Service Record
Show/hide table
SERVICE TABLE - RECORD OF SETPOINT VALUES     | |||||
---|---|---|---|---|---|
Generator Description: Site, Serial No., EMCP II Model No., etc.     | |||||
Setpoint     | Specified Value     | Actual Value (1)     | Setpoint Description     | Possible Values     | Default Value     |
Setpoint Programming - OP5     | |||||
P01     |     |     | Fuel Solenoid Type     | 0 = ETR, 1 = ETS     | 0     |
P02     |     |     | Units Shown     | 0 = Eng, 1 = metric     | 0     |
P03     |     |     | Shutdown Override For Engine Fault     | 0 = shutdown, 1 = alarm     | 0     |
P04     |     |     | Shutdown Override For Sensor Fault     | 0 = alarm, 1 = shutdown     | 0     |
P05     |     |     | Coolant Loss Sensor     | 0 = w/o sensor, 1 = w/sensor     |     |
P06     |     |     | Shutdown Override For Coolant Loss Fault     | 0 = shutdown, 1 = alarm     | 0     |
P07     |     |     | System Voltage     | 0 = 24 volts, 1 = 32 volts     | 0     |
P08     |     |     | Upper Display     | 0 = enable, 1 = disable     | 0     |
P09     |     |     | Ring Gear Teeth     | 95 to 350 teeth     | 136 teeth     |
P10     |     |     | Engine Overspeed     | 500 to 4330 rpm     | 2120 rpm     |
P11     |     |     | Crank Terminate Speed     | 100 to 1000 rpm     | 400 rpm     |
P12     |     |     | Oil Step Speed     | 400 to 1800 rpm     | 1350 rpm     |
P13     |     |     | Low Oil Pressure Shutdown At Rated Speed     | 34 to 420 kPa (5 to 60 psi)     |
205 kPa (30 psi)     |
P14     |     |     | Low Oil Pressure Shutdown At Idle Speed     | 20 to 336 kPa (3 to 50 psi)     |
70 kPa (10 psi)     |
P15     |     |     | High Water Temperature Shutdown     | 94 to 123°C (201 to 253°F)     |
107°C (225°F)     |
P16     |     |     | Low Water Temperature Alarm     | 0 to 36°C (32 to 97°F)     |
21°C (70°F)     |
P17     |     |     | Total Cycle Crank Time     | 5 to 120 seconds     | 90 seconds     |
P18     |     |     | Cycle Crank Time     | 5 to 60 seconds     | 10 seconds     |
P19     |     |     | Cooldown Time     | 0 to 30 minutes     | 5 minutes     |
P20     |     |     | AC Voltage Full Scale     | 150 V to 18000 V     | 700 V     |
P21     |     |     | AC Current Full Scale     | 75 A to 40000 A     | 600 A     |
P22     |     |     | GSC Engine Number     | 01 to 08     | 01     |
P23     |     |     | Engine Type     | 0 = MUI diesel, 1 = spark ignited, 2 = EUI diesel     | 0     |
P24     |     |     | Crank Time Delay     | 0 to 20 seconds     | 5 seconds     |
Spare Input/Output Programming - OP6     | |||||
SP01     |     |     | Spare Fault 1 Active State     | 0 = Low, 1 = High     | 0     |
SP02     |     |     | Spare Fault 1 Response     | 0 = Shutdown, 1 = Alarm     | 0     |
SP03     |     |     | Spare Fault 2 Active State     | 0 = Low, 1 = High     | 0     |
SP04     |     |     | Spare Fault     | 0 = Shutdown, 1 = Alarm     | 0     |
SP05     |     |     | Spare Fault     | 0 = Low, 1 = High     | 0     |
SP06     |     |     | Spare Fault     | 0 = Shutdown, 1 = Alarm     | 0     |
SP07     |     |     | Spare Output Active State     | 0 = Low, 1 = High     | 0     |
SP08     |     |     | Spare Fault 1 Delay Time     | 0 to 250 seconds     | 0 seconds     |
SP09     |     |     | Spare Fault 2 Delay Time     | 0 to 250 seconds     | 0 seconds     |
SP10     |     |     | Spare Fault 3 Delay Time     | 0 to 250 seconds     | 0 seconds     |
SP11     |     |     | Spare Output Response     | See Service Manual     | 7 = cooldown     |
Voltmeter/Ammeter Programming - OP8     | |||||
AC01     |     |     | A-B Voltage Calibration     | 0 to 255     | NA (2)     |
AC02     |     |     | B-C Voltage Calibration     | 0 to 255     | (2)     |
AC03     |     |     | C-A Voltage Calibration     | 0 to 255     | (2)     |
AC04     |     |     | A Current Calibration     | 0 to 255     | (2)     |
AC05     |     |     | B Current Calibration     | 0 to 255     | (2)     |
AC06     |     |     | C Current Calibration     | 0 to 255     | (2)     |
Show/hide table
( 1 ) | The actual value space is provided for recording and comparing values during future servicing or troubleshooting of the particular genset. |
( 2 ) | The default value is not applicable (NA). A random value is assigned to the setpoint when a GSC internal memory fault (CID 268 0 occurs. |
This table provides a record of setpoint values for a singular genset. The table is intended to be an easy reference for future servicing or troubleshooting of a particular genset.
Caterpillar Information System:
G3612 and G3616 Engines Engine Supervisory System
3306B Industrial Engine Fuel Injection Lines
3306B Industrial Engine Alternator - Remove and Install
3306B Industrial Engine Electric Starting Motor - Remove and Install
3306B Industrial Engine Troubleshooting
3304B and 3306B Engines for Caterpillar Built Machines Inlet and Exhaust Valve Seat Inserts - Remove and Install
3306B Industrial Engine Fuel Ratio Control
3304B and 3306B Engines for Caterpillar Built Machines Inlet and Exhaust Valve Guides - Remove and Install
G3612 and G3616 Engines Engine Timing Procedures
C-10 and C-12 Truck Engines Rear Power Take-Off (RPTO)
G3612 and G3616 Engines Governor Adjustment Procedure
3406C (PEEC III) Truck Engine Engine Support (Front)
G3612 and G3616 Engines Ignition System
3406C (PEEC III) Truck Engine Manual Shutoff
3306B Industrial Engine Gear Group (Front)
3306B Industrial Engine Fuel System
3406C (PEEC III) Truck Engine Governor and Fuel Pump Drive
3406C (PEEC III) Truck Engine Timing Position Sensor and Timing Solenoid (BTM)
3406C (PEEC III) Truck Engine Fuel Rack Controls
3406E Truck Engines Engine Design
Electronic Modular Control Panel II (EMCP II) For MUI Engines General Information
3406E Truck Engine Valve Mechanism
Electronic Modular Control Panel II (EMCP II) General Information
3304B and 3306B Engines for Caterpillar Built Machines Coolant Temperature Sensor - Remove and Install