CID 0821 FMI 04 Display Power Supply Voltage Below Normal - Test

Usage:

3516B 1NW



Illustration 1g00573982

Schematic For The Display Power Supply.

(1) Locomotive Engines - A304-RD: Marine Engines and Generator Set Engines - 049-OR.

This diagnostic code is recorded when the Main Display Module reads the voltage of contact 34 below normal or the voltage is shorted to ground. Normal supply voltage is 9.0 ± 0.5 DCV.

  1. Measure the Voltage at the Main Display Module.

    1. Turn the "ECS" switch to the COOLDOWN/STOP position.

    1. Use the 7X-1710 Multimeter Probe to measure the voltage at the connector for the Main Display Module. The voltage should be measured from contact 34 to contact 2.

    1. Do NOT disconnect the harness from the Main Display Module.

      Expected Result: The voltage should measure 9.0 ± 0.5.

      Results:

      • OK - The voltage is correct. If the FMI 04 diagnostic code is still active, the Main Display Module has a problem. Replace the Main Display Module. For more information on this subject, see Testing And Adjusting, "Module - Replace".

      • Not OK - The voltage is not correct. The Display Power Supply has a problem. Proceed to Step 2.

  1. Disconnect the Quad Gauge Cluster Modules.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Disconnect the Quad Gauge Cluster Modules.

    1. Turn the ECS switch to the COOLDOWN/STOP position.

    1. At the engine harness connector for the Main Display Module, measure the voltage from connector contact 34 to connector contact 2 (ground).

    1. Reconnect the Quad Gauge Cluster Modules one at a time. Between reconnecting the Modules, record the voltage of the display power supply.

      Expected Result: The voltage should be 9.0 ± 0.5 DCV after each of the Quad Gauge Cluster Modules have been reconnected.

      Results:

      • OK - The voltage is correct. The Display Power Supply is correct. Proceed to Step 3.

      • Not OK - The voltage is not correct after reconnecting one of the Quad Gauge Cluster Modules. The Quad Gauge Cluster Module that affected the voltage has a problem. Replace the Quad Gauge Cluster Module. For more information on this subject, see Testing And Adjusting, "Module - Replace"STOP.

  1. Check for a Short to Ground.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Disconnect the machine harness from the main display module.

    1. At the machine harness connector for the Main Display Module, measure the resistance between connector contact 34 and connector contact 2.

      Expected Results: The resistance should be greater than 5000 ohms.

      Results:

      • OK - The resistance of the harness circuit is correct. The Main Display Module is faulty. Replace the Main Display Module. See Testing And Adjusting, "Module - Replace".

      • Not OK - The resistance of the harness circuit is incorrect. The machine harness is faulty. Repair the harness or replace the harness.

Caterpillar Information System:

3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0821 FMI 03 Display Power Supply Voltage Above Normal - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0819 FMI 02 Display Data Link Incorrect - Test
3606 and 3608 Engines Vibration Damper - Dual
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0271 FMI 06 Alarm (Action) Current Above Normal - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0271 FMI 05 Alarm (Action) Current Below Normal - Test
C-10 and C-12 Industrial Engines Engine Oil Cooler
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0271 FMI 03 Alarm (Action) Voltage Above Normal - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0263 FMI 04 Sensor Power Supply Voltage Below Normal - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0263 FMI 03 Sensor Power Supply Voltage Above Normal - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0248 FMI 02 Cat Data Link Incorrect - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0177 FMI 08 Temperature Sensor (Transmission Oil) Abnormal Signal - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System CID 0175 FMI 04 Temperature Sender (Engine Oil) Voltage Below Normal - Test
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System Alert Indicator - Troubleshoot
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System LH/RH Switch - Troubleshoot
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System Scroll Switch - Troubleshoot
G3408 and G3412 Engines Engine Oil Filter Base
3176C and 3196 Marine Engines Engine Oil Cooler
3606 and 3608 Engines Vibration Damper - Single
G3408 and G3412 Engines Crankshaft
3612 and 3616 Engines Stub Shaft (Front)
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System Clear/Mode Switch - Troubleshoot
3612 and 3616 Engines Stub Shaft (Front)
3606 and 3608 Engines Stub Shaft (Front)
3508, 3508B, 3508C, 3512, 3512B, 3512C, 3516, 3516B and 3516C Engines Caterpillar Monitoring System Alarm Silence Switch - Troubleshoot
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.