5N-8891 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3.4(3,4,3,4,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 10 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 37.4 kg (82.5 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0118 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).
5N-8892 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 2.4(2,3,2,3,2)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1226.8 mm (48.3 inch)     |
-     | -     | |
Copper Weight     | 39.9 kg (88.1 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0053 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.4 kg (9.8 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8893 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 2.8(3,3,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 10 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 39.9 kg (88.0 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #14     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0077 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8894 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 2.8(3,3,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 10 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 39.9 kg (88.0 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #14     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0077 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8895 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 2.8(3,3,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 10 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 39.9 kg (88.0 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #14     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0077 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8896 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 2.4(2,3,2,3,2)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1226.8 mm (48.3 inch)     |
-     | -     | |
Copper Weight     | 39.9 kg (88.1 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0053 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.4 kg (9.8 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8897 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 2.8(3,3,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 10 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 39.9 kg (88.0 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #14     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0077 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8898 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
292.1 mm (11.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3.4(3,4,3,4,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 10 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 37.4 kg (82.5 lb)     |
41.7 kg (91.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0122 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.760 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).
5N-8899 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 11 - #13     | 1 - #7     | -     | |
Mean Length Turn     | 1399.5 mm (55.1 inch)     |
-     | -     | |
Copper Weight     | 43.9 kg (96.8 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0043 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.4 kg (9.8 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8900 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 2.4(2,2,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1348.7 mm (53.1 inch)     |
-     | -     | |
Copper Weight     | 45.2 kg (99.7 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0057 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8901 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1348.7 mm (53.1 inch)     |
-     | -     | |
Copper Weight     | 43.6 kg (96.1 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0091 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).
5N-8902 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 2.4(2,2,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1348.7 mm (53.1 inch)     |
-     | -     | |
Copper Weight     | 45.2 kg (99.7 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0057 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8903 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 2.4(2,2,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1348.7 mm (53.1 inch)     |
-     | -     | |
Copper Weight     | 45.2 kg (99.7 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0057 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8904 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 11 - #13     | 1 - #7     | -     | |
Mean Length Turn     | 1399.5 mm (55.1 inch)     |
-     | -     | |
Copper Weight     | 43.9 kg (96.8 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0043 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.4 kg (9.8 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8905 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 2.4(2,2,2,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1348.7 mm (53.1 inch)     |
-     | -     | |
Copper Weight     | 45.2 kg (99.7 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0057 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8906 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 330.2 mm (13.0 inch)     |
330.2 mm (13.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 12 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1348.7 mm (53.1 inch)     |
-     | -     | |
Copper Weight     | 43.6 kg (96.1 lb)     |
44.9 kg (98.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0091 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.820 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).
5N-8908 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 381.0 mm (15.0 inch)     |
381.0 mm (15.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 1.8(2,2,1,2,2)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 15 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1465.6 mm (57.7 inch)     |
-     | -     | |
Copper Weight     | 45.9 kg (101.1 lb)     |
49.1 kg (108.3 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0042 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.895 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.4 kg (9.8 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8909 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 381.0 mm (15.0 inch)     |
381.0 mm (15.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 14 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1503.7 mm (59.2 inch)     |
-     | -     | |
Copper Weight     | 49.2 kg (108.5 lb)     |
49.1 kg (108.3 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0048 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.895 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-8910 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 381.0 mm (15.0 inch)     |
381.0 mm (15.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 2.6(2,2,3,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 13 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1452.9 mm (57.2 inch)     |
-     | -     | |
Copper Weight     | 45.5 kg (100.4 lb)     |
49.1 kg (108.3 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0081 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.895 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).
5N-8911 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 381.0 mm (15.0 inch)     |
381.0 mm (15.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 1.8(2,2,1,2,2)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 15 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1465.6 mm (57.7 inch)     |
-     | -     | |
Copper Weight     | 45.9 kg (101.1 lb)     |
49.1 kg (108.3 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0042 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.895 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.4 kg (9.8 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3000 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |