Note: If you change a parameter, you must exit the parameter before the change of the parameter will take effect.
- Check the wiring.
- Stop the generator set.
- Check the wiring.
Expected Result: The wiring is correct.
Results:
- OK: Go to Step 2.
- NOT OK: The CT polarity or PT polarity is incorrect. Reverse the polarity. See the proper wiring diagram for details. Refer to Testing And Adjusting, "Wiring Diagrams". STOP.
- Check the parameter values.
- Start the generator set and load with 25% to 50% of rated load. Use 0.8 power factor inductive load, if at all possible.
- Check the values in parameters :04 and :05.
Note: Parameter :52 (current) provides the measured value of the current in the B phase only.
- Measure the ampere load on the B phase.
- Measure the signal voltage level at regulator terminals 5 and 6.
- Verify that it is in correct proportion to load amperes and agrees with the settings of parameters :04 and :05.
Expected Result: Any parameters show negative numbers.
Results:
- OK: If any parameters show negative numbers, a CT or PT polarity is incorrect or the phase rotation is wrong. Verify the polarity and the rotation. STOP.
- NOT OK: Go to Step 3.
- Check the value of the generator output current.
- Compare the value of parameter :52 to the actual generator current.
Expected Result: Parameter :52 reads less than the actual generator current, which was measured by another meter.
Results:
- OK: Parameter :52 reads less than the actual generator current, which was measured by another meter. Slowly decrease parameter :05 until the currents match.
- NOT OK: Parameter :52 reads more than the actual generator current which is measured by another meter. Slowly increase parameter :05 until the currents match.
Note: If the generator set neutral is connected to ground or a neutral bus, then measure the neutral current. If a significant amount of circulating current is present, it may cause incorrect readings. A harmonic analysis is recommended in order to help determine the nature of the problem.
Note: It is normal for the accuracy to be reduced at levels below 15% of rated load. The digital voltage regulator is sensitive to the size of CT. The droop current transformer should be sized in order to provide no more than 5 VAC (RMS) at full rated load but not less than 3.5 VAC either. Proper sizing will significantly aid the accuracy at lower power levels.
- Compare the value of parameter :52 to the actual generator current.