- Electric Power Generation:
- SR4 (S/N: 1DJ1-UP; 1JJ1-UP; 1MS1-UP; 2MM1-UP; 3FF1-UP; 3KJ1-UP; 3YM1-UP; 4LM1-UP; 4SJ1-UP; 5CG1-UP; 5JF1-UP; 5JM1-UP; 5NF1-UP; 5NJ1-UP; 5WF1-UP; 6CG1-UP; 6DF1-UP; 6DG1-UP; 6EG1-UP; 6EJ1-UP; 6FF1-UP; 6GF1-UP; 6HF1-UP; 6JM1-UP; 6YR1-UP; 7AJ1-UP; 7BF1-UP; 7CF1-UP; 7YR1-UP; 8DR1-UP; 8ER1-UP; 8HG1-UP; 8JF1-UP; 8KF1-UP; 8LF1-UP; 9CR1-UP; 9DR1-UP)
- Engine:
- 3208 DI T (S/N: 30A1-UP)
- SR4 PC (S/N: 9EF1-UP)
- SR4 (S/N: 9FF1-UP; 9FG1-UP; 9GF1-UP)
- SR4B (S/N: 1HN1-UP; 2DM1-UP; 2DN1-UP; 2FN1-UP; 2GM1-UP; 2GN1-UP; 2GZ1-UP; 2HN1-UP; 2SN1-UP; 3BM1-UP; 3EN1-UP; 3FN1-UP; 3GN1-UP; 3HN1-UP; 4DM1-UP; 4EN1-UP; 4FN1-UP; 4GN1-UP; 4WN1-UP; 5CK1-UP; 5DM1-UP; 5JW1-UP; 5LF1-UP; 5SN1-UP; 5WN1-UP; 6DW1-UP; 6GM1-UP; 6PK1-UP; 6SN1-UP; 6ZZ1-UP; 7DN1-UP; 7GM1-UP; 7TN1-UP; 8DM1-UP; 8EZ1-UP; 8GK1-UP; 8GW1-UP; 8HM1-UP; 8LZ1-UP; 8NN1-UP; 8PZ1-UP; 8TZ1-UP; 9AZ1-UP; 9CN1-UP; 9DZ1-UP; 9EN1-UP; 9GZ1-UP; 9MZ1-UP; 9RZ1-UP; 9WZ1-UP; 9XZ1-UP; AAD1-UP; AAJ1-UP; AAR1-UP; AAY1-UP)
- 3208 DI STDBY T (S/N: 5YF1-UP)
- 3304 DI (S/N: 83Z1-UP)
- 3304B DI RENTL T (S/N: 9HK1-UP)
- 3306 DI T (S/N: 85Z1-UP)
- 3306B DI STDBY T (S/N: 2AJ1-UP)
- 3306B DI RENTL TA (S/N: 8JJ1-UP)
- 3306B ATAAC (S/N: 9NR1-UP)
- 3406B (S/N: 2WB1-UP; 4JK1-UP; 4RG1-UP)
- 3406C (S/N: 1LS1-UP)
- 3406C TA (S/N: 4ZR1-UP)
- 3408B (S/N: 78Z1-UP)
- 3412C (S/N: 81Z1-UP)
- 3508 (S/N: 1ZF1-UP; 23Z1-UP; 70Z1-UP)
- 3512 (S/N: 24Z1-UP; 3YF1-UP; 67Z1-UP)
- 3516 (S/N: 25Z1-UP; 4XF1-UP; 73Z1-UP)
The following two illustrations that appear in the External Potential Transformer Connections topic of the referenced publication are incorrect:
- Open Delta Configuration of External Potential Transformers on Three-Wire Delta Generator
- Open Delta Configuration of External Potential Transformers on Four-Wire Wye Generator
These illustrations show an incorrect connection between "Phase B" and "F14". Both of these illustrations have been corrected. The correct illustrations will appear in subsequent revisions of SENR5832. The two incorrect illustrations that appear in the referenced publication should be replaced by the following two illustrations.
Illustration 1 | g00584153 |
Open Delta Configuration of External Potential Transformers on Three-Wire Delta Generator This configuration allows the GSC+ to accurately measure power parameters when loads are unbalanced and when circulating current is present. The following real power phases cannot be determined: phase A, phase B and phase C. The following power factor phases cannot be determined: phase A, phase B and phase C. These phases are not shown on the GSC+ display. |
Illustration 2 | g00584154 |
Open Delta Configuration of External Potential Transformers on Four-Wire Wye Generator This configuration does NOT allow the GSC+ to measure all power parameters when loads are unbalanced and neutral current is present. The following real power phases cannot be determined: phase A, phase B and phase C. The following power factor phases cannot be determined: phase A, phase B and phase C. These phases are not shown on the GSC+ display. |