UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


Transfer to Bypass Mode (SMS)

Usage:

UPS 250 APZ

SMS Bypass Cabinet




Illustration 1g03428384

Bypass Cabinets (Front View with Shields)

(1) Bypass switch (optional)

(2) Output switch (optional)

(3) Input switch (optional)

(4) Upper shield

(5) Lower shield

(6) GSM circuit breaker (optional)




Illustration 2g01280608

(7) LCD display

(8) Key switch

(9) Home soft key

------ WARNING! ------

When servicing or repairing electric power generation equipment:

  • Make sure the unit is either locked out or tagged DO NOT OPERATE.

  • Remove all fuses.

  • Make sure the generator engine is stopped.

  • Make sure all batteries are disconnected.

  • Make sure all capacitors are discharged.

  • Make sure residual voltage in the rotor, stator and the generator is discharged.

Failure to do so could result in personal injury or death.

----------------------

System Internal Bypass Procedure

The internal bypass is used when the system voltage must regulate the power to the load, but not protecting the load in a utility outage.

  1. Turn the key switch (8) to the Bypass position at the flywheel cabinet.

  1. Ensure that the UPS is in Bypass mode. Confirm the mode by pressing the "Home" soft key (9) . The "Home" is located on the user interface panel. Observe the status line on the LCD (7) .

The system is now in Internal Bypass.

SMS with Bypass Cabinet

Maintenance Bypass Procedure

Perform the maintenance bypass procedure. The voltage is not regulated and the load is not protected.

  1. Turn the key switch (8) to Bypass position at the flywheel cabinet.

  1. Ensure that the UPS is in Bypass mode. Confirm the mode by pressing the "Home" soft key (9) . The "Home" is located on the user interface panel. Observe the status line on the LCD (7) .


    NOTICE

    If the system does not enter the Bypass mode, Do Not Proceed with this procedure. Equipment damage or load interruption may occur. Contact Technical Support.


    Note: When the flywheel is spinning, the following components are energized: the DC bus, the armature leads and the fuses (armature). In order to brake the flywheel, follow the procedure inSystems Operation, Testing and Adjusting, RENR9988, "System Pre-Shutdown ".

  1. Close the bypass switch (1) that is located in the bypass cabinet.

  1. Open the output switch (2) that is located in the bypass cabinet.

  1. Open the input switch (3) that is located in the bypass cabinet.

The system is now in Maintenance Bypass.

Follow procedures in Systems Operation, Testing and Adjusting, RENR9988, "System Startup (SMS)" to return from maintenance bypass.

SMS without Bypass Cabinet

Maintenance bypass procedure

This procedure is used when there is not a bypass cabinet in order to control the maintenance bypass. Possibly an external wrap-around bypass system is carried out.

  1. Turn the key witch (8) to Bypass position at the flywheel cabinet.

  1. Ensure that the UPS is in Bypass mode. Confirm the mode by pressing the "Home" soft key (9) . The "Home" is located on the user interface panel. Observe the status line on the LCD (7) .


    NOTICE

    If the system does not enter the bypass mode, Do Not Proceed with this procedure. Equipment damage or load interruption may occur. Contact technical support.


    Note: When the flywheel is spinning, the following components are energized: the DC bus, the armature leads and the fuses (armature). In order to brake the flywheel, follow the procedure inSystems Operation, Testing and Adjusting, RENR9988, "System Pre-Shutdown ".

  1. Close the external bypass switch.


    NOTICE

    Make sure that the circuit path to the customer load is unaffected when performing the following steps, so that the load is not dropped.


  1. Remove electrical input to the UPS.

  1. Disconnect the electrical path from the output of the UPS for electrical feedback prevention to the UPS.

    The system is now in maintenance bypass.

Follow procedures in Systems Operation, Testing and Adjusting, RENR9988, "System Startup (SMS)" to return from maintenance bypass.

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Bearing - Replace
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies AC Interface PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Power Distribution PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Interface PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Controller PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Monitor PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies EPO Reset Switch (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Purpose Interface PWA (MMS System Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys 4 Wire Transformer
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (4 Wire Transformer Cabinet)
G3408C and G3412C Engines Accumulator
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Specifications
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Operating Parameters
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys System Fuse (4 Wire Transformer Cabinet)
C15 On-Highway Engine Air Inlet and Exhaust System - Inspect
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Front Door Status Indicator Panel
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Transfer to Bypass Mode (MMS)
2006/10/09 New Test Kits for the Coolant {1395}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Purpose Interface PWA (4 Wire Transformer Cabinet)
3500 Generator Sets with Dynamic Gas Blending Air Shutoff - Test
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermal Switch Monitor PWA
SPF343 and SPF343C Trailer Mounted Pumpers Air Shutoff - Replace
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Controller Board Battery - Replace
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T12 to T16 )
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.