Electronic Modular Control Panel II (EMCP II) For PEEC Engines Caterpillar


CID 447 FMI 12 Fuel Control Relay Failed - Test

Usage:

3412 2WJ



Illustration 1g00598138

Schematic For Fuel Control Relay

The status of the FCR has no effect on the PEEC engine. The contacts are not used in applications of the PEEC electronic control module. However, the GSC still activates the FCR during normal running of the engine. The contacts for the fuel control relay (FCR) are available for use by the customer. The FCR is located within the relay module.

Note: Whenever the GSC activates the FCR, "K7" is shown on the lower display. "K7" is also shown when the GSC attempts to activate the FCR. When the FCR is not activated, "K7" is not shown.

Procedure

The possible cause of this diagnostic code is an open coil or a shorted coil of the FCR.

The following response is the system response to this fault while the engine is running:

  • If a CID 447 occurs, then any equipment that is connected to RM-4 and RM-15 is deactivated.

The following response is the system response to this fault while the engine is NOT running:

  • If a CID 447 occurs, then any equipment that is connected to RM-4 and RM-15 will remain deactivated.

The GSC treats this diagnostic code as an alarm fault. Active alarm faults are shown on the display when the alarm codes key is pressed. Also, the active alarm faults are shown when the ECS is in any position except the OFF/RESET position. Clear the diagnostic code from the fault log after troubleshooting is complete.

  1. Check the status of the diagnostic code (Active/Inactive).

    1. Turn the ECS to OFF/RESET and then turn the ECS to STOP.

    1. Press the alarm codes key.

    1. Observe the upper display. Check that a CID 447 FMI 12 is showing.

    1. If the diagnostic code is not showing, enter the service mode. View the fault log (OP1). Check that the diagnostic code is showing.

      Expected Result: A CID 447 FMI 12 is showing as a active fault or an inactive fault.

      Results:

      • No - A CID 447 FMI 12 has not occurred (NOT active and NOT inactive). STOP.

      • Yes - A CID 447 FMI 12 is active or inactive. Proceed to 2.

  1. Check internal cable of relay module.

    Note: Only open the relay module in a dry environment. If the inspection takes more than twenty minutes replace the desiccant bag in the GSC housing. See Testing And Adjusting, "Relay Module - Replace".

    1. Turn the ECS to OFF/RESET.

    1. Temporarily, remove the relay module from the GSC. See Testing And Adjusting, "Relay Module Replace".

    1. Check the cable that attaches the relay module to the GSC.

      Expected Result: The cable should be firmly seated in the connector. The clamp should be in place. The cable should not be damaged.

      Results:

      • OK - Reassemble the relay module to the GSC. Proceed to 3.

      • NOT OK - Replace the connector clamp if it is missing. If the cable is damaged, replace the GSC. STOP.

  1. Perform a functional check for the ASR.

    1. Turn the ECS to OFF/RESET.

    1. Disconnect all wires from RM-15 of the relay module.

    1. At the relay module, measure the resistance from RM-15 to RM-4. Resistance should be greater than 5000 ohms.

    1. Turn the ECS to the START position. Make sure that "K7" is showing in the lower display.

    1. At the relay module, measure the resistance from RM-15 to RM-4. Resistance should be less than 5 ohms.

      Expected Result: For 3.c, the resistance should be greater than 5000 ohms. For 3.e, the resistance should be less than 5 ohms.

      Results:

      • OK - It is likely that a temporary bad electrical connection existed and this troubleshooting procedure corrected it. Check the electrical connectors, terminals and wiring. See Testing And Adjusting, "Electrical Connector - Inspect". STOP.

      • NOT OK - Either one of the resistance measurements are NOT correct. The relay module is faulty. Replace the relay module. See Testing And Adjusting, "Relay Module - Replace". STOP.

Caterpillar Information System:

G3500 Engines Cylinder Head - Disassemble
3126B Marine Engine Electric Starting Motor
G3500 Engines Service Meter - Remove and Install
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 446 FMI 12 Air Shutoff Relay Failed - Test
G3500 Engines Fuel Control Valve - Remove and Install
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 445 FMI 12 Run Relay Failed - Test
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 444 FMI 12 Starting Motor Relay Failed - Test
3114, 3116 and 3126 Industrial, Marine and Generator Set Engines Balancer Group - 3114 Engine Only
G3500 Engines Gas Pressure Regulator - Assemble
3126B Marine Engine Alternator and Regulator
G3500 Engines Gas Pressure Regulator - Disassemble
3126B Marine Engine Alternator and Regulator
3126B Marine Engine Electric Starting Motor
3126B Marine Engine Electric Starting Motor
3500B Engines and 3500 Engines with EUI Option Prelubrication System
3126B Marine Engine Electric Starting Motor
G3516B and G3520B Generator Set Engines Air Starting Motor - Assemble
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 560 FMI 11 CAT Data Link Failure Mode Not Identified - Test
G3500 Engines Cylinder Head - Assemble
Electronic Modular Control Panel II (EMCP II) For PEEC Engines CID 566 FMI 7 Unexpected Shutdown Improper Mechanical Response - Test
3064 and 3066 Engines for Caterpillar Built Machines Camshaft Gear - Remove and Install
3003, 3013, 3014 and 3024 Engines for Caterpillar Built Machines Rocker Shaft - Disassemble - 3003 Engines
3500B Engines and 3500 Engines with EUI Option Ether Injection System