Electronic Modular Control Panel II (EMCP II) For MUI Engines Caterpillar


Modes Of Operation

Usage:

3304 02B

Table 1
Display Area Functions When In Normal Mode, Alarm Mode Or Shutdown Mode (1)    
Item Of Display Area     Normal Mode     Alarm Mode     Shutdown Mode    
Upper Display     AC Data Shown     AC Data Shown (2)     Fault Code Shown    
Lower Display     Engine Data And Relay Status Shown     Engine Data And Relay Status Shown     Engine Data And Relay Status Shown    
Shutdown Indicator/s     All Off     All Off     Flashing    
Fault Alarm Indicators     Off     Flashing (2)     Off    
   
Key Function     Normal Mode     Alarm Mode     Shutdown Mode    
Left Most Key (3)     No Function     No Function     No Function    
Phase Select Key     Selects The AC Phase That Is Shown On The Upper Display     Selects The AC Phase That Is Shown On The Upper Display     No Function    
Engine Meter Key     Stops And Starts The Scrolling Of Engine Conditions On Lower Display     Stops And Starts The Scrolling Of Engine Conditions On Lower Display     Stops And Starts The Scrolling Of Engine Conditions On Lower Display    
Lamp Test Key     Performs A Lamp Test     Performs A Lamp Test     Performs A Lamp Test    
Alarms Code Key     No Function     Shows The Fault Code On The Upper Display     No Function    
Exit Key (3)     No Function     No Function     No Function    
Service Mode Key     Enters The GSC Into Service Mode     Enters The GSC Into Service Mode     No Function    
( 1 ) For a description of the display area functions when in service mode, see Systems Operation, "Service Mode".
( 2 ) When an alarm fault is present, the fault code is shown on the upper display when the alarm codes key is pressed.
( 3 ) This key only functions when in service mode, see Systems Operation, "Service Mode".



Illustration 1g00714615

(1) Dedicated Shutdown Indicators

(2) Fault Shutdown Indicator

(3) Fault Alarm Indicator

(4) Upper Display

(5) Lower Display

(6) Keypad

(7) Scroll Right Key

(8) Phase Select Key And Scroll Up Key

(9) Engine Meter Key And Scroll Down Key

(10) Lamp Test Key And Select Key

(11) Alarm Codes Key And Enter Key

(12) Exit Key

(13) Service Mode Key

The GSC has four modes of operation. A brief description of each mode follows this paragraph. See the individual topic for more detailed information.

Normal Mode - The GSC uses normal mode for the normal operation of the generator set. The operator can identify the normal mode by observing the display area. When the GSC is in the normal mode, all dedicated shutdown indicators are OFF. The fault shutdown indicator is OFF. The fault alarm indicator is OFF and "SERV "is NOT SHOWING on the upper display.

Alarm Mode - If there is an alarm fault, the GSC will automatically go into alarm mode in order to alert the operator. The operator can identify the alarm mode by observing the display area. When the GSC is in alarm mode, the fault alarm indicator is FLASHING. When the alarm codes key is pressed, the diagnostic code will be shown.

Shutdown Mode - If there is a shutdown fault, the GSC will automatically go into shutdown mode in order to alert the operator. The operator can identify the shutdown mode by observing the display area. When the GSC is in shutdown mode, a dedicated shutdown indicator is FLASHING, or the fault shutdown indicator is FLASHING.

Service Mode - The GSC goes into service mode when the operator presses the service mode key on the keypad. The operator can use service mode for the following purposes.

  • Assist with troubleshooting diagnostic codes.

  • Verify the generator set functions.

  • Calibrate the generator set functions.

  • Adjust the generator set functions.

  • Satisfy special applications.

  • Satisfy the needs of the customer.

The operator can identify service mode by observing the display area. When the generator set is in service mode, "SERV" is SHOWN on the upper display.

Note: Service mode can not be entered when the ECS is in the AUTO position.

Caterpillar Information System:

3406E and 3456 Generator Set Engines Engine Oil Cooler - Install
G3500 Engines Turbocharger - Disassemble
G3500 Engines Turbocharger - Install
3114, 3116 and 3126 Industrial, Marine and Generator Set Engines Crankshaft
G3612 and G3616 Engines Air/Fuel Pressure Sensor Module - Remove and Install
3500B and 3500B High Displacement Generator Set Engines Customer Parameters Worksheet
3114, 3116 and 3126 Industrial, Marine and Generator Set Engines Cylinder Block Cover Group
G3606 and G3608 Engines Prechamber Ignition Body - Install
G3606 and G3608 Engines Gas Admission Valve - Install
G3606 and G3608 Engines Exhaust Bypass - Install
3003, 3013, 3014 and 3024 Engines for Caterpillar Built Machines Water Pump - Remove - 3003 Engines
3034 Engine for Caterpillar Built Machines Engine Oil Pump - Remove
G3606 and G3608 Engines Crankcase Cover - Remove and Install
G3606 and G3608 Engines Accessory Module Frame (Front) - Remove
3034 Engine for Caterpillar Built Machines Engine Oil Pump - Install
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Normal Mode
3406E and 3456 Generator Set Engines Engine Oil Cooler - Disassemble
3304B and 3306B Engines for Caterpillar Built Machines Fuel Injection Pump Housing and Governor - Remove
G3500 Engines Turbocharger - Assemble
3500B and 3500B High Displacement Generator Set Engines ECM/Personality Module
G3606 and G3608 Engines Accessory Module Frame (Front) - Install
3114, 3116 and 3126 Industrial, Marine and Generator Set Engines Crankshaft Seals
797 Off-Highway Truck Steering System Bearing Cup Cooling and Installation Procedure
3500B Engines and 3500 Engines with EUI Option Engine Speed/Timing Sensor
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.