     | XQ60     | XQ175     | |
"480V 3ph"     | 4     | 2.5     | 3.5     | 3.5     | 3.5     |
"208 3ph"     | 4.5     | 2.5     | 4     | 3.5     | 4     |
"240v 1ph"     | 4.5     | 3     | 4     | 4     | -     |
- Locate the relay for overload protection (A) .
Refer to Illustration 3.
Illustration 3 | g01889175 |
(A) Relay for Overload Protection (B) Timer |
- Adjust the overload protection relay (4). Refer to Table 1 for the proper setting for your application.
Refer to Illustration 4.
Illustration 4 | g01889174 |
(1) Ready/Run Knob (2) Relay Tripped Indicator (3) Manual/Auto Adjustment (4) Current Setting (5) Adjustment of Starting Time (6) Adjustment of Tripping Time (7) Single-Phase/3-Phase Adjustment (8) RESET Knob (9) TEST/STOP Knob (10) Retractable Fixing Lugs |
- Ensure that the "D - TIMER" (5) and the "O - TIMER" (6) are both set to "5".
Refer to Illustration 4.
Note: If you are only using the distribution panel sockets, ensure that the phase dip switch (7) is set to "lph".
- Locate the timer (B) .
Refer to Illustration 3.
- Set the knobs on the timer to the following settings. Set the "Blue Dial" (10) to "0.2". Set the "Time" (11) to "S-10". Set the "Function" (12) to "A".
Refer to Illustration 5.
Note: Reference the wiring diagram for overload protection setpoints. The settings on the wiring diagram are for the 100:5 current transformers.
Illustration 5 | g01890993 |
(10) Blue Dial (11) Time (12) Function |