Introduction
This Special Instruction contains the necessary information for configuring the touchscreen IP addresses on certain UPS models.
Note: When working to address issues with the UPS touchscreen, always disconnect from any networks external to the UPS. This precaution will enable isolation of UPS to avoid potential conflicts from external sources. Isolating the UPS from external networks will also assist when trouble shooting such errors as: incorrect information on the display, no information on the display, and display not found.
Do not perform any procedure in this Special Instruction until you have read and understood the information in the entire Special Instruction.
Important Safety Information
Work safely. Most accidents involving product operation, maintenance, and repairs, are caused by failure to observe basic safety rules or precautions. Accidents can often be avoided by recognizing potentially hazardous situations before the accident occurs.
A person must be alert to potential hazards. This person should also have the necessary training, skills, and tools, to perform these functions properly.
Safety precautions and warnings are provided in this instruction and on the product. If any hazard warning is not heeded, bodily injury or death can occur to you, or to other persons. Caterpillar cannot anticipate every possible circumstance that might involve a potential hazard. The warnings in this publication, and the warnings that are on the product, are not all inclusive.
Ensure that any tool, procedure, work method, or operating technique you use that is not recommended by Caterpillar is safe.
Ensure that the product will not be damaged, or made unsafe, by the operation, lubrication, maintenance, or the repair procedures that are used.
Configuration Procedure
MMU IP Settings
Perform the following procedure for MMU IP settings:
- Obtain your UPS components IP settings from IT/network admin.
Note: One static IP address is required for each MMU, as well as an additional static IP for the display. An additional static IP address may be required if the UPS is equipped with the SNMP option.
Refer to following for examples of what IP addresses will look like:
Display IP - 10.140.60.100
MMU1 IP - 10.140.60.101
MMU2 IP - 10.140.60.102
MMU3 IP - 10.140.60.103
Subnet Mask - 255.255.255.0
Default Gateway - 10.140.60.1
- Connect a computer loaded with UPS View to the serial port of the UPS.
Note: The configuration can only be performed with a serial connection. For other information on using UPS View, reference Systems Operation, RENR9558.
- Select Enter Password from the Menu bar in the UPS View window 1. Log in using a Technician level password.
Illustration 1 | g03620419 |
Log in screen page |
- Place the UPS in Bypass. Reference the Operation and Maintenance Manual for your product for instructions on how to perform this step.
Note: The APC board may require being rest after transferring to bypass. Use the "Ctrl-R" command to reset the APC board. There may be need to repeat using the "Ctrl-R" command multiple times, for the APC board to begin responding again.
- To complete the setup of Network Configuration for an individual MMU, refer to the following procedure:
Note: If a system has multiple MMUs, this procedure will need to be completed once for each MMU.
- Select "UPS Settings" from the Menu bar in the UPS View window. A list of choices will drop down. Refer to Illustration 2
- Select the "Network Configuration" (1) choice.
- On the new "Network Configuration" window, enter the correct static "IP Address" provided by the Network Administrator, as shown in example Illustration 3.
Show/hide tableIllustration 3 g03620223
IP Address "Network Configuration" window
- Select the "Send" button on the Network Configurations window. Wait approximately 10 seconds and reset the APC board by using the "Ctrl-R" command.
Note: If the system has multiple MMUs, the procedure will need to be completed for each MMU with a different static "IP Address".
Illustration 2 | g03620730 |
(1) "Network Configuration" selection window |
- To complete the configuration of the display, refer to the following procedure:
- Select "UPS Settings" from the Menu bar in the UPS View window. Refer to Illustration 4
- Select the "Set Display Configuration" (2) choice.
- On the new "Display Configuration" window, select "Color Display Installed" from the drop-down and enter the Display static "IP address" provided by the Network Administrator. Refer to Illustration 5.
Show/hide tableIllustration 5 g03621180
(3) "Send" button
- Select the "Send" button on the "Display Configuration" window. Wait approximately 10 seconds and rest the APC board by using the "Ctrl-R" command.
Illustration 4 | g03621057 |
(2) "Set Display Configuration" selection window |
- Press "ctrl+z" for each MMU to make sure that the information was stored correctly for each MMU. Once confirmed, the "UPS" can be placed back online if desired. Refer to theMaintenance and Operation Manual for the product, for the process to return the "UPS" online.
Touchscreen Configuration
Perform the following procedure for touchscreen configuration:
- Press the Home symbol (4) on the touchscreen.
Note: The flywheels will likely be red in color, and there will be zeros for all the data. That happens because the touchscreen does not know where to look for the MMUs at this time.
Illustration 6 | g03621280 |
(4) Home symbol |
- Press the Key symbol (5) to start the login. In the "User Name" block, enter "Tech". In the "Password" block, enter "makeitgo".
When entered correctly, the "User" block will say "tech".
Illustration 7 | g03621419 |
(5) Key symbol |
- Press the Compass Navigation button (6) .
Pressing the button brings up a drop-down that has "Configuration" at the bottom of the list.
- Select "Configuration" to bring up the screen as shown in Illustration 8.
Illustration 8 | g03621436 |
(7) "Save" buttons (8) "Next Screen" button |
- Verify that the static IP addresses listed match the ones provided to you by the network administrator.
If any errors are found, use this screen to make corrections as needed.
- Press both "Save" buttons (7) .
- Click the "Next Screen" button (8) twice, to get to a screen that looks like Illustration 9, and select the "Reboot" button (9) .
Note: Clicking "Next Screen" button (8) twice, and selecting the "Reboot" button (9) only reboots the display, and does not affect the operation of the UPS.
Illustration 9 | g03621487 |
(9) "Reboot" button |
- When the display is done rebooting, information should be populated for each MMU. If not, recheck that all the numbers have been entered accurately and in the correct places.
Note: The information must be entered correctly, for the UPS system to respond as expected.