Circuit Breaker Recommendation
上游保护
Show/hide table
在维护或修理发电设备时: 确保装置在脱机状态(脱开公用电网或其它发电设备),并锁定或者系上标签不准操作(DO NOT OPERATE)。 拆下所有保险丝。 |
表 1 中所列的断路器符合 UPS 内安装的保险丝的额定容量要求。 将每个断路器上贴上包含以下声明的标签:
"在进行此电路的工作前,隔离不间断电源(UPS)。"
Show/hide table
UPS 的额定功率     | 上游断路器     | ||
---|---|---|---|
分离正常交流输入 | 分离旁路交流输入     | 公共旁路和正常交流输入     | |
20 kVA     | C60L - 50 A     | NS100N 4P-TM100A     | NS100N 4P-TM100A     |
30 kVA     | C60L - 63 A     | NS100N 4P-TM100A     | NS100N 4P-TM100A     |
40 kVA     | NS100N 3P-TM80A     | NS100N 4P-TM100A     | NS100N 4P-TM100A     |
60 kVA     | NS125E 3P-TM125A     | NS125E 4P-TM125A     | NS125E 4P-TM125A     |
80 kVA     | NS160N 3P-TM160A     | NS160N 4P-TM160A     | NS160N 4P-TM160A     |
100 kVA     | NS250N 3P-TM200A     | NS250N 4P-TM250A     | NS250N 4P-TM250A     |
120 kVA     | NS250N 3P-TM250A     | NS250N 4P-TM250A     | NS250N 4P-TM250A     |
下游保护
Show/hide table
UPS 的额定功率     | 下游断路器     |
---|---|
20-30-40 kVA     | C60N - B - 40A     |
C60N - C - 20A | |
60-80 kVA     | C60N - C - 32A     |
C60N - B - 63A | |
100-120 kVA     | C120N - B - 80A     |
C60N - C - 40A | |
NS100 - TMG - 63A |
使用注释
所示保护可确保将处于 UPS 下游的每条输出电路区分开。 无论供电电源是正常的交流输入还是旁路交流输入,电路都可获得保护。
如果未安装正确的断路器,则输出电路中短路可能导致供电中断。 而这种供电中断可能在全部其它输出电路上持续超过 20 毫秒。
注: 有关公共交流输入或分离交流输入,参见参考一章"电气规格"中的简化示意图。 这些示意图说明了保护装置的位置和 UPS 内部保险丝的特性。 这些示意图还说明了在过载情况下 UPS 的线路电流。
地线漏电电流
地线漏电电流为 1 安。
Caterpillar Information System:
UPSB125 Uninterruptible Power Supply Communication Card Installation
UPSB125 Uninterruptible Power Supply Component Description
UPSB125 Uninterruptible Power Supply Component Location
UPSB125 Uninterruptible Power Supply Display Messages
UPSB125 Uninterruptible Power Supply Electrical Specification
UPSB125 Uninterruptible Power Supply External Battery Cabinet Connection
3508, 3512 and 3516 Generator Set Engines Air Starting Motor - Remove and Install
UPSB125 Uninterruptible Power Supply External Bypass Connection
UPSB125 Uninterruptible Power Supply General Hazard Information
UPSB125 Uninterruptible Power Supply General Information
UPSB125 Uninterruptible Power Supply Glossary
UPSB125 Uninterruptible Power Supply Isolation Transformer Connection
UPSB125 Uninterruptible Power Supply Cable Size Requirement
UPSB125 Uninterruptible Power Supply Cable Routing
UPSB125 Uninterruptible Power Supply Battery Service
UPSB125 Uninterruptible Power Supply Battery Packing Material Removal
UPSB125 Uninterruptible Power Supply Battery Circuit Breaker Installation
UPSB125 Uninterruptible Power Supply Auxiliary Connection
UPSB125 Uninterruptible Power Supply Alarm Operation
3508, 3512 and 3516 Generator Set Engines Air Starting Motor - Disassemble
Reuse and Salvage of Water Pumps {1361} Reuse and Salvage of Water Pumps {1361}
793F Off-Highway Truck Engine Supplement Modular Front End - Remove and Install
3508, 3512 and 3516 Generator Set Engines Air Starting Motor - Assemble
349F and 352F Excavators Indicators and Gauges - Test