Electronic Modular Control Panel II (EMCP II) For PEEC Engines Caterpillar


SP Fault Code - Troubleshoot

Usage:

3412 2WJ



Illustration 1g00515355

Upper Display With SP Fault Code SP1 Showing




Illustration 2g00598329

System Schematic For Spare Fault Inputs

A spare fault informs the operator of an undesirable condition (fault) that exists. The spare inputs are programmed into the GSC to meet the requirements of the customer or application. An active spare input causes an alarm fault or a shutdown fault. For programming of the spare inputs, see Systems Operation, "Spare Input/Output Programming OP6". The programmer (customer, operator, or service personnel) is responsible for noting the actual conditions that cause a SP fault code. The GSC does not diagnose the spare inputs and spare faults are not recorded in the fault log.

The GSC treats an active input state as a fault. The active state is programmable on the GSC to be either a high or a low (factory default) voltage level. A high level is within the range of +5 DCV to the positive battery. If the input is left floating (for example an open switch), the GSC pulls the input voltage up to 10.5 DCV and the input is treated as high level. A low level on the input is B- (ground).

When a spare fault occurs (active), the GSC determines the type of fault (alarm or shutdown). The GSC also FLASHES the corresponding fault alarm indicator or fault shutdown indicator. For a shutdown type of fault, the SP fault code is immediately shown on the upper display. For an alarm type of fault, the alarm code key is pressed first. Then the SP fault code is shown on the upper display. After a spare fault is corrected or is not present, the SP fault code is no longer shown on the upper display.

Table 1
Spare Fault Codes    
Spare Fault Code     GSC Connector Contact     Terminal Strip     Related Setpoints (1)    
SP1 Spare Fault 1     23     SP1     SP01, SP02, SP08    
SP2 Spare Fault 2     24     SP2     SP03, SP04, SP09    
SP3 Spare Fault 3     25     SP3     SP05, SP06, SP10    
( 1 ) See Spare Input/Output Programming OP6 within the topic Service Mode in the Systems Operation section.

SP fault codes are associated with the spare inputs. The SP fault code that is shown on the upper display, identifies the spare input that caused the alarm fault or shutdown fault. The spare inputs are accessed on the terminal strip within the control panel on the rear wall.

When a SP fault code is showing on the upper display, check the programming notes in order to determine the cause.

The spare fault inputs can be used with options that are installed by the factory and/or the customer. The following list contains the factory options for the spare fault inputs:

  • ground fault

  • low fuel level

  • high fuel level

  • high generator winding temperature

  • high generator bearing temperature

Each of these options will include a dedicated indicator and a label on the custom alarm module.

Troubleshooting Procedure

To troubleshoot spare faults, use this general procedure.

  1. Check for obvious causes that are related to the device that is responsible for the spare fault.

  1. Verify that the programming of the spare fault (alarm or shutdown) is appropriate for the application.

  1. Check the function of the responsible device. Reset the fault by turning the ECS to the OFF/RESET position. Verify that the fault is still present.

  1. Disconnect the device that is responsible from the spare fault input. Verify that the fault still exists.

  1. Check the wiring to the corresponding spare fault input for an unwanted short to either battery negative (B-) or battery positive (B+).

Caterpillar Information System:

3500B Engines and 3500 Engines with EUI Option Ether Injection System
3003, 3013, 3014 and 3024 Engines for Caterpillar Built Machines Rocker Shaft - Disassemble - 3003 Engines
3064 and 3066 Engines for Caterpillar Built Machines Camshaft Gear - Remove and Install
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 566 FMI 7 Unexpected Shutdown Improper Mechanical Response - Test
G3500 Engines Cylinder Head - Assemble
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 560 FMI 11 CAT Data Link Failure Mode Not Identified - Test
G3516B and G3520B Generator Set Engines Air Starting Motor - Assemble
3126B Marine Engine Electric Starting Motor
3500B Engines and 3500 Engines with EUI Option Prelubrication System
3126B Marine Engine Electric Starting Motor
3126B Marine Engine Electric Starting Motor
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 447 FMI 12 Fuel Control Relay Failed - Test
Electronic Modular Control Panel II (EMCP II) For MUI Engines AL Fault Code - Troubleshoot
Electronic Modular Control Panel II (EMCP II) For MUI Engines Troubleshooting Dedicated Shutdown Indicators
G3606 and G3608 Engines Camshaft Speed Sensor - Remove and Install
3034 Engine for Caterpillar Built Machines Water Temperature Regulator - Remove and Install
Electronic Modular Control Panel II (EMCP II) For MUI Engines Indicator for Low Oil Pressure - Troubleshoot
3114, 3116 and 3126 Industrial, Marine and Generator Set Engines Flywheel
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Indicator for Emergency Stop - Troubleshoot
G3606 and G3608 Engines Caterpillar Ignition System (CIS) Module - Remove and Install
Electronic Modular Control Panel II (EMCP II) For MUI Engines Indicator for High Water Temperature - Troubleshoot
G3606 and G3608 Engines Actuator (Hydrax) - Disassemble
Electronic Modular Control Panel II (EMCP II) For MUI Engines Indicator for Low Coolant Level - Troubleshoot
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Indicator for Overcrank - Troubleshoot
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.