If the generator is received during cold weather, allow the unit to reach room temperature before you remove the protective packing material. Warming the generator to room temperature will prevent the following problems:
- Water condensation on cold surfaces
- Early failures due to wet windings
- Early failures due to wet insulating materials
Improper lift rigging can allow unit to tumble causing injury and damage. |
NOTICE |
---|
Do not use the engine lifting eyes to remove the engine and generator together. |
Unpack the equipment with care in order to avoid scratching painted surfaces. Move the unit to the mounting location. Follow the instructions under the "Product Lifting" topic. The hoist and the hoist cables should have a rating that is greater than the weight of the generator.
The location of the generator must comply with all local regulations. The location of the generator must also comply with all special industrial regulations. Locate the generator in an area that meets the following requirements:
- Clean
- Dry
- Well ventilated
- Easily accessible for inspection and maintenance
Do not obstruct air inlet openings. Do not obstruct discharge openings. Air flow must reach these openings. If the generator is exposed to harsh environmental conditions, the generator can be modified in the field in order to add filters and space heaters. In addition, a more rigid periodic maintenance schedule should be established.
Note: For further information concerning the installation of this generator set, see the appropriate Application and Installation Guide.
The output to the load of the generator should always be protected with an overload protection device such as a circuit breaker or fuses. Fuses should be sized by using the lowest possible current rating. However, this rating must be above the current rating for full load. A common recommendation is 115 percent of rated current. Determine the size of fuses or determine the size of circuit breakers in accordance with NEMA, IEC, and Local Electrical Codes.
If the generator is not installed immediately, refer to the "Product Storage" topic for the proper considerations for storing the unit.