Usage:
Three Phase
The connections for both high and low voltage are given in the following diagrams.
TYPICAL LOW VOLTAGE CONNECTION
The terminals must be connected securely and insulated with a good quality electrical tape.
TYPICAL HIGH VOLTAGE CONNECTION
Single Phase Current From A Three-Phase Generator
Three phase and single phase current can be taken simultaneously from a generator connected for three phase service. Connecting the load to any two of the three phase leads will provide single phase voltage at the same voltage as three phase power. Connecting the load to any phase lead and to neutral will produce voltage at 58% of the three phase voltage. DO NOT exceed the nameplate current rating for any one phase.
Single phase power taken from a three phase source can be a problem unless the single phase loading is equally distributed.