Electrical Specification
关于表 1 中所用的首字母缩略词的说明,请参见本出版物的, "术语表"部分。
Show/hide table
UPS 功率,单位:kVA     | 160     | 200     | 250     | 300     | 400     | 500     |
正常交流电输出     | ||||||
导线数     | 3 相/3 线     | |||||
Pn 下的参考电压     | 380 到 415 V     | |||||
参考频率     | 45 Hz 到 66 Hz     | |||||
电流失真(THDI)     | Pn 下通常为 3%     | |||||
功率因子     | > 0.99     | |||||
旁路交流电输入     | ||||||
导线数     | 三相 + 中线     | |||||
Pn 下的参考电压     | 380 到 415 V     | |||||
参考频率     | 45 Hz 到 66 Hz     | |||||
负载输出     | ||||||
导线数     | 三相 + 中线     | |||||
设定相间电压     | 380 V / 400 V / 415 V     | |||||
设定相电压     | 220 V / 230 V / 240 V     | |||||
电压变化     | +/- 1%     | |||||
可调频率和公差(蓄电池供电)     | 50 Hz 或者 60 Hz +/- 0.1 Hz     | |||||
0 至 100% 负载阶跃冲击的电压变化     | +/- 1%     | |||||
容许过载     | 150% 30 秒,125% 10 分钟     | |||||
THDU 非线性负载的相间电压及相电压     | < 2% 相间电压     | |||||
蓄电池     | ||||||
标准蓄电池技术     | 密封式铅酸蓄电池(气体重组)(阀控式铅酸型)     |
Show/hide table
UPS 功率,单位:kVA     | 160     | 200     | 250     | 300     | 400     | 500     | ||||||
    | Pn/2     | Pn     | Pn/2     | Pn     | Pn/2     | Pn     | Pn/2     | Pn     | Pn/2     | Pn     | Pn/2     | Pn     |
有效功率(kW)     | 72     | 144     | 90     | 180     | 112     | 225     | 135     | 270     | 180     | 360     | 225     | 450     |
效率     | 92.0     | 93.2     | 93.0     | 93.0     | 93.2     | 93.8     | 93.5     | 93.6     | 94.1     | 94.1     | 94.3     | 94.3     |
热损失(kW)     | 6.3     | 10.5     | 6.8     | 13.5     | 8.2     | 14.9     | 9.4     | 18.6     | 11.3     | 22.6     | 13.6     | 27.2     |
热损失(cal/s)     | 1496     | 2511     | 1619     | 3238     | 1962     | 3554     | 2243     | 4449     | 2697     | 5395     | 3250     | 6501     |
储存温度范围     | −25° C (−13° F) 到 45° C (113° F)     |
|||||||||||
Pn 下的操作温度范围     | 0° C (32° F) 到 35° C (95° F)     |
|||||||||||
相对湿度     | 45% 至 75%     | |||||||||||
未降额的最大作业高度     | 1000 m     | |||||||||||
调整后的噪声级分贝(dBA)     | 75     |
Show/hide table
蓄电池特征     | |||
    | 密封式铅酸型     | 开放式铅酸型     | NiCd     |
电池最小/最大数目     | 44/48     | 44/48     | 428/468     |
每个电池的浮动电压     | 2.27 V     | 2.2 V     | 1.4 V     |
最低/最高浮动电压     | 600 V / 654 V     | 581 V / 634 V     | 600 V / 655 V     |
每个电池的最低电压     | 1.65 到 1.9 V     | 1.65 到 1.9 V     | 最小阈值 1.1 V     |
Caterpillar Information System:
CG137-08 and CG137-12 Industrial Engines Cylinder Liner Projection - Inspect
C11 and C13 Industrial Engines Engine Speed/Timing Sensor - Clean/Inspect
CG137-08 and CG137-12 Industrial Engines Main Bearings - Inspect
C4.4 Industrial Engine Temperature Sensor (DPF Inlet)
C4.4 Industrial Engine Diesel Particulate Filter
2011/01/27 A New Pressure Regulating Valve Is Used for Air Starting on some 3500B Marine Engines {108A, 1462}
Using the 8T-2700 Blowby/Air Flow Indicator{0781, 0785, 1317} Using the 8T-2700 Blowby/Air Flow Indicator{0781, 0785, 1317}
C11 and C13 Industrial Engines Engine Oil and Filter - Change
C11 and C13 Industrial Engines Refill Capacities
UPSB505 Uninterruptible Power Supply Component Description
CG137-08 and CG137-12 Industrial Engines Exhaust Temperature Module - Test
C11 and C13 Industrial Engines Configuration Parameters
C11 and C13 Industrial Engines Grounding Stud - Inspect/Clean/Tighten
2011/02/09 New Configuration Feature for the Remote Advisor Panel for Some G3500 Petroleum Engines with NO<SUB>x</SUB> Feedback {1901, 1920}
3508B, 3508C, 3512B, 3512C, 3516B and and 3516C Marine Engines Control Panel
2011/02/11 Redesigned Fluid Sampling Valves Are Now Available for All Cat Products {7542}
C13 and C15 Generator Set Engines Fuel System
C280 Marine, Marine Auxiliary, and Petroleum Engines Control Panel - Inspect/Test
UPSB505 Uninterruptible Power Supply Product Location
PM3516 Power Modules Parallel Operation
C13 and C15 Generator Set Engines Air Inlet and Exhaust System
3512C and 3516C Marine Auxiliary and Generator Set Engines Coolant Level - Check
PM3516 Power Modules Battery Charger - Check
345D, 349D and 349D2 Excavator Machine System Specifications Pilot Lines