CID 0821 FMI 03 Display Power Supply Voltage Above Normal - Test

Usage:

3412C 4BZ



Illustration 1g00565164

This diagnostic code is recorded when the main display module reads the voltage of the display power supply circuit as above normal. Normal display power supply voltage is 9.0 ± 0.5 DCV. The schematic that is shown above represents a typical installation of the component. Verify the connector contact and wire numbers by using the Electrical System Schematic for the engine that is being serviced.

  1. Check The Voltage At The Main Display Module.

    1. Turn the "ECS" switch to the COOLDOWN/STOP position.

    1. Use the 7X-1710 Multimeter Probe Group. Check the voltage at the connector for the main display module. Measure the voltage from the contact 34 to contact 2 (ground).

    1. DO NOT disconnect the harness from the Main Display Module.

    1. The correct voltage should measure 9.0 ± 0.5 DCV.

      Expected Results: The voltage that is measured is 9.0 ± 0.5 DCV.

      Results:

      • OK: The voltage is 9.0 ± 0.5 DCV. The display power supply voltage is correct. Check the main display module for the same diagnostic code. If the service code indicator is still ON, the main display module is faulty. Replace the module. See Testing and Adjusting, "Module - Replace". STOP.

      • NOT OK: The voltage is NOT 9.0 ± 0.5 DCV. The display power supply voltage is NOT correct. Proceed to Step 2.

  1. Check The Harness For A Short To The +Battery.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Disconnect the engine harness from the main display module.

    1. At the engine harness connector for the Main Display Module, measure the voltage from the connector Contact 34 to Contact 2 (ground).

      Expected Result: The voltage that is measured is 0.0 ± 0.5 DCV.

      Results:

      • OK: The voltage is 0.0 ± 0.5 DCV. The voltage is correct. The main display module is faulty. Replace the module. See Testing and Adjusting, "Module - Replace". STOP.

      • NOT OK: The voltage is NOT 0.0 ± 0.5 DCV. The harness is faulty. Repair the harness or replace the harness. STOP.

Caterpillar Information System:

797 Off-Highway Truck Power Train Relief Valve (Torque Converter Inlet)
Generator Set Control Panel for Switchgear Conversion CID 0819 FMI 02 Display Data Link Incorrect - Test
Generator Set Control Panel for Switchgear Conversion CID 0460 FMI 08 Pressure Sensor (Fuel) Abnormal Signal - Test
Generator Set Control Panel for Switchgear Conversion CID 0248 FMI 02 CAT Data Link Incorrect - Test
Generator Set Control Panel for Switchgear Conversion CID 0175 FMI 08 Temperature Sensor (Engine Oil) Abnormal Signal - Test
G3606 and G3608 Engines Valve Mechanism - Remove
Electric Protection System Energize-To-Shutoff (ETS) For Generator Set, Industrial and Marine Diesel Engines Troubleshooting the ETS Partial Protection System (OP, WT) - 3200-3400 Engines
Generator Set Control Panel for Switchgear Conversion CID 0172 FMI 04 Temperature Sender (Inlet Air) Voltage Below Normal - Test
Generator Set Control Panel for Switchgear Conversion CID 0110 FMI 08 Temperature Sensor (Engine Coolant) Abnormal Signal - Test
G3606 and G3608 Engines Rocker Arm - Install
G3606 and G3608 Engines Rocker Arm - Remove
Generator Set Control Panel for Switchgear Conversion CID 0102 FMI 08 Pressure Sensor (Boost) Abnormal Signal - Test
G3606 and G3608 Engines Valve Mechanism - Install
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines General Troubleshooting Information
Generator Set Control Panel for Switchgear Conversion CID 0821 FMI 04 Display Power Supply Voltage Below Normal - Test
3412E, C30 and C32 Marine Engines Alternator - Remove and Install
797 Off-Highway Truck Power Train Relief Valve (Torque Converter Outlet)
Generator Set Control Panel for Switchgear Conversion CID 0827 FMI 08 Temperature Sensor (Left Exhaust) Abnormal Signal - Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Electric Protection System Functional Test
Generator Set Control Panel for Switchgear Conversion CID 0828 FMI 08 Temperature Sensor (Right Exhaust) Abnormal Signal - Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Overspeed Verification Test
3500B High Displacement Generator Set Engines Air Starting Motor - Inspect
3500B and 3500 Marine Propulsion Engines with EUI Option Electric Starting Motor - Inspect
3508B, 3512B, and 3516B High Displacement Generator Sets Prelube Pump - Inspect
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.