UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Breaker and Contactor Status PWA

Usage:

ES12F CZE



Illustration 1g01277292

Controls Cabinet Left Panel

(17) Breaker and Contactor Status Board

(18) Remote EPO Terminal Block

(19) T8 Modem Power Transformer

(20) T6 Transformer

(21) General Purpose Interface Board

(22) Fan Power Fuse Block

(23) Fuses F29-F32

(24) Fuses F20-F22

(25) Fuses F25-F28

(26) EPO Reset

(27) Neutral Distribution Terminal

(28) K1 Motor Power Relay (K9)

The Breaker and Contactor Status Board is located in the Controls cabinet (CC) at the top of the left panel.

The Breaker and Contactor Status Board has the primary function of controlling most breakers and contactors in the UPS 1200 System. In addition, the status of all the breakers and contactors are monitored by the Breaker and Contactor Status Board.

The Breaker and Contactor Status Board receives commands from the APC2 over the Multidrop network as to which device to operate and then relays the status of that device back to the APC2.

If the Breaker and Contactor Status Board loses communication with the APC2, the Breaker and Contactor Status Board initiates a safe and controlled transfer to bypass and open the K3 and K4 contactors.

Another function of the Breaker and Contactor Status Board is Local EPO and Remote EPO control. The local, normally open EPO, input is combined with both the normally open and normally closed remote EPO signals to perform the total system EPO function. If any one of these three inputs is activated, a signal is sent out of this board to the EPO switch to remove 230VAC control power to all contactors and breakers as well as issue a shunt trip command to the input breakers thereby isolating the UPS system.

Multidrop Bus

The Breaker and Contactor Status Board provides serial data over the Series 1200 Multidrop Bus. The Breaker and Contactor Status Board functions as a slave on this bus, receiving commands from the APC-2 and responding with status information.

The Breaker and Contactor Status Board has a jumper-selectable 100 Ohm terminating resistor for the Multidrop bus. Jumper "JMP1" provides terminal resistance. There is also a switch that sets the Node ID. Set the Breaker and Contactor Status Board Node ID and terminating resistor jumper to the settings in Table 1.

Table 1
BCS Settings    
Node ID     3    
Terminating Resistor     JMP1 - Never installed    

Refer to Systems Operation, Testing and Adjusting, RENR7654, "Multidrop Network - Setup" for information on setting up the Multidrop Network.

Fuses

The type and the function of the fuses are indicated in Table 2. Visually inspect the fuses and replace if the fuse is blown.

Table 2
Breaker and Contactor Status Board Fuses    
Fuse     Type    
BCS-F2     250VAC 5A Time Lag    
BCS-F3     250VAC 5A Time Lag    
BCS-F4     250VAC 5A Time Lag    
BCS-F5     250VAC 5A Time Lag    
BCS-F6     250VAC 5A Time Lag    
BCS-F7     250VAC 5A Time Lag    
BCS-F8     250VAC 5A Time Lag    
BCS-F9     250VAC 5A Fast    
BCS-F10     250VAC 5A Fast    
BCS-F11     250VAC 5A Time Lag    
BCS-F12     250VAC 5A Time Lag    

Breaker and Contactor Status Board Diagram - Version 1 Hardware




Illustration 2g01277586

Breaker and Contactor Status Board - Version 1 (BCS1)

Breaker and Contactor Status Board Diagram - Version 2 Hardware




Illustration 3g01277587

Breaker and Contactor Status Board - Version 2 (BCS2)

LED Indicators

Table 3
Breaker and Contactor Status Board LED Indicators    
LED     Board Designation     Purpose    
1     D1     K1 Status    
2     D2     Bypass SS Status    
3     D3     K3 Status    
4     D4     K4 Status    
Datalock     D5     Datalock with APC    
    D24     K3 Command    
    D25     K4 Command    
    D26     K6 Command    
    D27     K7 Command    
    D28     K1 Close Command (1)    
    D29     Not Used    
( 1 ) Cycles until closed.

Removal

  1. Perform steps in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Controls Cabinet)" in order to de-energize the system and gain access to internal components.


    NOTICE

    Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. When not in use, keep the module in the static-shield bag. Follow these guidelines when you handle any module:

    Touch a grounded object to discharge static potential.

    Wear an approved wrist-strap grounding device.

    Do not touch the bus connector or connector pins.

    Do not touch circuit components inside the module.

    If available, use a static-safe work station.


  1. Disconnect all connectors from the board. The connectors locations in the unit are labeled. Verify each connector to make sure that the label is present and legible.

    Refer to Illustration 2.

  1. Fasten the cross tip screw that is located at the bottom right of the board.

  1. Disconnect the seven white plastic stand-offs connecting the board to the left panel using the following method.

    Note: The board must be removed from the stand-offs without bending the board.

    1. Pinch the head of each stand-off so that the board is not locked to the stand-off but is still attached to the stand-off.

    1. Remove the board by gently and evenly pulling the board from all stand-offs at the same time.

Installation


NOTICE

Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. When not in use, keep the module in the static-shield bag. Follow these guidelines when you handle any module:

Touch a grounded object to discharge static potential.

Wear an approved wrist-strap grounding device.

Do not touch the bus connector or connector pins.

Do not touch circuit components inside the module.

If available, use a static-safe work station.


  1. Position the board in the cabinet over the seven white stand-offs that are connected to the left panel.

  1. Push the board, gently and evenly, onto all the stand-offs simultaneously. Make sure all stand-offs are locked in place.

  1. Screw the cross tip screw into the bottom right of the board in the hole labeled "J2".

  1. Plug the wire connectors into the correct connectors on the board. Check the labels on each connector for proper placement.

    Refer to Figure 2.

Caterpillar Information System:

UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Vacuum Pump
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Flywheel Interface PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Vacuum Gauge
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Rotor Position Sensor Assembly
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Flywheel Assembly
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies SKiiP Interface PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Utility Inverter Assembly
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Fuse (Controls Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Flywheel Inverter Assembly
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (Controls Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Field Coil Driver
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies DC Interface PWA
793F and 797F Off-Highway Trucks Braking System Service Tools
Proper Oil Changing Procedures {1000, 1308, 1316, 1325, 1348, 3000, 3004, 3005, 3030, 3064, 3067, 3080, 3081, 4000, 4001, 4050, 4051, 5050, 5056, 5068, 5095} Proper Oil Changing Procedures {1000, 1308, 1316, 1325, 1348, 3000, 3004, 3005, 3030, 3064, 3067, 3080, 3081, 4000, 4001, 4050, 4051, 5050, 5056, 5068, 5095}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T6)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Purpose Interface PWA (Controls Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Relay (Control Power Switch)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys EPO/EMO Reset Switch
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Modem Power Transformer (T8)
Proper Grounding for the 161-0797 Governor Control As {1264, 1408} Proper Grounding for the 161-0797 Governor Control As {1264, 1408}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Precharge Contactor (K6, K7)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Precharge Resistor
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Precharge Zig Zag Transformer
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T1 to T4)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.